-- automatically generated by mosy 7.1 #379 (dbc), do not edit!
|
|
|
|
UPS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
TRAP-TYPE
|
|
FROM RFC-1215
|
|
mib-2, DisplayString
|
|
FROM RFC1213-MIB
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
Gauge, Counter
|
|
FROM RFC1155-SMI;
|
|
|
|
-- created from upsMIB (9402230000Z)
|
|
|
|
upsMIB OBJECT IDENTIFIER ::= { mib-2 33 }
|
|
|
|
PositiveInteger ::=
|
|
INTEGER
|
|
|
|
NonNegativeInteger ::=
|
|
INTEGER
|
|
|
|
upsObjects OBJECT IDENTIFIER ::= { upsMIB 1 }
|
|
|
|
upsIdent OBJECT IDENTIFIER ::= { upsObjects 1 }
|
|
|
|
upsIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the UPS manufacturer."
|
|
::= { upsIdent 1 }
|
|
|
|
upsIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Model designation."
|
|
::= { upsIdent 2 }
|
|
|
|
upsIdentUPSSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS firmware/software version(s). This variable
|
|
may or may not have the same value as
|
|
upsIdentAgentSoftwareVersion in some implementations."
|
|
::= { upsIdent 3 }
|
|
|
|
upsIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS agent software version. This variable may or
|
|
may not have the same value as
|
|
upsIdentUPSSoftwareVersion in some implementations."
|
|
::= { upsIdent 4 }
|
|
|
|
upsIdentName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the UPS. This object should be
|
|
set by the administrator."
|
|
::= { upsIdent 5 }
|
|
|
|
upsIdentAttachedDevices OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the devices attached to the
|
|
output(s) of the UPS. This object should be set by
|
|
the administrator."
|
|
::= { upsIdent 6 }
|
|
|
|
upsBattery OBJECT IDENTIFIER ::= { upsObjects 2 }
|
|
|
|
upsBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
batteryNormal(2),
|
|
batteryLow(3),
|
|
batteryDepleted(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries. A value of batteryNormal
|
|
indicates that the remaining run-time is greater than
|
|
upsConfigLowBattTime. A value of batteryLow indicates
|
|
that the remaining battery run-time is less than or
|
|
equal to upsConfigLowBattTime. A value of
|
|
batteryDepleted indicates that the UPS will be unable
|
|
to sustain the present load when and if the utility
|
|
power is lost (including the possibility that the
|
|
utility power is currently absent and the UPS is
|
|
unable to sustain the output)."
|
|
::= { upsBattery 1 }
|
|
|
|
upsSecondsOnBattery OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS seconds
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the unit is on battery power, the elapsed time
|
|
since the UPS last switched to battery power, or the
|
|
time since the network management subsystem was last
|
|
restarted, whichever is less. Zero shall be returned
|
|
if the unit is not on battery power."
|
|
::= { upsBattery 2 }
|
|
|
|
upsEstimatedMinutesRemaining OBJECT-TYPE
|
|
SYNTAX PositiveInteger -- UNITS minutes
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the time to battery charge depletion
|
|
under the present load conditions if the utility power
|
|
is off and remains off, or if it were to be lost and
|
|
remain off."
|
|
::= { upsBattery 3 }
|
|
|
|
upsEstimatedChargeRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS percent
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the battery charge remaining expressed
|
|
as a percent of full charge."
|
|
::= { upsBattery 4 }
|
|
|
|
upsBatteryVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Volt DC
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present battery voltage."
|
|
::= { upsBattery 5 }
|
|
|
|
upsBatteryCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER (-2147483648..2147483647) -- UNITS 0.1 Amp DC
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present battery current."
|
|
::= { upsBattery 6 }
|
|
|
|
upsBatteryTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (-2147483648..2147483647) -- UNITS degrees Centigrade
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ambient temperature at or near the UPS Battery
|
|
casing."
