XUPS-MIB DEFINITIONS ::= BEGIN
|
||
|
||
-- Revised February 25, 1993
|
||
-- Revised June 21, 1993
|
||
-- Revised (Variable types of ) August 5, 1993
|
||
-- Revised August 16, 1993 - added units of measure
|
||
-- Added Event History to Alarm Group and get/set time/date.
|
||
-- Cleanup for final release. 9/3/93
|
||
|
||
-- Release Version 0.91 9/17/93
|
||
-- Release Version 1.00 11/16/93
|
||
|
||
-- Changes for Release Version 2.00 9/7/94
|
||
-- 1) Renamed UPS-MIB to XUPS-MIB and all names from upsVariable
|
||
-- to xupsVariable to avoid conflicts with RFC 1628 Standard UPS MIB names
|
||
-- 2) Renamed all traps from upsName to xupstName to avoid conflicts with
|
||
-- similar alarm names
|
||
-- 3) Added well known alarms and traps:
|
||
-- BreakerOpen, AlarmEntryAdded, AlarmEntryRemoved
|
||
-- 4) Deprecated xupsControlOutputOnTrapDelay
|
||
-- 5) Added xupsTrapControl group
|
||
-- 6) enumerated the value startTest for xupsTestBattery
|
||
-- 7) Defined oid values to use for sysObjectId
|
||
|
||
-- Changes for Release Version 2.10 11/1/94
|
||
-- 1) Corrected type of xupsAlarms, xupsAlarmNumEvents (Gauge)
|
||
-- 2) Defined three trap sources, which differ in their descriptions
|
||
-- of trap variables (none, Defined, defined plus Port N Interface vars)
|
||
-- 3) Clarified AlarmEvent order and numbering
|
||
|
||
-- Changes for Release Version 2.11 3/30/95
|
||
-- 1) Removed references to version 2.00 MIB files
|
||
-- 2) Added range declarations for appropriate objects
|
||
-- 3) Added Object IDs for new products
|
||
|
||
-- Changes for Release Version 2.20 8/29/96
|
||
-- 1) Corrected upper Integer range from 2147483648 to 2147483647
|
||
-- 2) Added xupsEnvironment group and its objects and alarm xupsAmbientTempBad
|
||
-- 3) Added xupsBatteryAbmStatus to monitor Advanced Battery Management status
|
||
-- 4) Added well-known alarms from RFC 1628 which weren't previously supported:
|
||
-- xupsAlarmBatteryBad, xupsOutputOffAsRequested, xupsDiagnosticTestFailed,
|
||
-- xupsCommunicationsLost, xupsUpsShutdownPending, xupsAlarmTestInProgress
|
||
-- 5) Added Defined and PortN (but not Basic) type traps for above alarms
|
||
-- 6) Added xupsControlToBypassDelay to allow Go To Bypass command.
|
||
|
||
-- Changes for Release Version 2.21 5/19/99
|
||
-- Renaming from Exide Electronics to Powerware Corporation
|
||
|
||
-- Changes for Release Version 3.00 3-Apr-02 Connectivity Systems Group,
|
||
-- Power Systems Division, Invensys
|
||
-- 1) Rolled in Receptacle Control extensions from separate file
|
||
-- 2) Added Topology group objects
|
||
-- 3) Added new var xupsOutputSource, which extends upsOutputSource
|
||
-- 4) Added new var xupsAlarmEventMsg to replace the other deprecated xAEEntry vars
|
||
|
||
-- Changes for Release Version 3.01 15-Aug-02 Connectivity Systems Group,
|
||
-- Powerware, Power Systems Division, Invensys
|
||
-- 1) Added new vars xupsConfigLow- and -HighOutputVoltageLimit.
|
||
|
||
-- Changes for Release Version 3.02 06-Oct-02 Connectivity Systems Group,
|
||
-- Powerware, Power Systems Division, Invensys
|
||
-- To support the ConnectUPS Web/SNMP card's ability to monitor an external contact,
|
||
-- the following traps were added:
|
||
-- 1) Added new trap xupstdContactAlarmActive in xupsTrapDefined
|
||
-- 2) Added new trap xupstdContactAlarmInactive in xupsTrapDefined
|
||
--
|
||
-- These are added to support the ConnectUPS Web/SNMP card's ability to monitor
|
||
-- a single contact closure (firmware and custom cable required)
|
||
|
||
-- Changes for Release Version 3.03 05-Feb-03 Connectivity Systems Group,
|
||
-- Powerware, Invensys Energy Systems
|
||
-- 1) To support the ability to monitor additional external contacts,
|
||
-- the var lists of the xupstdContactActiveNotice and
|
||
-- xupstdContactInactiveNotice traps were modified.
|
||
-- 2) Added new var xupsInputSource
|
||
-- 3) Added new vars xupsLoadShedSecsWithRestart and xupsRecepShedSecsWithRestart to
|
||
-- provide guaranteed correct load shedding behavior to the management software.
|
||
-- 4) Added vars to the Environmental group: xupsEnvAmbientHumidity,
|
||
-- xupsEnvRemoteTemp, and xupsEnvRemoteHumidity.
|
||
-- 5) Added xupsEnvNumContacts and the Environmental Contact Sensing Table,
|
||
-- xupsContactSenseTable.
|
||
-- 6) Updated Tech Support telephone numbers listed below.
|
||
|
||
-- Changes for Release Version 3.04 30-Apr-03 Connectivity Systems Group,
|
||
-- Powerware, Invensys Energy Systems
|
||
-- 1) Added new Well-Known Alarm and traps for xupsLossOfRedundancy,
|
||
-- xupsAlarmTempBad, xupsAlarmChargerFailed, xupsAlarmFanFailure,
|
||
-- xupsAlarmFuseFailure, xupsPowerSwitchBad, xupsModuleFailure,
|
||
-- xupsOnAlternatePowerSource, xupsAltPowerNotAvailable, xupsNoticeCondition
|
||
-- 2) Added new vars for Min/Max limits for Remote Temp & Humidity
|
||
-- 3) Added new W-K Alarms and traps for Min/Max limits for Remote Temp & Humidity
|
||
|
||
--
|
||
-- Customer Support: contact Tech Support at
|
||
--
|
||
-- Single-Phase Products: 800-356-5737 (US) or 608-565-2100
|
||
--
|
||
-- 3-Phase Products: 800-843-9433 (US) or 919-871-1800
|
||
--
|
||
|
||
IMPORTS
|
||
enterprises, IpAddress, TimeTicks, Gauge, Counter
|
||
FROM RFC1155-SMI
|
||
DisplayString, ifIndex, ifDescr
|
||
FROM RFC1213-MIB
|
||
OBJECT-TYPE
|
||
FROM RFC-1212
|
||
TRAP-TYPE
|
||
FROM RFC-1215;
|
||
|
||
|
||
-- Note that .534. was originally assigned to Exide Electronics
|
||
-- before it was renamed to Invensys Powerware.
|
||
|
||
powerware OBJECT IDENTIFIER ::= {enterprises 534}
|
||
xups OBJECT IDENTIFIER ::= {powerware 1}
|
||
|
||
xupsIdent OBJECT IDENTIFIER ::= { xups 1 }
|
||
xupsBattery OBJECT IDENTIFIER ::= { xups 2 }
|
||
xupsInput OBJECT IDENTIFIER ::= { xups 3 }
|
||
xupsOutput OBJECT IDENTIFIER ::= { xups 4 }
|
||
xupsBypass OBJECT IDENTIFIER ::= { xups 5 }
|
||
xupsEnvironment OBJECT IDENTIFIER ::= { xups 6 }
|
||
xupsAlarm OBJECT IDENTIFIER ::= { xups 7 }
|
||
xupsTest OBJECT IDENTIFIER ::= { xups 8 }
|
||
xupsControl OBJECT IDENTIFIER ::= { xups 9 }
|
||
xupsConfig OBJECT IDENTIFIER ::= { xups 10 }
|
||
xupsTrapControl OBJECT IDENTIFIER ::= { xups 11 }
|
||
xupsRecep OBJECT IDENTIFIER ::= { xups 12 }
|
||
xupsTopology OBJECT IDENTIFIER ::= { xups 13 }
|
||
|
||
|
||
--
|
||
-- The following Object Identifiers are used to distinguish Powerware's
|
||
-- SNMP agents:
|
||
xupsObjectId OBJECT IDENTIFIER ::= {powerware 2}
|
||
|
||
powerwareEthernetSnmpAdapter OBJECT IDENTIFIER ::= {xupsObjectId 1}
|
||
powerwareNetworkSnmpAdapterEther OBJECT IDENTIFIER ::= {xupsObjectId 2}
|
||
powerwareNetworkSnmpAdapterToken OBJECT IDENTIFIER ::= {xupsObjectId 3}
|
||
onlinetDaemon OBJECT IDENTIFIER ::= {xupsObjectId 4}
|
||
connectUPSAdapterEthernet OBJECT IDENTIFIER ::= {xupsObjectId 5}
|
||
powerwareNetworkDigitalIOEther OBJECT IDENTIFIER ::= {xupsObjectId 6}
|
||
connectUPSAdapterTokenRing OBJECT IDENTIFIER ::= {xupsObjectId 7}
|
||
simpleSnmpAdapter OBJECT IDENTIFIER ::= {xupsObjectId 8}
|
||
|
||
|
||
--
|
||
-- xupsIdent group:
|
||
--
|
||
xupsIdentManufacturer OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..31))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The UPS Manufacturer Name (e.g. Powerware Corporation)."