|
|
::= { upsBattery 7 }
|
|
|
|
upsInput OBJECT IDENTIFIER ::= { upsObjects 3 }
|
|
|
|
upsInputLineBads OBJECT-TYPE
|
|
SYNTAX Counter
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A count of the number of times the input entered an
|
|
out-of-tolerance condition as defined by the
|
|
manufacturer. This count is incremented by one each
|
|
time the input transitions from zero out-of-tolerance
|
|
lines to one or more input lines out-of-tolerance."
|
|
::= { upsInput 1 }
|
|
|
|
upsInputNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of input lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
input table."
|
|
::= { upsInput 2 }
|
|
|
|
upsInputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of input table entries. The number of entries
|
|
is given by the value of upsInputNumLines."
|
|
::= { upsInput 3 }
|
|
|
|
upsInputEntry OBJECT-TYPE
|
|
SYNTAX UpsInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular input line."
|
|
INDEX { upsInputLineIndex }
|
|
::= { upsInputTable 1 }
|
|
|
|
UpsInputEntry ::=
|
|
SEQUENCE {
|
|
upsInputLineIndex
|
|
PositiveInteger,
|
|
|
|
upsInputFrequency
|
|
NonNegativeInteger,
|
|
|
|
upsInputVoltage
|
|
NonNegativeInteger,
|
|
|
|
upsInputCurrent
|
|
NonNegativeInteger,
|
|
|
|
upsInputTruePower
|
|
NonNegativeInteger
|
|
}
|
|
|
|
upsInputLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The input line identifier."
|
|
::= { upsInputEntry 1 }
|
|
|
|
upsInputFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present input frequency."
|
|
::= { upsInputEntry 2 }
|
|
|
|
upsInputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage."
|
|
::= { upsInputEntry 3 }
|
|
|
|
upsInputCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input current."
|
|
::= { upsInputEntry 4 }
|
|
|
|
upsInputTruePower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Watts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input true power."
|
|
::= { upsInputEntry 5 }
|
|
|
|
upsOutput OBJECT IDENTIFIER ::= { upsObjects 4 }
|
|
|
|
upsOutputSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
none(2),
|
|
normal(3),
|
|
bypass(4),
|
|
battery(5),
|
|
booster(6),
|
|
reducer(7)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present source of output power. The enumeration
|
|
none(2) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker."
|
|
::= { upsOutput 1 }
|
|
|
|
upsOutputFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output frequency."
|
|
::= { upsOutput 2 }
|
|
|
|
upsOutputNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of output lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
output table."
|
|
::= { upsOutput 3 }
|
|
|
|
upsOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of output table entries. The number of
|
|
entries is given by the value of upsOutputNumLines."
|
|
::= { upsOutput 4 }
|
|
|
|
upsOutputEntry OBJECT-TYPE
|
|
SYNTAX UpsOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular output line."
|
|
INDEX { upsOutputLineIndex }
|
|
::= { upsOutputTable 1 }
|
|
|
|
UpsOutputEntry ::=
|
|
SEQUENCE {
|
|
upsOutputLineIndex
|
|
PositiveInteger,
|
|
|
|
upsOutputVoltage
|
|
NonNegativeInteger,
|
|
|
|
upsOutputCurrent
|
|
NonNegativeInteger,
|
|
|
|
upsOutputPower
|
|
NonNegativeInteger,
|
|
|
|
upsOutputPercentLoad
|
|
INTEGER
|
|
}
|
|
|
|
upsOutputLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output line identifier."
|
|
::= { upsOutputEntry 1 }
|
|
|
|
upsOutputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output voltage."
|
|
::= { upsOutputEntry 2 }
|
|
|
|
upsOutputCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output current."
|
|
::= { upsOutputEntry 3 }
|
|
|
|
upsOutputPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Watts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output true power."
|
|
::= { upsOutputEntry 4 }
|
|
|
|
upsOutputPercentLoad OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS percent
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The percentage of the UPS power capacity presently
|
|
being used on this output line, i.e., the greater of
|
|
the percent load of true power capacity and the
|
|
percent load of VA."
|
|
::= { upsOutputEntry 5 }
|
|
|
|
upsBypass OBJECT IDENTIFIER ::= { upsObjects 5 }
|
|
|
|
upsBypassFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass frequency."
|
|
::= { upsBypass 1 }
|
|
|
|
upsBypassNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of bypass lines utilized in this device.
|
|
This entry indicates the number of rows in the bypass
|
|
table."
|
|
::= { upsBypass 2 }
|
|
|
|
upsBypassTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsBypassEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of bypass table entries. The number of
|
|
entries is given by the value of upsBypassNumLines."
|
|
::= { upsBypass 3 }
|
|
|
|
upsBypassEntry OBJECT-TYPE
|
|
SYNTAX UpsBypassEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular bypass input."
|
|
INDEX { upsBypassLineIndex }
|
|
::= { upsBypassTable 1 }
|
|
|
|
UpsBypassEntry ::=
|
|
SEQUENCE {
|
|
upsBypassLineIndex
|
|
PositiveInteger,
|
|
|
|
upsBypassVoltage
|
|
NonNegativeInteger,
|
|
|
|
upsBypassCurrent
|
|
NonNegativeInteger,
|
|
|
|
upsBypassPower
|
|
NonNegativeInteger
|
|
}
|
|
|
|
upsBypassLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line identifier."
|
|
::= { upsBypassEntry 1 }
|
|
|
|
upsBypassVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass voltage."
|
|
::= { upsBypassEntry 2 }
|
|
|
|
upsBypassCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass current."
|
|
::= { upsBypassEntry 3 }
|
|
|
|
upsBypassPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Watts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present true power conveyed by the bypass."
|
|
::= { upsBypassEntry 4 }
|
|
|
|
upsAlarm OBJECT IDENTIFIER ::= { upsObjects 6 }
|
|
|
|
upsAlarmsPresent OBJECT-TYPE
|
|
SYNTAX Gauge
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present number of active alarm conditions."
|
|
::= { upsAlarm 1 }
|
|
|
|
upsAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of alarm table entries. The table contains
|
|
zero, one, or many rows at any moment, depending upon
|
|
the number of alarm conditions in effect. The table
|
|
is initially empty at agent startup. The agent
|
|
creates a row in the table each time a condition is
|
|
detected and deletes that row when that condition no
|
|
longer pertains. The agent creates the first row with
|
|
upsAlarmId equal to 1, and increments the value of
|
|
upsAlarmId each time a new row is created, wrapping to
|
|
the first free value greater than or equal to 1 when
|
|
the maximum value of upsAlarmId would otherwise be
|
|
exceeded. Consequently, after multiple operations,
|
|
the table may become sparse, e.g., containing entries
|
|
for rows 95, 100, 101, and 203 and the entries should
|
|
not be assumed to be in chronological order because
|
|
upsAlarmId might have wrapped.
|
|
|
|
Alarms are named by an AutonomousType (OBJECT
|
|
IDENTIFIER), upsAlarmDescr, to allow a single table to
|
|
reflect well known alarms plus alarms defined by a
|
|
particular implementation, i.e., as documented in the
|
|
private enterprise MIB definition for the device. No
|
|
two rows will have the same value of upsAlarmDescr,
|
|
since alarms define conditions. In order to meet this
|
|
requirement, care should be taken in the definition of
|
|
alarm conditions to insure that a system cannot enter
|
|
the same condition multiple times simultaneously.
|
|
|
|
The number of rows in the table at any given time is
|
|
reflected by the value of upsAlarmsPresent."
|
|
::= { upsAlarm 2 }
|
|
|
|
upsAlarmEntry OBJECT-TYPE
|
|
SYNTAX UpsAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
|
|
|
|
|
|
|
|
|
|
particular alarm."
|
|
INDEX { upsAlarmId }
|
|
::= { upsAlarmTable 1 }
|
|
|
|
UpsAlarmEntry ::=
|
|
SEQUENCE {
|
|
upsAlarmId
|
|
PositiveInteger,
|
|
|
|
upsAlarmDescr
|
|
OBJECT IDENTIFIER,
|
|
|
|
upsAlarmTime
|
|
PositiveInteger
|
|
}
|
|
|
|
upsAlarmId OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition. This
|
|
value must remain constant."