|
||
::= { xupsIdent 1}
|
||
|
||
xupsIdentModel OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..63))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The UPS Model (e.g. Powerware Plus Model 18)."
|
||
::= {xupsIdent 2}
|
||
|
||
xupsIdentSoftwareVersion OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..63))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The firmware revision level(s) of the UPS microcontroller(s)."
|
||
::= {xupsIdent 3}
|
||
|
||
xupsIdentOemCode OBJECT-TYPE
|
||
SYNTAX INTEGER (0..255)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"A binary code indicating who the UPS was manufactured or labeled for.
|
||
0 or 255 indicates Powerware itself."
|
||
::= {xupsIdent 4}
|
||
|
||
|
||
|
||
--
|
||
-- xupsBattery group:
|
||
--
|
||
xupsBatTimeRemaining OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS seconds
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Battery run time in seconds before UPS turns off due
|
||
to low battery."
|
||
::= { xupsBattery 1}
|
||
|
||
xupsBatVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS Volts DC
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Battery voltage as reported by the UPS meters."
|
||
::= {xupsBattery 2}
|
||
|
||
xupsBatCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER (-2147483648..2147483647) -- UNITS Amp DC
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Battery Current as reported by the UPS metering.
|
||
Current is positive when discharging, negative
|
||
when recharging the battery."
|
||
::= {xupsBattery 3}
|
||
|
||
xupsBatCapacity OBJECT-TYPE
|
||
SYNTAX INTEGER (0..100) -- UNITS percent
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Battery percent charge."
|
||
::= { xupsBattery 4}
|
||
|
||
xupsBatteryAbmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
batteryCharging(1),
|
||
batteryDischarging(2),
|
||
batteryFloating(3),
|
||
batteryResting(4),
|
||
unknown(5)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Gives the status of the Advanced Battery Management;
|
||
batteryFloating(3) status means that the charger is temporarily
|
||
charging the battery to its float voltage; batteryResting(4) is the
|
||
state when the battery is fully charged and none of the other actions
|
||
(charging/discharging/floating) is being done."
|
||
::= { xupsBattery 5}
|
||
|
||
--
|
||
-- xupsInput group:
|
||
--
|
||
xupsInputFrequency OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS 0.1 Hertz
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The utility line frequency in tenths of Hz."
|
||
::= {xupsInput 1}
|
||
|
||
xupsInputLineBads OBJECT-TYPE
|
||
SYNTAX Counter
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The number of times the Input was out of tolerance
|
||
in voltage or frequency."
|
||
::= {xupsInput 2}
|
||
|
||
xupsInputNumPhases OBJECT-TYPE
|
||
SYNTAX INTEGER (0..6)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
::= {xupsInput 3}
|
||
|
||
xupsInputTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF XupsInputEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "The Aggregate Object with number of entries equal to
|
||
NumPhases and including the xupsInput group."
|
||
::= {xupsInput 4}
|
||
|
||
xupsInputEntry OBJECT-TYPE
|
||
SYNTAX XupsInputEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "The input table entry containing the current,
|
||
voltage, etc."
|
||
INDEX { xupsInputPhase }
|
||
::= { xupsInputTable 1 }
|
||
|
||
XupsInputEntry ::= SEQUENCE {
|
||
xupsInputPhase
|
||
INTEGER,
|
||
xupsInputVoltage
|
||
INTEGER,
|
||
xupsInputCurrent
|
||
INTEGER,
|
||
xupsInputWatts
|
||
INTEGER
|
||
}
|
||
|
||
xupsInputPhase OBJECT-TYPE
|
||
SYNTAX INTEGER (0..6)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The number of the phase. Serves as index for input table."
|
||
::= {xupsInputEntry 1}
|
||
|
||
xupsInputVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The measured input voltage from the UPS meters in volts."
|
||
::= {xupsInputEntry 2}
|
||
|
||
xupsInputCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS RMS Amp
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The measured input current from the UPS meters in amps."
|
||
::= {xupsInputEntry 3}
|
||
|
||
xupsInputWatts OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS Watts
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The measured input real power in watts."
|
||
::= {xupsInputEntry 4}
|
||
|
||
xupsInputSource OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
other(1),
|
||
none(2), -- For example, Utility failure
|
||
primaryUtility(3), -- Normal utility feed to the UPS
|
||
bypassFeed(4), -- Bypass utility, separate from primaryUtility
|
||
secondaryUtility(5), -- Secondary utility feed (on a dual AC input UPS)
|
||
generator(6), -- Power provided by a generator
|
||
flywheel(7), -- Power provided by a flywheel (not necessarily AC)
|
||
fuelcell(8) -- Power provided by fuel cell(s) (not necessarily AC)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The present external source of input power. The enumeration
|
||
none(2) indicates that there is no external source of
|
||
power, for example, the UPS is On Battery (an internal source).
|
||
The bypassFeed(4) can only be used when the Bypass source is known
|
||
to be a separate utility feed than the primaryUtility(3)."
|
||
::= { xupsInput 5 }
|
||
|
||
|
||
|
||
--
|
||
-- xupsOutput group:
|
||
--
|
||
xupsOutputLoad OBJECT-TYPE
|
||
SYNTAX INTEGER (0..200)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The UPS output load in percent of rated capacity."
|
||
::= {xupsOutput 1}
|
||
|
||
xupsOutputFrequency OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS 0.1 Hertz
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The measured UPS output frequency in tenths of Hz."
|
||
::= {xupsOutput 2}
|
||
|
||
xupsOutputNumPhases OBJECT-TYPE
|
||
SYNTAX INTEGER (0..6)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The number of metered output phases, serves as the table
|
||
index."
|
||
::= {xupsOutput 3}
|
||
|
||
xupsOutputTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF XupsOutputEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Aggregate Object with number of entries equal to NumPhases
|
||
and including the xupsOutput group."
|
||
::= {xupsOutput 4}
|
||
|
||
xupsOutputEntry OBJECT-TYPE
|
||
SYNTAX XupsOutputEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Output Table Entry containing voltage, current, etc."
|
||
INDEX { xupsOutputPhase }
|
||
|
||
::= {xupsOutputTable 1}
|
||
|
||
XupsOutputEntry ::= SEQUENCE {
|
||
xupsOutputPhase
|
||
INTEGER,
|
||
xupsOutputVoltage
|
||
INTEGER,
|
||
xupsOutputCurrent
|
||
INTEGER,
|
||
xupsOutputWatts
|
||
INTEGER
|
||
}
|
||
|
||
xupsOutputPhase OBJECT-TYPE
|
||
SYNTAX INTEGER (0..6)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The number {1..3} of the output phase."
|
||
::= {xupsOutputEntry 1}
|
||
|
||
xupsOutputVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The measured output voltage from the UPS metering in volts."
|
||
::= {xupsOutputEntry 2}
|
||
|
||
xupsOutputCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS RMS Amp
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The measured UPS output current in amps."
|
||
::= {xupsOutputEntry 3}
|
||
|
||
xupsOutputWatts OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS Watts
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The measured real output power in watts."
|
||
::= {xupsOutputEntry 4}
|
||
|
||
xupsOutputSource OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
other(1),
|
||
none(2),
|
||
normal(3), -- normal, single UPS module output
|
||
bypass(4),
|
||
battery(5),
|
||
booster(6), -- Single or Double Boost, line-interactive UPSs only
|
||
reducer(7), -- Buck, line-interactive UPSs only
|
||
parallelCapacity(8), -- normal enhanced by Parallel for Capacity operation
|
||
parallelRedundant(9), -- normal enhanced by Redundant Parallel operation
|
||
highEfficiencyMode(10) -- normal enhanced by High Efficiency mode
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The present source of output power. The enumeration
|
||
none(2) indicates that there is no source of output
|
||
power (and therefore no output power), for example,
|
||
the system has opened the output breaker."
|
||
::= { xupsOutput 5 }
|
||
|
||
|
||
--
|
||
-- xupsBypass group:
|
||
--
|
||
xupsBypassFrequency OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS 0.1 Hertz
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The bypass frequency in tenths of Hz."
|
||
::= {xupsBypass 1}
|
||
|
||
xupsBypassNumPhases OBJECT-TYPE
|
||
SYNTAX INTEGER (0..6)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The number of lines in the UPS bypass table."
|
||
::= {xupsBypass 2}
|
||
|
||
xupsBypassTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF XupsBypassEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
::= {xupsBypass 3}
|
||
|
||
xupsBypassEntry OBJECT-TYPE
|
||
SYNTAX XupsBypassEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Entry in the XUPS bypass table."
|
||
INDEX { xupsBypassPhase }
|
||
::= {xupsBypassTable 1}
|
||
|
||
XupsBypassEntry ::= SEQUENCE {
|
||
xupsBypassPhase
|
||
INTEGER,
|
||
xupsBypassVoltage
|
||
INTEGER
|
||
}
|
||
|
||
xupsBypassPhase OBJECT-TYPE
|
||
SYNTAX INTEGER (0..6)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Bypass Phase, index for the table."
|
||
::= {xupsBypassEntry 1}
|
||
|
||
xupsBypassVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The measured UPS bypass voltage in volts."