|
|
::= { upsAlarmEntry 1 }
|
|
|
|
upsAlarmDescr OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A reference to an alarm description object. The
|
|
object referenced should not be accessible, but rather
|
|
be used to provide a unique description of the alarm
|
|
condition."
|
|
::= { upsAlarmEntry 2 }
|
|
|
|
upsAlarmTime OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of sysUpTime when the alarm condition was
|
|
detected. If the alarm condition was detected at the
|
|
time of agent startup and presumably existed before
|
|
agent startup, the value of upsAlarmTime shall equal
|
|
0."
|
|
::= { upsAlarmEntry 3 }
|
|
|
|
upsWellKnownAlarms OBJECT IDENTIFIER ::= { upsAlarm 3 }
|
|
|
|
upsAlarmBatteryBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms 1 }
|
|
|
|
upsAlarmOnBattery OBJECT IDENTIFIER ::= { upsWellKnownAlarms 2 }
|
|
|
|
upsAlarmLowBattery OBJECT IDENTIFIER ::= { upsWellKnownAlarms 3 }
|
|
|
|
upsAlarmDepletedBattery OBJECT IDENTIFIER ::= { upsWellKnownAlarms 4 }
|
|
|
|
upsAlarmTempBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms 5 }
|
|
|
|
upsAlarmInputBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms 6 }
|
|
|
|
upsAlarmOutputBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms 7 }
|
|
|
|
upsAlarmOutputOverload OBJECT IDENTIFIER ::= { upsWellKnownAlarms 8 }
|
|
|
|
upsAlarmOnBypass OBJECT IDENTIFIER ::= { upsWellKnownAlarms 9 }
|
|
|
|
upsAlarmBypassBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms 10 }
|
|
|
|
upsAlarmOutputOffAsRequested OBJECT IDENTIFIER ::= { upsWellKnownAlarms 11 }
|
|
|
|
upsAlarmUpsOffAsRequested OBJECT IDENTIFIER ::= { upsWellKnownAlarms 12 }
|
|
|
|
upsAlarmChargerFailed OBJECT IDENTIFIER ::= { upsWellKnownAlarms 13 }
|
|
|
|
upsAlarmUpsOutputOff OBJECT IDENTIFIER ::= { upsWellKnownAlarms 14 }
|
|
|
|
upsAlarmUpsSystemOff OBJECT IDENTIFIER ::= { upsWellKnownAlarms 15 }
|
|
|
|
upsAlarmFanFailure OBJECT IDENTIFIER ::= { upsWellKnownAlarms 16 }
|
|
|
|
upsAlarmFuseFailure OBJECT IDENTIFIER ::= { upsWellKnownAlarms 17 }
|
|
|
|
upsAlarmGeneralFault OBJECT IDENTIFIER ::= { upsWellKnownAlarms 18 }
|
|
|
|
upsAlarmDiagnosticTestFailed OBJECT IDENTIFIER ::= { upsWellKnownAlarms 19 }
|
|
|
|
upsAlarmCommunicationsLost OBJECT IDENTIFIER ::= { upsWellKnownAlarms 20 }
|
|
|
|
upsAlarmAwaitingPower OBJECT IDENTIFIER ::= { upsWellKnownAlarms 21 }
|
|
|
|
upsAlarmShutdownPending OBJECT IDENTIFIER ::= { upsWellKnownAlarms 22 }
|
|
|
|
upsAlarmShutdownImminent OBJECT IDENTIFIER ::= { upsWellKnownAlarms 23 }
|
|
|
|
upsAlarmTestInProgress OBJECT IDENTIFIER ::= { upsWellKnownAlarms 24 }
|
|
|
|
upsControl OBJECT IDENTIFIER ::= { upsObjects 8 }
|
|
|
|
upsShutdownType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
output(1),
|
|
system(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object determines the nature of the action to be
|
|
taken at the time when the countdown of the
|
|
|
|
|
|
|
|
|
|
|
|
upsShutdownAfterDelay and upsRebootWithDuration
|
|
objects reaches zero.
|
|
|
|
Setting this object to output(1) indicates that
|
|
shutdown requests should cause only the output of the
|
|
UPS to turn off. Setting this object to system(2)
|
|
indicates that shutdown requests will cause the entire
|
|
UPS system to turn off."
|
|
::= { upsControl 1 }
|
|
|
|
upsShutdownAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS seconds
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will shutdown (i.e., turn off)
|
|
either the UPS output or the UPS system (as determined
|
|
by the value of upsShutdownType at the time of
|
|
shutdown) after the indicated number of seconds, or
|
|
less if the UPS batteries become depleted. Setting
|
|
this object to 0 will cause the shutdown to occur
|
|
immediately. Setting this object to -1 will abort the
|
|
countdown. If the system is already in the desired
|
|
state at the time the countdown reaches 0, then
|
|
nothing will happen. That is, there is no additional
|
|
action at that time if upsShutdownType = system and
|
|
the system is already off. Similarly, there is no
|
|
additional action at that time if upsShutdownType =
|
|
output and the output is already off. When read,
|
|
upsShutdownAfterDelay will return the number of
|
|
seconds remaining until shutdown, or -1 if no shutdown
|
|
countdown is in effect. On some systems, if the agent
|
|
is restarted while a shutdown countdown is in effect,
|
|
the countdown may be aborted. Sets to this object
|
|
override any upsShutdownAfterDelay already in effect."
|
|
::= { upsControl 2 }
|
|
|
|
upsStartupAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS seconds
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will start the output after the
|
|
indicated number of seconds, including starting the
|
|
UPS, if necessary. Setting this object to 0 will
|
|
cause the startup to occur immediately. Setting this
|
|
|
|
|
|
|
|
|
|
|
|
object to -1 will abort the countdown. If the output
|
|
is already on at the time the countdown reaches 0,
|
|
then nothing will happen. Sets to this object
|
|
override the effect of any upsStartupAfterDelay
|
|
countdown or upsRebootWithDuration countdown in
|
|
progress. When read, upsStartupAfterDelay will return
|
|
the number of seconds until startup, or -1 if no
|
|
startup countdown is in effect. If the countdown
|
|
expires during a utility failure, the startup shall
|
|
not occur until the utility power is restored. On
|
|
some systems, if the agent is restarted while a
|
|
startup countdown is in effect, the countdown is
|
|
aborted."
|
|
::= { upsControl 3 }
|
|
|
|
upsRebootWithDuration OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS seconds
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will immediately shutdown (i.e.,
|
|
turn off) either the UPS output or the UPS system (as
|
|
determined by the value of upsShutdownType at the time
|
|
of shutdown) for a period equal to the indicated
|
|
number of seconds, after which time the output will be
|
|
started, including starting the UPS, if necessary. If
|
|
the number of seconds required to perform the request
|
|
is greater than the requested duration, then the
|
|
requested shutdown and startup cycle shall be
|
|
performed in the minimum time possible, but in no case
|
|
shall this require more than the requested duration
|
|
plus 60 seconds. When read, upsRebootWithDuration
|
|
shall return the number of seconds remaining in the
|
|
countdown, or -1 if no countdown is in progress. If
|
|
the startup should occur during a utility failure, the
|
|
startup shall not occur until the utility power is
|
|
restored."
|
|
::= { upsControl 4 }
|
|
|
|
upsAutoRestart OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object to 'on' will cause the UPS system
|
|
to restart after a shutdown if the shutdown occurred
|
|
during a power loss as a result of either a
|
|
upsShutdownAfterDelay or an internal battery depleted
|
|
condition. Setting this object to 'off' will prevent
|
|
the UPS system from restarting after a shutdown until
|
|
an operator manually or remotely explicitly restarts
|
|
it. If the UPS is in a startup or reboot countdown,
|
|
then the UPS will not restart until that delay has
|
|
been satisfied."