|
||
::= {xupsBypassEntry 2}
|
||
|
||
|
||
--
|
||
-- xupsEnvironment group:
|
||
--
|
||
|
||
xupsEnvAmbientTemp OBJECT-TYPE
|
||
SYNTAX INTEGER (-100..200) -- UNITS Degrees Centigrade
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The reading of the ambient temperature in the vicinity of the
|
||
UPS or SNMP agent."
|
||
::= { xupsEnvironment 1 }
|
||
|
||
xupsEnvAmbientLowerLimit OBJECT-TYPE
|
||
SYNTAX INTEGER (-100..200) -- UNITS Degrees Centigrade
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Lower Limit of the ambient temperature; if xupsEnvAmbientTemp
|
||
falls below this value, the xupsAmbientTempBad alarm will occur."
|
||
::= { xupsEnvironment 2 }
|
||
|
||
xupsEnvAmbientUpperLimit OBJECT-TYPE
|
||
SYNTAX INTEGER (-100..200) -- UNITS Degrees Centigrade
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Upper Limit of the ambient temperature; if xupsEnvAmbientTemp
|
||
rises above this value, the xupsAmbientTempBad alarm will occur.
|
||
This value should be greater than xupsEnvAmbientLowerLimit."
|
||
::= { xupsEnvironment 3 }
|
||
|
||
xupsEnvAmbientHumidity OBJECT-TYPE
|
||
SYNTAX INTEGER (0..100) -- UNITS %
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The reading of the ambient humidity in the vicinity of the
|
||
UPS or SNMP agent."
|
||
::= { xupsEnvironment 4 }
|
||
|
||
xupsEnvRemoteTemp OBJECT-TYPE
|
||
SYNTAX INTEGER (-100..200) -- UNITS Degrees Centigrade
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The reading of a remote temperature sensor connected to the
|
||
UPS or SNMP agent."
|
||
::= { xupsEnvironment 5 }
|
||
|
||
xupsEnvRemoteHumidity OBJECT-TYPE
|
||
SYNTAX INTEGER (0..100) -- UNITS %
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The reading of a remote humidity sensor connected to the
|
||
UPS or SNMP agent."
|
||
::= { xupsEnvironment 6 }
|
||
|
||
--
|
||
-- The Environmental Contact Sensing Table
|
||
-- Contains the table for monitoring all contacts (digital
|
||
-- inputs).
|
||
--
|
||
|
||
xupsEnvNumContacts OBJECT-TYPE
|
||
SYNTAX INTEGER (1..1024)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The number of Contacts in the xupsContactSenseTable.
|
||
This object indicates the number of rows in the
|
||
xupsContactSenseTable."
|
||
::= { xupsEnvironment 7 }
|
||
|
||
xupsContactSenseTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF XupsContactsTableEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"A list of Contact Sensing table entries.
|
||
The number of entries is given by the value of
|
||
xupsEnvNumContacts."
|
||
::= { xupsEnvironment 8 }
|
||
|
||
xupsContactsTableEntry OBJECT-TYPE
|
||
SYNTAX XupsContactsTableEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"An entry containing information applicable
|
||
to a particular Contact input."
|
||
INDEX { xupsContactIndex }
|
||
::= { xupsContactSenseTable 1 }
|
||
|
||
XupsContactsTableEntry ::=
|
||
SEQUENCE {
|
||
xupsContactIndex
|
||
INTEGER,
|
||
|
||
xupsContactType
|
||
INTEGER,
|
||
|
||
xupsContactState
|
||
INTEGER,
|
||
|
||
xupsContactDescr
|
||
DisplayString
|
||
}
|
||
|
||
xupsContactIndex OBJECT-TYPE
|
||
SYNTAX INTEGER (1..1024)
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Contact identifier; identical to the Contact Number."
|
||
::= { xupsContactsTableEntry 1 }
|
||
|
||
xupsContactType OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
normallyOpen(1), -- or Input Normally High
|
||
normallyClosed(2), -- or Input Normally Low
|
||
anyChange(3), -- No normal Open/Closed state
|
||
notUsed(4) -- Contact not in service
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The normal state for this contact. The 'other'
|
||
state is the Active state for generating the xupstdContactActiveNotice
|
||
trap. If anyChange(3) is selected, then this trap is sent
|
||
any time the contact changes to either Open or Closed.
|
||
No traps are sent if the Contact is set to notUsed(4).
|
||
In many cases, the configuration for Contacts may be done by other
|
||
means, so this object may be read-only."
|
||
::= { xupsContactsTableEntry 2 }
|
||
|
||
xupsContactState OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
open(1),
|
||
closed(2),
|
||
openWithNotice(3),
|
||
closedWithNotice(4)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The current state of the Contact input;
|
||
the value is based on the open/closed input state
|
||
and the setting for xupsContactType.
|
||
When entering the openWithNotice(3) and closedWithNotice(4)
|
||
states, no entries added to the xupsAlarmTable, but
|
||
the xupstdContactActiveNotice trap is sent."
|
||
::= { xupsContactsTableEntry 3 }
|
||
|
||
xupsContactDescr OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..63))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"A label identifying the Contact. This object should be
|
||
set by the administrator."
|
||
::= { xupsContactsTableEntry 4 }
|
||
|
||
xupsEnvRemoteTempLowerLimit OBJECT-TYPE
|
||
SYNTAX INTEGER (-100..200) -- UNITS Degrees Centigrade
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Lower Limit of the remote temperature; if xupsEnvRemoteTemp
|
||
falls below this value, the xupsRemoteTempBad alarm will occur."
|
||
::= { xupsEnvironment 9 }
|
||
|
||
xupsEnvRemoteTempUpperLimit OBJECT-TYPE
|
||
SYNTAX INTEGER (-100..200) -- UNITS Degrees Centigrade
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Upper Limit of the remote temperature; if xupsEnvRemoteTemp
|
||
rises above this value, the xupsRemoteTempBad alarm will occur.
|
||
This value should be greater than xupsEnvRemoteTempLowerLimit."
|
||
::= { xupsEnvironment 10 }
|
||
|
||
xupsEnvRemoteHumidityLowerLimit OBJECT-TYPE
|
||
SYNTAX INTEGER (0..100) -- UNITS %
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Lower Limit of the remote humidity reading; if xupsEnvRemoteHumidity
|
||
falls below this value, the xupsRemoteHumidityBad alarm will occur."
|
||
::= { xupsEnvironment 11 }
|
||
|
||
xupsEnvRemoteHumidityUpperLimit OBJECT-TYPE
|
||
SYNTAX INTEGER (0..100) -- UNITS %
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Upper Limit of the remote humidity reading; if xupsEnvRemoteHumidity
|
||
rises above this value, the xupsRemoteHumidityBad alarm will occur.
|
||
This value should be greater than xupsEnvRemoteHumidityLowerLimit."
|
||
::= { xupsEnvironment 12 }
|
||
|
||
|
||
|
||
--
|
||
-- xupsAlarm group:
|
||
--
|
||
xupsAlarms OBJECT-TYPE
|
||
SYNTAX Gauge
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The current number of alarm conditions."
|
||
::= {xupsAlarm 1}
|
||
|
||
xupsAlarmTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF XupsAlarmEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
::= {xupsAlarm 2}
|
||
|
||
xupsAlarmEntry OBJECT-TYPE
|
||
SYNTAX XupsAlarmEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
INDEX { xupsAlarmID }
|
||
::= {xupsAlarmTable 1}
|
||
|
||
XupsAlarmEntry ::= SEQUENCE {
|
||
xupsAlarmID
|
||
INTEGER,
|
||
xupsAlarmDescr
|
||
OBJECT IDENTIFIER,
|
||
xupsAlarmTime
|
||
TimeTicks
|
||
}
|
||
|
||
xupsAlarmID OBJECT-TYPE
|
||
SYNTAX INTEGER (1..2147483647)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"A unique identifier for an alarm condition."
|
||
::= {xupsAlarmEntry 1}
|
||
|
||
xupsAlarmDescr OBJECT-TYPE
|
||
SYNTAX OBJECT IDENTIFIER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"A reference to an alarm description object. The object
|
||
referenced should not be accessible, but rather be used to
|
||
provide a unique description of the alarm condition."
|
||
::= {xupsAlarmEntry 2}
|
||
|
||
xupsAlarmTime OBJECT-TYPE
|
||
SYNTAX TimeTicks
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The value of the MIB-II variable sysUpTime when the alarm
|
||
condition occurred."
|
||
::= {xupsAlarmEntry 3}
|
||
|
||
--
|
||
-- Well known alarm conditions.
|
||
--
|
||
xupsOnBattery OBJECT IDENTIFIER ::= {xupsAlarm 3}
|
||
xupsLowBattery OBJECT IDENTIFIER ::= {xupsAlarm 4}
|
||
xupsUtilityPowerRestored OBJECT IDENTIFIER ::= {xupsAlarm 5}
|
||
xupsReturnFromLowBattery OBJECT IDENTIFIER ::= {xupsAlarm 6}
|
||
xupsOutputOverload OBJECT IDENTIFIER ::= {xupsAlarm 7}
|
||
xupsInternalFailure OBJECT IDENTIFIER ::= {xupsAlarm 8}
|
||
xupsBatteryDischarged OBJECT IDENTIFIER ::= {xupsAlarm 9}
|
||
xupsInverterFailure OBJECT IDENTIFIER ::= {xupsAlarm 10}
|
||
xupsOnBypass OBJECT IDENTIFIER ::= {xupsAlarm 11}
|
||
xupsBypassNotAvailable OBJECT IDENTIFIER ::= {xupsAlarm 12}
|
||
xupsOutputOff OBJECT IDENTIFIER ::= {xupsAlarm 13}
|
||
xupsInputFailure OBJECT IDENTIFIER ::= {xupsAlarm 14}
|
||
xupsBuildingAlarm OBJECT IDENTIFIER ::= {xupsAlarm 15}
|
||
xupsShutdownImminent OBJECT IDENTIFIER ::= {xupsAlarm 16}
|
||
xupsOnInverter OBJECT IDENTIFIER ::= {xupsAlarm 17}
|
||
|
||
|
||
xupsAlarmNumEvents OBJECT-TYPE
|
||
SYNTAX Gauge
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The number of entries in the UPS event history queue."