|
|
::= { upsControl 5 }
|
|
|
|
upsConfig OBJECT IDENTIFIER ::= { upsObjects 9 }
|
|
|
|
upsConfigInputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal input voltage. On those
|
|
systems which support read-write access to this
|
|
object, if there is an attempt to set this variable to
|
|
a value that is not supported, the request must be
|
|
rejected and the agent shall respond with an
|
|
appropriate error message, i.e., badValue for SNMPv1,
|
|
or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 1 }
|
|
|
|
upsConfigInputFreq OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The nominal input frequency. On those systems which
|
|
support read-write access to this object, if there is
|
|
an attempt to set this variable to a value that is not
|
|
supported, the request must be rejected and the agent
|
|
shall respond with an appropriate error message, i.e.,
|
|
badValue for SNMPv1, or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 2 }
|
|
|
|
upsConfigOutputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output voltage. On
|
|
those systems which support read-write access to this
|
|
object, if there is an attempt to set this variable to
|
|
a value that is not supported, the request must be
|
|
rejected and the agent shall respond with an
|
|
appropriate error message, i.e., badValue for SNMPv1,
|
|
or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 3 }
|
|
|
|
upsConfigOutputFreq OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The nominal output frequency. On those systems which
|
|
support read-write access to this object, if there is
|
|
an attempt to set this variable to a value that is not
|
|
supported, the request must be rejected and the agent
|
|
shall respond with an appropriate error message, i.e.,
|
|
badValue for SNMPv1, or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 4 }
|
|
|
|
upsConfigOutputVA OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Volt-Amps
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal Volt-Amp rating."
|
|
::= { upsConfig 5 }
|
|
|
|
upsConfigOutputPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Watts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal true power rating."
|
|
::= { upsConfig 6 }
|
|
|
|
upsConfigLowBattTime OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS minutes
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of upsEstimatedMinutesRemaining at which a
|
|
lowBattery condition is declared. For agents which
|
|
support only discrete (discontinuous) values, then the
|
|
agent shall round up to the next supported value. If
|
|
the requested value is larger than the largest
|
|
supported value, then the largest supported value
|
|
shall be selected."
|
|
::= { upsConfig 7 }
|
|
|
|
upsConfigAudibleStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2),
|
|
muted(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The requested state of the audible alarm. When in
|
|
the disabled state, the audible alarm should never
|
|
sound. The enabled state is self-describing. Setting
|
|
this object to muted(3) when the audible alarm is
|
|
sounding shall temporarily silence the alarm. It will
|
|
remain muted until it would normally stop sounding and
|
|
the value returned for read operations during this
|
|
period shall equal muted(3). At the end of this
|
|
period, the value shall revert to enabled(2). Writes
|
|
of the value muted(3) when the audible alarm is not
|
|
sounding shall be accepted but otherwise shall have no
|
|
effect."
|
|
::= { upsConfig 8 }
|
|
|
|
upsConfigLowVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum input line voltage allowed before the UPS
|
|
system transfers to battery backup."
|
|
::= { upsConfig 9 }
|
|
|
|
upsConfigHighVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum line voltage allowed before the UPS
|
|
system transfers to battery backup."
|
|
::= { upsConfig 10 }
|
|
|
|
upsTraps OBJECT IDENTIFIER ::= { upsMIB 2 }
|
|
|
|
upsTrapOnBattery TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
VARIABLES { upsEstimatedMinutesRemaining, upsSecondsOnBattery,
|
|
upsConfigLowBattTime }
|
|
DESCRIPTION
|
|
"The UPS is operating on battery power. This trap is
|
|
persistent and is resent at one minute intervals until
|
|
the UPS either turns off or is no longer running on
|
|
battery."
|
|
::= 1
|
|
|
|
upsTrapTestCompleted TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"This trap is sent upon completion of a UPS diagnostic
|
|
test."
|
|
::= 2
|
|
|
|
upsTrapAlarmEntryAdded TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"This trap is sent each time an alarm is inserted into
|
|
to the alarm table. It is sent on the insertion of
|
|
|
|
all alarms except for upsAlarmOnBattery and
|
|
upsAlarmTestInProgress."
|
|
::= 3
|
|
|
|
upsTrapAlarmEntryRemoved TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"This trap is sent each time an alarm is removed from
|
|
the alarm table. It is sent on the removal of all
|
|
alarms except for upsAlarmTestInProgress."
|
|
::= 4
|
|
|
|
|
|
END
|