|
||
::= { xupsAlarm 18 }
|
||
|
||
xupsAlarmEventTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF XupsAlarmEventEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"A table of the UPS internal event history queue."
|
||
::= { xupsAlarm 19 }
|
||
|
||
xupsAlarmEventEntry OBJECT-TYPE
|
||
SYNTAX XupsAlarmEventEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"One of the entries in the UPS event history queue."
|
||
INDEX { xupsAlarmEventID }
|
||
::= { xupsAlarmEventTable 1 }
|
||
|
||
-- The first 4 vars in the xAEEntry have been deprecated, since they resulted in
|
||
-- a flood of difficult to interpret data. They have been replaced by the single
|
||
-- entry, xupsAlarmEventMsg, which gives a human-readable description of the event.
|
||
XupsAlarmEventEntry ::= SEQUENCE {
|
||
xupsAlarmEventID
|
||
INTEGER,
|
||
xupsAlarmEventDateAndTime
|
||
DisplayString,
|
||
xupsAlarmEventKind
|
||
INTEGER,
|
||
xupsAlarmEventDescr
|
||
INTEGER,
|
||
xupsAlarmEventMsg
|
||
DisplayString
|
||
}
|
||
|
||
xupsAlarmEventID OBJECT-TYPE
|
||
SYNTAX INTEGER (1..400)
|
||
ACCESS read-only
|
||
STATUS deprecated
|
||
DESCRIPTION
|
||
"A unique number that reflects the order in which the event
|
||
occurred. The oldest event in the queue will be number 1.
|
||
Subsequent events will be numbered 2, 3, 4, etc."
|
||
::= { xupsAlarmEventEntry 1 }
|
||
|
||
xupsAlarmEventDateAndTime OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..22))
|
||
ACCESS read-only
|
||
STATUS deprecated
|
||
DESCRIPTION
|
||
"The time and date that an event occurred as recorded in the UPS
|
||
internal event queue. This string will reflect the time and
|
||
date as set in the UPS itself and will not be referenced to
|
||
sysUpTime. The format is MM/DD/YYYY:HH:MM:SS. Time is 24 hour standard."
|
||
::= { xupsAlarmEventEntry 2 }
|
||
|
||
xupsAlarmEventKind OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
occurred (1),
|
||
cleared (2),
|
||
unknown (3)
|
||
}
|
||
ACCESS read-only
|
||
STATUS deprecated
|
||
DESCRIPTION
|
||
"Enumerated value that tells whether the event is an
|
||
occurrence of an alarm condition or a clearing of an
|
||
alarm condition."
|
||
::= { xupsAlarmEventEntry 3 }
|
||
|
||
xupsAlarmEventDescr OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647)
|
||
ACCESS read-only
|
||
STATUS deprecated
|
||
DESCRIPTION
|
||
"A description of the event stored in the UPS event queue.
|
||
This description will be a sixteen bit integer value
|
||
representing one of the defined alarms in the Powerware Binary
|
||
Computer Mode communication specification; for example,
|
||
a value of 0 represents the 'Inverter AC Over Voltage'
|
||
alarm (byte 1, bit 0 in the BCM Alarm Map)."
|
||
::= { xupsAlarmEventEntry 4 }
|
||
|
||
xupsAlarmEventMsg OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..80))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"A text string describing each entry in the Event Log. The format of this
|
||
text message is free (not fixed) for the operator to read; good contents
|
||
would be a time & date stamp, the event type, and a description of the event."
|
||
::= { xupsAlarmEventEntry 5 }
|
||
|
||
--
|
||
-- More Well known alarm conditions.
|
||
--
|
||
xupsBreakerOpen OBJECT IDENTIFIER ::= {xupsAlarm 20}
|
||
xupsAlarmEntryAdded OBJECT IDENTIFIER ::= {xupsAlarm 21}
|
||
xupsAlarmEntryRemoved OBJECT IDENTIFIER ::= {xupsAlarm 22}
|
||
|
||
-- Same as RFC 1628 Well Known Alarms:
|
||
xupsAlarmBatteryBad OBJECT IDENTIFIER ::= {xupsAlarm 23}
|
||
xupsOutputOffAsRequested OBJECT IDENTIFIER ::= {xupsAlarm 24}
|
||
xupsDiagnosticTestFailed OBJECT IDENTIFIER ::= {xupsAlarm 25}
|
||
xupsCommunicationsLost OBJECT IDENTIFIER ::= {xupsAlarm 26}
|
||
xupsUpsShutdownPending OBJECT IDENTIFIER ::= {xupsAlarm 27}
|
||
xupsAlarmTestInProgress OBJECT IDENTIFIER ::= {xupsAlarm 28}
|
||
|
||
-- Alarm for the Ambient Temperature, when outside of lo/hi limits
|
||
xupsAmbientTempBad OBJECT IDENTIFIER ::= {xupsAlarm 29}
|
||
|
||
-- For Loss of Redundancy in parallel systems
|
||
xupsLossOfRedundancy OBJECT IDENTIFIER ::= {xupsAlarm 30}
|
||
|
||
-- More Same as RFC 1628 Well Known Alarms:
|
||
xupsAlarmTempBad OBJECT IDENTIFIER ::= {xupsAlarm 31}
|
||
xupsAlarmChargerFailed OBJECT IDENTIFIER ::= {xupsAlarm 32}
|
||
xupsAlarmFanFailure OBJECT IDENTIFIER ::= {xupsAlarm 33}
|
||
xupsAlarmFuseFailure OBJECT IDENTIFIER ::= {xupsAlarm 34}
|
||
|
||
-- A Relay, Contactor, or Breaker has failed
|
||
xupsPowerSwitchBad OBJECT IDENTIFIER ::= {xupsAlarm 35}
|
||
|
||
-- One module in a parallel or composite system has failed
|
||
xupsModuleFailure OBJECT IDENTIFIER ::= {xupsAlarm 36}
|
||
|
||
-- Two Alarms for systems with an Alternate Power Source, such as
|
||
-- Secondary utility feed (on a dual AC input UPS), generator,
|
||
-- flywheel, or fuelcell.
|
||
xupsOnAlternatePowerSource OBJECT IDENTIFIER ::= {xupsAlarm 37}
|
||
xupsAltPowerNotAvailable OBJECT IDENTIFIER ::= {xupsAlarm 38}
|
||
|
||
-- Some Notice condition exists which is not covered by the other WKA
|
||
-- (like an xupsInternalFailure, but at a lower level of urgency)
|
||
xupsNoticeCondition OBJECT IDENTIFIER ::= {xupsAlarm 39}
|
||
|
||
-- Alarms for the Remote Temperature & Humidity, when outside of lo/hi limits
|
||
xupsRemoteTempBad OBJECT IDENTIFIER ::= {xupsAlarm 40}
|
||
xupsRemoteHumidityBad OBJECT IDENTIFIER ::= {xupsAlarm 41}
|
||
|
||
|
||
|
||
--
|
||
-- xupsTest group:
|
||
--
|
||
xupsTestBattery OBJECT-TYPE
|
||
SYNTAX INTEGER { startTest (1) }
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Setting this variable to startTest initiates the
|
||
battery test. All other set values are invalid."
|
||
::= {xupsTest 1}
|
||
|
||
xupsTestBatteryStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
unknown (1),
|
||
passed (2),
|
||
failed (3),
|
||
inProgress (4),
|
||
notSupported (5),
|
||
inhibited (6),
|
||
scheduled (7)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Reading this enumerated value gives an indication of the
|
||
UPS Battery test status."
|
||
::= {xupsTest 2}
|
||
|
||
|
||
--
|
||
-- xupsControl group:
|
||
--
|
||
xupsControlOutputOffDelay OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS seconds
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Setting this value to other than zero will cause the UPS
|
||
output to turn off after the number of seconds.
|
||
Setting it to 0 will cause an attempt to abort a pending
|
||
shutdown."
|
||
::= {xupsControl 1}
|
||
|
||
xupsControlOutputOnDelay OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS seconds
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Setting this value to other than zero will cause the UPS
|
||
output to turn on after the number of seconds.
|
||
Setting it to 0 will cause an attempt to abort a pending
|
||
startup."
|
||
::= {xupsControl 2}
|
||
|
||
xupsControlOutputOffTrapDelay OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS seconds
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"When xupsControlOutputOffDelay reaches this value, a trap will
|
||
be sent."
|
||
::= {xupsControl 3}
|
||
|
||
xupsControlOutputOnTrapDelay OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS seconds
|
||
ACCESS read-write
|
||
STATUS deprecated
|
||
DESCRIPTION
|
||
"When xupsControlOutputOnDelay reaches this value, a
|
||
xupsOutputOff trap will be sent."
|
||
::= {xupsControl 4}
|
||
|
||
xupsControlToBypassDelay OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS seconds
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Setting this value to other than zero will cause the UPS
|
||
output to go to Bypass after the number of seconds.
|
||
If the Bypass is unavailable, this may cause the UPS
|
||
to not supply power to the load.
|
||
Setting it to 0 will cause an attempt to abort a pending
|
||
shutdown."
|
||
::= {xupsControl 5}
|
||
|
||
xupsLoadShedSecsWithRestart OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS seconds
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Setting this value will cause the UPS output to turn off
|
||
after the set number of seconds, then restart (after a UPS-defined
|
||
'down time') when the utility is again available.
|
||
Unlike xupsControlOutputOffDelay, which might or might not,
|
||
this object always maps to the XCP 0x8A Load Dump & Restart command,
|
||
so the desired shutdown and restart behavior is guaranteed to happen.
|
||
Once set, this command cannot be aborted.
|
||
This is the preferred Control object to use when performing an On
|
||
Battery OS Shutdown."
|
||
::= {xupsControl 6}
|
||
|
||
--
|
||
-- xupsConfig group:
|
||
--
|
||
xupsConfigOutputVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The nominal UPS Output voltage per phase in volts."
|
||
::= {xupsConfig 1}
|
||
|
||
xupsConfigInputVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The nominal UPS Input voltage per phase in volts."
|
||
::= {xupsConfig 2}
|
||
|
||
xupsConfigOutputWatts OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS Watts
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The nominal UPS available real power output in watts."
|
||
::= {xupsConfig 3}
|
||
|
||
xupsConfigOutputFreq OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS 0.1 Hertz
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The nominal output frequency in tenths of Hz."
|
||
::= {xupsConfig 4}
|
||
|
||
xupsConfigDateAndTime OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..22))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Date and time information for the UPS. Setting this variable
|
||
will initiate a set UPS date and time to this value. Reading
|
||
this variable will return the UPS time and date. This value
|
||
is not referenced to sysUpTime. It is simply the clock value
|
||
from the UPS real time clock.
|
||
Format is as follows: MM/DD/YYYY:HH:MM:SS."
|
||
::= { xupsConfig 5 }
|
||
|
||
xupsConfigLowOutputVoltageLimit OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Lower limit for acceptable Output Voltage, per the UPS
|
||
specifications."
|
||
::= {xupsConfig 6}
|
||
|
||
xupsConfigHighOutputVoltageLimit OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Upper limit for acceptable Output Voltage, per the UPS
|
||
specifications."
|
||
::= {xupsConfig 7}
|
||
|
||
|
||
|
||
--
|
||
-- xupsTrapControl group:
|
||
--
|
||
xupsMaxTrapLevel OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
none (1),
|
||
critical (2),
|
||
major (3),
|
||
allTraps (4)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The level of severity of traps which will be sent to the
|
||
requesting host; individual trap receivers will have
|
||
individual values for this variable. Values are:
|
||
(1) none: no traps will be sent to this host;
|
||
(2) critical: only traps for Critical alarm conditions will
|
||
be sent to this host;
|
||
(3) major: Critical and Major traps will be sent;
|
||
(4) allTraps: all Traps will be sent to this host
|
||
(Critical, Major, Minor, Informational)."
|
||
::= {xupsTrapControl 1}
|
||
|
||
xupsSendTrapType OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
stnd (1),
|
||
xups (2),
|
||
stndPlus (3),
|
||
xupsPlus (4)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The type of traps which will be sent to the
|
||
requesting host; individual trap receivers will have
|
||
individual values for this variable. The additional
|
||
variables in types (3) and (4) are useful for determining
|
||
which UPS is the source on multi-port network adapters,
|
||
and for getting additional descriptive information.
|
||
Types (1) through (4) are all SNMP version 1 trap PDUs.
|
||
Values are:
|
||
(1) stnd: Traps as defined in the Standard UPS MIB (RFC1628)
|
||
and Generic (MIB II) traps as defined in RFC 1215.
|
||
(2) xups: xupsTrapDefined Traps as defined in the PowerMIB
|
||
and Generic (MIB II) traps as defined in RFC 1215.
|
||
(3) stndPlus: same as stnd plus variables from the interface
|
||
group and, where appropriate, xupsTrapMessage.
|
||
(4) xupsPlus: xupsTrapPortN Traps (same as xups plus
|
||
variables from the interface group) and,
|
||
for authFail, xupsTrapMessage."
|
||
::= {xupsTrapControl 2}
|
||
|
||
xupsTrapMessage OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..79))
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"A descriptive message which may be sent with traps to
|
||
further explain the reason for the trap."
|
||
::= {xupsTrapControl 3}
|
||
|
||
|
||
|
||
--
|
||
-- xupsRecep group:
|
||
--
|
||
-- (Note that the terms Receptacle, Outlet, and Load Group are used interchangeably
|
||
-- here and all mean "one of a set of controllable, power-switched outputs")
|
||
--
|
||
xupsNumReceptacles OBJECT-TYPE
|
||
SYNTAX INTEGER (0..64)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The number of independently controllable Receptacles, as described in the
|
||
xupsRecepTable."
|
||
::= {xupsRecep 1}
|
||
|
||
xupsRecepTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF XupsRecepEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "The Aggregate Object with number of entries equal to
|
||
NumReceptacles and including the xupsRecep group."
|
||
::={xupsRecep 2}
|
||
|
||
xupsRecepEntry OBJECT-TYPE
|
||
SYNTAX XupsRecepEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION "The Recep table entry, etc."
|
||
INDEX { xupsRecepIndex }
|
||
::= { xupsRecepTable 1 }
|
||
|
||
XupsRecepEntry ::= SEQUENCE {
|
||
xupsRecepIndex
|
||
INTEGER,
|
||
xupsRecepStatus
|
||
INTEGER,
|
||
xupsRecepOffDelaySecs
|
||
INTEGER,
|
||
xupsRecepOnDelaySecs
|
||
INTEGER,
|
||
xupsRecepAutoOffDelay
|
||
INTEGER,
|
||
xupsRecepAutoOnDelay
|
||
INTEGER,
|
||
xupsRecepShedSecsWithRestart
|
||
INTEGER
|
||
}
|
||
|
||
xupsRecepIndex OBJECT-TYPE
|
||
SYNTAX INTEGER (1..64)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The number of the Receptacle. Serves as index for Receptacle table."
|
||
::= {xupsRecepEntry 1}
|
||
|
||
|
||
xupsRecepStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
on(1), off(2), pendingOff(3), pendingOn(4), unknown(5) }
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
|
||
4=Off w/Pending ON, 5=Unknown."
|
||
::={xupsRecepEntry 2}
|
||
|
||
|
||
xupsRecepOffDelaySecs OBJECT-TYPE
|
||
SYNTAX INTEGER (-1..2147483647) -- UNITS seconds
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The Delay until the Receptacle is turned Off. Setting
|
||
this value to other than -1 will cause the UPS output to
|
||
turn off after the number of seconds (0 is immediately).
|
||
Setting it to -1 will cause an attempt to abort a pending shutdown.
|
||
When this object is set while the UPS is On Battery, it is not necessary
|
||
to set xupsRecepOnDelaySecs, since the outlet will turn back on
|
||
automatically when power is available again."
|
||
::= {xupsRecepEntry 3}
|
||
|
||
xupsRecepOnDelaySecs OBJECT-TYPE
|
||
SYNTAX INTEGER (-1..2147483647) -- UNITS seconds
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
" The Delay until the Receptacle is turned On. Setting
|
||
this value to other than -1 will cause the UPS output to
|
||
turn on after the number of seconds (0 is immediately).
|
||
Setting it to -1 will cause an attempt to abort a pending restart."
|
||
::={xupsRecepEntry 4}
|
||
|
||
|
||
xupsRecepAutoOffDelay OBJECT-TYPE
|
||
SYNTAX INTEGER (-1..32767) -- UNITS seconds
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"The delay after going On Battery until the Receptacle is
|
||
automatically turned Off. A value of -1 means that this Output should
|
||
never be turned Off automatically, but must be turned Off only by command.
|
||
Values from 0 to 30 are valid, but probably innappropriate.
|
||
The AutoOffDelay can be used to prioritize loads in the event of a prolonged
|
||
power outage; less critical loads will turn off earlier to extend battery
|
||
time for the more critical loads. If the utility power is restored before the
|
||
AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off."
|
||
::= {xupsRecepEntry 5}
|
||
|
||
xupsRecepAutoOnDelay OBJECT-TYPE
|
||
SYNTAX INTEGER (-1..32767) -- UNITS seconds
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Seconds delay after the Outlet is signaled to turn On before the Output is
|
||
Automatically turned ON. A value of -1 means that this Output should never
|
||
be turned On automatically, but only when specifically commanded to do so.
|
||
A value of 0 means that the Receptacle should come On immediately
|
||
at power-up or for an On command."
|
||
::= {xupsRecepEntry 6}
|
||
|
||
-- xupsRecepAutoOnDelay has three purposes:
|
||
-- 1. To coordinate the automatic startup of various outlets, when the normal
|
||
-- auto-sequencing of 1 second per outlet is not adequate. For example, they may
|
||
-- be used to power up hard disk arrays before CPU units are started.
|
||
-- 2. To force additional 'Down Time' during xupsRecepOffDelaySecs commands, for
|
||
-- equipment to be reset, when the standard 'Down Time' is not long enough.
|
||
-- 3. For the -1 value, to ensure that loads wont be powered until commanded,
|
||
-- following power-up or a xupsRecepOffDelaySecs command.
|
||
|
||
xupsRecepShedSecsWithRestart OBJECT-TYPE
|
||
SYNTAX INTEGER (0..2147483647) -- UNITS seconds
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Setting this value will cause the UPS output to turn off
|
||
after the set number of seconds, then restart (after a UPS-defined
|
||
'down time') when the utility is again available.
|
||
Unlike xupsRecepOffDelaySecs, which might or might not,
|
||
this object always maps to the XCP 0x8A Load Dump & Restart command,
|
||
so the desired shutdown and restart behavior is guaranteed to happen.
|
||
Once set, this command cannot be aborted."
|
||
::= {xupsRecepEntry 7}
|
||
|
||
--
|
||
-- xupsTopology group:
|
||
--
|
||
xupsTopologyType OBJECT-TYPE
|
||
SYNTAX INTEGER (0..32767)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Value which denotes the type of UPS by its power topology. Values are the
|
||
same as those described in the XCP Topology block's Overall Topology field."
|
||
::= {xupsTopology 1}
|
||
|
||
xupsTopoMachineCode OBJECT-TYPE
|
||
SYNTAX INTEGER (0..32767)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"ID Value which denotes the Powerware model of the UPS for software. Values
|
||
are the same as those described in the XCP Configuration block's Machine Code
|
||
field."
|
||
::= {xupsTopology 2}
|
||
|
||
xupsTopoUnitNumber OBJECT-TYPE
|
||
SYNTAX INTEGER (0..64)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Identifies which unit and what type of data is being reported.
|
||
A value of 0 means that this MIB information comes from the top-level system
|
||
view (eg, manifold module or system bypass cabinet reporting total system
|
||
output). Standalone units also use a value of 0, since they are the 'full
|
||
system' view.
|
||
A value of 1 or higher indicates the number of the module in the system
|
||
which is reporting only its own data in the PowerMIB objects."
|
||
::= {xupsTopology 3}
|
||
|
||
xupsTopoPowerStrategy OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
highAlert(1), standard(2), enableHighEfficiency(3),
|
||
immediateHighEfficiency(4) }
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Value which denotes which Power Strategy is currently set for the UPS.
|
||
The values are:
|
||
highAlert(1) - The UPS shall optimize its operating state to maximize its
|
||
power-protection levels. This mode will be held for at most 24 hours.
|
||
standard(2) - Balanced, normal power protection strategy. UPS will not enter
|
||
HE operating mode from this setting.
|
||
enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to
|
||
optimize its operating state to maximize its efficiency, when
|
||
conditions change to permit it (as determined by the UPS).
|
||
forceHighEfficiency(4) - If this value is permitted to be Set for this UPS,
|
||
and if conditions permit, requires the UPS to enter High Efficiency
|
||
mode now, without delay (for as long as utility conditions permit).
|
||
After successfully set to forceHighEfficiency(4),
|
||
xupsTopoPowerStrategy changes to value enableHighEfficiency(3).
|
||
xupsOutputSource will indicate if the UPS status is actually operating in
|
||
High Efficiency mode."
|
||
::= {xupsTopology 4}
|
||
|
||
-- *************************************************************************
|
||
-- *************************************************************************
|
||
|
||
--
|
||
-- Traps (xupst)
|
||
--
|
||
-- 1) Powerware's traps are defined in this MIB for three different sources:
|
||
-- a) Basic Agents for which the trap variables have not been defined,
|
||
-- though trap variables are included with the trap PDU
|
||
-- b) Agents with exactly Defined trap variables, which may be
|
||
-- used as input to trap response macros on management stations
|
||
-- c) Agents with Defined traps including ifIndex and ifDescr,
|
||
-- which can be used to determine which UPS of a multi-port
|
||
-- agent (eg, Powerware Network SNMP Adapter) sent the trap
|
||
-- The trap definitions for the three sources are very similar,
|
||
-- and use the same alarms as their triggers; their names are prefaced
|
||
-- by xupstb, xupstd, and xupstp to distinguish the three types
|
||
--
|
||
-- 2) Trap Severity Level is given as a comment to indicate which
|
||
-- xupsMaxTrapLevel will result in this trap being sent; levels
|
||
-- are (in order): Critical, Major, Minor, Informational
|
||
--
|
||
-- 3) The following Object Identifiers are used to distinguish Powerware's
|
||
-- Trap sources:
|
||
-- a) The first is for traps without defined trap variables
|
||
xupsNull OBJECT IDENTIFIER ::= { xups 0 }
|
||
xupsTrapBasic OBJECT IDENTIFIER ::= { xupsNull 0 }
|
||
-- b) The second is for traps with defined variables,
|
||
-- without ifIndex & ifDescr
|
||
xupsTrapSource OBJECT IDENTIFIER ::= {xupsTrapControl 4}
|
||
xupsTrapDefined OBJECT IDENTIFIER ::= {xupsTrapSource 1}
|
||
-- c) The third is for traps with defined variables
|
||
-- plus ifIndex & ifDescr
|
||
xupsTrapPortN OBJECT IDENTIFIER ::= {xupsTrapSource 2}
|
||
|
||
|
||
-- ****************************************************************************
|
||
-- ****************************************************************************
|
||
--
|
||
-- Traps from xupsTrapBasic source (xupstb):
|
||
--
|
||
xupstbControlOff TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The UPS output power will turn off in a number of
|
||
seconds equal to upsControlOutputOffTrapDelay."
|
||
--#SEVERITY CRITICAL
|
||
::= 1
|
||
|
||
xupstbControlOn TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The UPS output power will turn on in a number of
|
||
seconds equal to upsControlOutputOnTrapDelay."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 2
|
||
|
||
xupstbOnBattery TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The UPS has no AC input power and is running on
|
||
battery."
|
||
--#SEVERITY MAJOR
|
||
::= 3
|
||
|
||
xupstbLowBattery TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The UPS batteries are low. Tied to low battery
|
||
alarm condition."
|
||
--#SEVERITY CRITICAL
|
||
::= 4
|
||
|
||
xupstbUtilityPowerRestored TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"Input power has been restored after running on battery."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 5
|
||
|
||
xupstbReturnFromLowBattery TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The battery has recovered from a low battery condition."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 6
|
||
|
||
xupstbOutputOverload TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The ups has sensed an overload of greater than
|
||
106 percent. Tied to the 106% overload alarm."
|
||
--#SEVERITY MINOR
|
||
::= 7
|
||
|
||
xupstbInternalFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"Some component of the ups - rectifier, inverter,
|
||
control panel has failed. Tied to alarms indicating failure."
|
||
--#SEVERITY CRITICAL
|
||
::= 8
|
||
|
||
xupstbBatteryDischarged TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The Battery Totally Discharged Alarm has occurred."
|
||
--#SEVERITY CRITICAL
|
||
::= 9
|
||
|
||
xupstbInverterFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The ups inverter is unavailable due to an internal failure."
|
||
--#SEVERITY CRITICAL
|
||
::= 10
|
||
|
||
xupstbOnBypass TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The ups has gone on bypass for some reason."
|
||
--#SEVERITY CRITICAL
|
||
::= 11
|
||
|
||
xupstbBypassNotAvailable TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The ups bypass is unavailable"
|
||
--#SEVERITY MAJOR
|
||
::= 12
|
||
|
||
xupstbOutputOff TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The ups output is switched off."
|
||
--#SEVERITY CRITICAL
|
||
::= 13
|
||
|
||
xupstbInputFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The ups input power is incorrect in voltage,
|
||
frequency, or phase rotation."
|
||
--#SEVERITY MINOR
|
||
::= 14
|
||
|
||
xupstbBuildingAlarm TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"One of the defined building alarms has occurred."
|
||
--#SEVERITY MAJOR
|
||
::= 15
|
||
|
||
xupstbShutdownImminent TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The ups shutdown imminent alarm has occurred."
|
||
--#SEVERITY CRITICAL
|
||
::= 16
|
||
|
||
xupstbOnInverter TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"The ups is returned to utility power running the inverter
|
||
after either a transfer to bypass or a run on battery."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 17
|
||
|
||
xupstbBreakerOpen TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"One of the UPS breakers or contactors has been opened."
|
||
--#SEVERITY MAJOR
|
||
::= 20
|
||
|
||
xupstbAlarmEntryAdded TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"An alarm not defined in the xups Well Known Alarms
|
||
(eg, an alarm defined in RFC1628)
|
||
has been added to the Alarm Table."
|
||
--#SEVERITY MAJOR
|
||
::= 21
|
||
|
||
xupstbAlarmEntryRemoved TRAP-TYPE
|
||
ENTERPRISE xupsTrapBasic
|
||
DESCRIPTION
|
||
"An alarm not defined in the xups Well Known Alarms
|
||
has been removed from the Alarm Table."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 22
|
||
|
||
|
||
-- The following alarms do not have equivalents as Basic Traps
|
||
-- xupstbAlarmBatteryBad ::= 23
|
||
-- xupstbOutputOffAsRequested ::= 24
|
||
-- xupstbDiagnosticTestFailed ::= 25
|
||
-- xupstbCommunicationsLost ::= 26
|
||
-- xupstbUpsShutdownPending ::= 27
|
||
-- xupstbAlarmTestInProgress ::= 28
|
||
-- xupstbAmbientTempBad ::= 29
|
||
-- xupstbContactActiveNotice ::= 30
|
||
-- xupstbContactInactiveNotice ::= 31
|
||
-- xupstbLossOfRedundancy ::= 32
|
||
-- xupstbAlarmTempBad ::= 33
|
||
-- xupstbAlarmChargerFailed ::= 34
|
||
-- xupstbAlarmFanFailure ::= 35
|
||
-- xupstbAlarmFuseFailure ::= 36
|
||
-- xupstbPowerSwitchBad ::= 37
|
||
-- xupstbModuleFailure ::= 38
|
||
-- xupstbOnAlternatePowerSource ::= 39
|
||
-- xupstbAltPowerNotAvailable ::= 40
|
||
-- xupstbNoticeCondition ::= 41
|
||
-- xupstbRemoteTempBad ::= 42
|
||
-- xupstbRemoteHumidityBad ::= 43
|
||
|
||
|
||
-- ****************************************************************************
|
||
-- ****************************************************************************
|
||
--
|
||
-- Traps from xupsTrapDefined source (xupstd):
|
||
--
|
||
|
||
xupstdControlOff TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The UPS output power will turn off in a number of
|
||
seconds equal to upsControlOutputOffTrapDelay."
|
||
--#SEVERITY CRITICAL
|
||
::= 1
|
||
|
||
xupstdControlOn TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The UPS output power will turn on in a number of
|
||
seconds equal to upsControlOutputOnTrapDelay."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 2
|
||
|
||
xupstdOnBattery TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The UPS has no AC input power and is running on
|
||
battery."
|
||
--#SEVERITY MAJOR
|
||
::= 3
|
||
|
||
xupstdLowBattery TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The UPS batteries are low. Tied to low battery
|
||
alarm condition."
|
||
--#SEVERITY CRITICAL
|
||
::= 4
|
||
|
||
xupstdUtilityPowerRestored TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"Input power has been restored after running on battery."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 5
|
||
|
||
xupstdReturnFromLowBattery TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The battery has recovered from a low battery condition."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 6
|
||
|
||
xupstdOutputOverload TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The ups has sensed an overload of greater than
|
||
106 percent. Tied to the 106% overload alarm."
|
||
--#SEVERITY MINOR
|
||
::= 7
|
||
|
||
xupstdInternalFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"Some component of the ups - rectifier, inverter,
|
||
control panel has failed. Tied to alarms indi-
|
||
cating failure."
|
||
--#SEVERITY CRITICAL
|
||
::= 8
|
||
|
||
xupstdBatteryDischarged TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The Battery Totally Discharged Alarm has occurred."
|
||
--#SEVERITY CRITICAL
|
||
::= 9
|
||
|
||
xupstdInverterFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The ups inverter is unavailable due to an internal failure."
|
||
--#SEVERITY CRITICAL
|
||
::= 10
|
||
|
||
xupstdOnBypass TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The ups has gone on bypass for some reason."
|
||
--#SEVERITY CRITICAL
|
||
::= 11
|
||
|
||
xupstdBypassNotAvailable TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The ups bypass is unavailable"
|
||
--#SEVERITY MAJOR
|
||
::= 12
|
||
|
||
xupstdOutputOff TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The ups output is switched off."
|
||
--#SEVERITY CRITICAL
|
||
::= 13
|
||
|
||
xupstdInputFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The ups input power is incorrect in voltage,
|
||
frequency, or phase rotation."
|
||
--#SEVERITY MINOR
|
||
::= 14
|
||
|
||
xupstdBuildingAlarm TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"One of the defined building alarms has occurred."
|
||
--#SEVERITY MAJOR
|
||
::= 15
|
||
|
||
xupstdShutdownImminent TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The ups shutdown imminent alarm has occurred."
|
||
--#SEVERITY CRITICAL
|
||
::= 16
|
||
|
||
xupstdOnInverter TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The ups is returned to utility power running the inverter
|
||
after either a transfer to bypass or a run on battery."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 17
|
||
|
||
xupstdBreakerOpen TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"One of the UPS breakers or contactors has been opened."
|
||
--#SEVERITY MAJOR
|
||
::= 20
|
||
|
||
xupstdAlarmEntryAdded TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"An alarm not defined in the xups Well Known Alarms
|
||
(eg, an alarm defined in RFC1628)
|
||
has been added to the Alarm Table."
|
||
--#SEVERITY MAJOR
|
||
::= 21
|
||
|
||
xupstdAlarmEntryRemoved TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"An alarm not defined in the xups Well Known Alarms
|
||
has been removed from the Alarm Table."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 22
|
||
|
||
xupstdAlarmBatteryBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"One or more batteries have been determined to require replacement."
|
||
--#SEVERITY MAJOR
|
||
::= 23
|
||
|
||
xupstdOutputOffAsRequested TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The UPS has shutdown as requested, i.e., the output is off."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 24
|
||
|
||
xupstdDiagnosticTestFailed TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The result of the last diagnostic test indicates a failure."
|
||
--#SEVERITY MINOR
|
||
::= 25
|
||
|
||
xupstdCommunicationsLost TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"A problem has been encountered in the communications
|
||
between the agent and the UPS."
|
||
--#SEVERITY MAJOR
|
||
::= 26
|
||
|
||
xupstdUpsShutdownPending TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"An xupsControlOutputOffDelay countdown is underway."
|
||
--#SEVERITY MAJOR
|
||
::= 27
|
||
|
||
xupstdAlarmTestInProgress TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"A test is in progress, as initiated and indicated by the
|
||
Battery Test Group."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 28
|
||
|
||
-- Provide additional information with the AmbientTemp trap
|
||
xupstdAmbientTempBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
xupsEnvAmbientTemp, xupsEnvAmbientLowerLimit,
|
||
xupsEnvAmbientUpperLimit }
|
||
DESCRIPTION
|
||
"The ambient temperature, xupsEnvAmbientTemp, has fallen below
|
||
the set lower limit, xupsEnvAmbientLowerLimit, or has risen above
|
||
the set upper limit, xupsEnvAmbientUpperLimit."
|
||
--#SEVERITY MAJOR
|
||
::= 29
|
||
|
||
-- Added to support the ConnectUPS Web/SNMP card's ability to monitor contact(s)
|
||
xupstdContactActiveNotice TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr }
|
||
DESCRIPTION
|
||
"The Contact indicated by xupsContactIndex is in its Active state.
|
||
The following are the situations that generate this trap:
|
||
For xupsContactType: and xupsContactState:
|
||
normallyOpen(1) and closedWithNotice(4)
|
||
normallyClosed(2) and openWithNotice(3)
|
||
anyChange(3) and openWithNotice(3) or closedWithNotice(4)"
|
||
--#SEVERITY MAJOR
|
||
::= 30
|
||
|
||
xupstdContactInactiveNotice TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr }
|
||
DESCRIPTION
|
||
"The Contact indicated by xupsContactIndex has changed to its Inactive state."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 31
|
||
|
||
xupstdLossOfRedundancy TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"A parallel UPS system is no longer operating in N+1 redundant mode;
|
||
this may be due to module failure or removal, or due to overloading."
|
||
--#SEVERITY MINOR
|
||
::= 32
|
||
|
||
xupstdAlarmTempBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"An internal temperature is out of tolerance."
|
||
--#SEVERITY MAJOR
|
||
::= 33
|
||
|
||
xupstdAlarmChargerFailed TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"An uncorrected problem has been detected within the UPS charger subsystem."
|
||
--#SEVERITY MAJOR
|
||
::= 34
|
||
|
||
xupstdAlarmFanFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The failure of one or more fans in the UPS has been detected."
|
||
--#SEVERITY MAJOR
|
||
::= 35
|
||
|
||
xupstdAlarmFuseFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"The failure of one or more fuses has been detected."
|
||
--#SEVERITY CRITICAL
|
||
::= 36
|
||
|
||
xupstdPowerSwitchBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"A Relay, Contactor, or Breaker has failed."
|
||
--#SEVERITY CRITICAL
|
||
::= 37
|
||
|
||
xupstdModuleFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"One module in a parallel or composite system has failed."
|
||
--#SEVERITY MAJOR
|
||
::= 38
|
||
|
||
-- Adds xupsInputSource to its var list
|
||
xupstdOnAlternatePowerSource TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, xupsInputSource }
|
||
DESCRIPTION
|
||
"The system is being powered by its Alternate Power Source, such as a
|
||
Secondary utility feed (on a dual AC input UPS), generator, flywheel,
|
||
or fuelcell."
|
||
--#SEVERITY MINOR
|
||
::= 39
|
||
|
||
xupstdAltPowerNotAvailable TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"On systems with a separate alternate power source (eg, dual AC inputs),
|
||
that alternate power source is currently not available. This could be
|
||
a problem if the primary power source (eg, utility) fails for a period
|
||
of time longer than that for which the internal batteries can supply power."
|
||
--#SEVERITY MINOR
|
||
::= 40
|
||
|
||
xupstdNoticeCondition TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
||
DESCRIPTION
|
||
"Some Notice condition exists which is not covered by the other traps.
|
||
This is like an xupstdInternalFailure, but at a lower severity level."
|
||
--#SEVERITY MINOR
|
||
::= 41
|
||
|
||
|
||
-- Provide additional information with the RemoteTemp and RemoteHumidity traps
|
||
xupstdRemoteTempBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit,
|
||
xupsEnvRemoteTempUpperLimit }
|
||
DESCRIPTION
|
||
"The remote temperature, xupsEnvRemoteTemp, has fallen below
|
||
the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above
|
||
the set upper limit, xupsEnvRemoteTempUpperLimit."
|
||
--#SEVERITY MAJOR
|
||
::= 42
|
||
|
||
xupstdRemoteHumidityBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapDefined
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit,
|
||
xupsEnvRemoteHumidityUpperLimit }
|
||
DESCRIPTION
|
||
"The remote temperature, xupsEnvRemoteHumidity, has fallen below
|
||
the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above
|
||
the set upper limit, xupsEnvRemoteHumidityUpperLimit."
|
||
--#SEVERITY MINOR
|
||
::= 43
|
||
|
||
|
||
|
||
-- ****************************************************************************
|
||
-- ****************************************************************************
|
||
--
|
||
-- Traps from xupsTrapPortN source (xupstp):
|
||
--
|
||
|
||
xupstpControlOff TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The UPS output power will turn off in a number of
|
||
seconds equal to upsControlOutputOffTrapDelay."
|
||
--#SEVERITY CRITICAL
|
||
::= 1
|
||
|
||
xupstpControlOn TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The UPS output power will turn on in a number of
|
||
seconds equal to upsControlOutputOnTrapDelay."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 2
|
||
|
||
xupstpOnBattery TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The UPS has no AC input power and is running on
|
||
battery."
|
||
--#SEVERITY MAJOR
|
||
::= 3
|
||
|
||
xupstpLowBattery TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The UPS batteries are low. Tied to low battery
|
||
alarm condition."
|
||
--#SEVERITY CRITICAL
|
||
::= 4
|
||
|
||
xupstpUtilityPowerRestored TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"Input power has been restored after running on battery."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 5
|
||
|
||
xupstpReturnFromLowBattery TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The battery has recovered from a low battery condition."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 6
|
||
|
||
xupstpOutputOverload TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The ups has sensed an overload of greater than
|
||
106 percent. Tied to the 106% overload alarm."
|
||
--#SEVERITY MINOR
|
||
::= 7
|
||
|
||
xupstpInternalFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"Some component of the ups - rectifier, inverter,
|
||
control panel has failed. Tied to alarms indi-
|
||
cating failure."
|
||
--#SEVERITY CRITICAL
|
||
::= 8
|
||
|
||
xupstpBatteryDischarged TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The Battery Totally Discharged Alarm has occurred."
|
||
--#SEVERITY CRITICAL
|
||
::= 9
|
||
|
||
xupstpInverterFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The ups inverter is unavailable due to an internal failure."
|
||
--#SEVERITY CRITICAL
|
||
::= 10
|
||
|
||
xupstpOnBypass TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The ups has gone on bypass for some reason."
|
||
--#SEVERITY CRITICAL
|
||
::= 11
|
||
|
||
xupstpBypassNotAvailable TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The ups bypass is unavailable"
|
||
--#SEVERITY MAJOR
|
||
::= 12
|
||
|
||
xupstpOutputOff TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The ups output is switched off."
|
||
--#SEVERITY CRITICAL
|
||
::= 13
|
||
|
||
xupstpInputFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The ups input power is incorrect in voltage,
|
||
frequency, or phase rotation."
|
||
--#SEVERITY MINOR
|
||
::= 14
|
||
|
||
xupstpBuildingAlarm TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"One of the defined building alarms has occurred."
|
||
--#SEVERITY MAJOR
|
||
::= 15
|
||
|
||
xupstpShutdownImminent TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The ups shutdown imminent alarm has occurred."
|
||
--#SEVERITY CRITICAL
|
||
::= 16
|
||
|
||
xupstpOnInverter TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The ups is returned to utility power running the inverter
|
||
after either a transfer to bypass or a run on battery."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 17
|
||
|
||
xupstpBreakerOpen TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"One of the UPS breakers or contactors has been opened."
|
||
--#SEVERITY MAJOR
|
||
::= 20
|
||
|
||
xupstpAlarmEntryAdded TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"An alarm not defined in the xups Well Known Alarms
|
||
(eg, an alarm defined in RFC1628)
|
||
has been added to the Alarm Table."
|
||
--#SEVERITY MAJOR
|
||
::= 21
|
||
|
||
xupstpAlarmEntryRemoved TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"An alarm not defined in the xups Well Known Alarms
|
||
has been removed from the Alarm Table."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 22
|
||
|
||
xupstpAlarmBatteryBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"One or more batteries have been determined to require replacement."
|
||
--#SEVERITY MAJOR
|
||
::= 23
|
||
|
||
xupstpOutputOffAsRequested TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The UPS has shutdown as requested, i.e., the output is off."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 24
|
||
|
||
xupstpDiagnosticTestFailed TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The result of the last diagnostic test indicates a failure."
|
||
--#SEVERITY MINOR
|
||
::= 25
|
||
|
||
xupstpCommunicationsLost TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"A problem has been encountered in the communications
|
||
between the agent and the UPS."
|
||
--#SEVERITY MAJOR
|
||
::= 26
|
||
|
||
xupstpUpsShutdownPending TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"An xupsControlOutputOffDelay countdown is underway."
|
||
--#SEVERITY MAJOR
|
||
::= 27
|
||
|
||
xupstpAlarmTestInProgress TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"A test is in progress, as initiated and indicated by the
|
||
Battery Test Group."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 28
|
||
|
||
-- Provide additional information with the AmbientTemp trap
|
||
xupstpAmbientTempBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr,
|
||
xupsEnvAmbientTemp, xupsEnvAmbientLowerLimit,
|
||
xupsEnvAmbientUpperLimit }
|
||
DESCRIPTION
|
||
"The ambient temperature, xupsEnvAmbientTemp, has fallen below
|
||
the set lower limit, xupsEnvAmbientLowerLimit, or has risen above
|
||
the set upper limit, xupsEnvAmbientUpperLimit."
|
||
--#SEVERITY MAJOR
|
||
::= 29
|
||
|
||
-- The following alarms do not have equivalents as PortN Traps
|
||
-- xupstdContactActiveNotice ::= 30
|
||
-- xupstdContactInactiveNotice ::= 31
|
||
|
||
xupstpLossOfRedundancy TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"A parallel UPS system is no longer operating in N+1 redundant mode;
|
||
this may be due to module failure or removal, or due to overloading."
|
||
--#SEVERITY MINOR
|
||
::= 32
|
||
|
||
|
||
xupstpAlarmTempBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"An internal temperature is out of tolerance."
|
||
--#SEVERITY MAJOR
|
||
::= 33
|
||
|
||
xupstpAlarmChargerFailed TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"An uncorrected problem has been detected within the UPS charger subsystem."
|
||
--#SEVERITY MAJOR
|
||
::= 34
|
||
|
||
xupstpAlarmFanFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The failure of one or more fans in the UPS has been detected."
|
||
--#SEVERITY MAJOR
|
||
::= 35
|
||
|
||
xupstpAlarmFuseFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The failure of one or more fuses has been detected."
|
||
--#SEVERITY CRITICAL
|
||
::= 36
|
||
|
||
xupstpPowerSwitchBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"A Relay, Contactor, or Breaker has failed."
|
||
--#SEVERITY CRITICAL
|
||
::= 37
|
||
|
||
xupstpModuleFailure TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"One module in a parallel or composite system has failed."
|
||
--#SEVERITY MAJOR
|
||
::= 38
|
||
|
||
xupstpOnAlternatePowerSource TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, xupsInputSource,
|
||
ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"The system is being powered by its Alternate Power Source, such as a
|
||
Secondary utility feed (on a dual AC input UPS), generator, flywheel,
|
||
or fuelcell."
|
||
--#SEVERITY MINOR
|
||
::= 39
|
||
|
||
xupstpAltPowerNotAvailable TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"On systems with a separate alternate power source (eg, dual AC inputs),
|
||
that alternate power source is currently not available. This could be
|
||
a problem if the primary power source (eg, utility) fails for a period
|
||
of time longer than that for which the internal batteries can supply power."
|
||
--#SEVERITY MINOR
|
||
::= 40
|
||
|
||
xupstpNoticeCondition TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
|
||
DESCRIPTION
|
||
"Some Notice condition exists which is not covered by the other traps.
|
||
This is like an xupstpInternalFailure, but at a lower severity level."
|
||
--#SEVERITY MINOR
|
||
::= 41
|
||
|
||
|
||
-- Provide additional information with the RemoteTemp and RemoteHumidity traps
|
||
xupstpRemoteTempBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr,
|
||
xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit,
|
||
xupsEnvRemoteTempUpperLimit }
|
||
DESCRIPTION
|
||
"The remote temperature, xupsEnvRemoteTemp, has fallen below
|
||
the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above
|
||
the set upper limit, xupsEnvRemoteTempUpperLimit."
|
||
--#SEVERITY MAJOR
|
||
::= 42
|
||
|
||
xupstpRemoteHumidityBad TRAP-TYPE
|
||
ENTERPRISE xupsTrapPortN
|
||
VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
||
ifIndex, ifDescr,
|
||
xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit,
|
||
xupsEnvRemoteHumidityUpperLimit }
|
||
DESCRIPTION
|
||
"The remote temperature, xupsEnvRemoteHumidity, has fallen below
|
||
the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above
|
||
the set upper limit, xupsEnvRemoteHumidityUpperLimit."
|
||
--#SEVERITY MINOR
|
||
::= 43
|
||
|
||
|
||
END
|