librenms/mibs/avtech/ROOMALERTST4E-MIB

203 lines
6.9 KiB
Plaintext

--
--defines ROOMALERTST4E-MIB for SNMP agent extension of Room Alert ST4E
--Contents: Global Registration Module
-- Room Alert OIDs - Enterprise 20916
--Version: 1.0.0
--Date: 29 January 2008
--Developed By: AVTECH Software, Inc.
--
--Copyright (c) 2008 AVTECH Software, Inc.
--
ROOMALERTST4E-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress, Counter, TimeTicks
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215;
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
products OBJECT IDENTIFIER ::= { avtech 1 }
ROOMALERTST4E OBJECT IDENTIFIER ::= { products 6 }
sensors OBJECT IDENTIFIER ::= { ROOMALERTST4E 1 }
signaltower OBJECT IDENTIFIER ::= { ROOMALERTST4E 2 }
traps OBJECT IDENTIFIER ::= { ROOMALERTST4E 3 }
internal OBJECT IDENTIFIER ::= { sensors 1 }
temperature OBJECT IDENTIFIER ::= { internal 1 }
humidity OBJECT IDENTIFIER ::= { internal 2 }
heat-index OBJECT IDENTIFIER ::= { internal 3 }
digital OBJECT IDENTIFIER ::= { sensors 2 }
digital-sen1 OBJECT IDENTIFIER ::= { digital 1 }
digital-sen2 OBJECT IDENTIFIER ::= { digital 2 }
switch OBJECT IDENTIFIER ::= { sensors 3 }
-- Room Alert ST4E MIB
-- Parameters
internal-tempf OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The internal temperature reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value."
::= { temperature 1 }
internal-tempc OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The internal temperature reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value."
::= { temperature 2 }
internal-humidity OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The internal relative humidity reading in %RH. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value."
::= { humidity 1 }
internal-heat-index OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The internal heat index reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value."
::= { heat-index 1 }
digital-sen1-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { digital-sen1 1 }
digital-sen1-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { digital-sen1 2 }
digital-sen1-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { digital-sen1 3 }
digital-sen1-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { digital-sen1 4 }
digital-sen2-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { digital-sen2 1 }
digital-sen2-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { digital-sen2 2 }
digital-sen2-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { digital-sen2 3 }
digital-sen2-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { digital-sen2 4 }
switch-sen1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED)."
::= { switch 1 }
red-led OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS current
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
::= { signaltower 1 }
amber-led OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS current
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
::= { signaltower 2 }
green-led OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS current
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
::= { signaltower 3 }
blue-led OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS current
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
::= { signaltower 4 }
white-led OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS current
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
::= { signaltower 5 }
alarm1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS current
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
::= { signaltower 6 }
alarm2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS current
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
::= { signaltower 7 }
alarmmessage OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "Last Alarm Message"
::= { traps 1 }
-- ROOMALERTST4E TRAPS
room-alert-st4e-snmp-trap TRAP-TYPE
ENTERPRISE ROOMALERTST4E
VARIABLES { alarmmessage }
DESCRIPTION "A room-alert-st4e-snmp-trap indicates that an alarm
condition has occurred on the sensor indicated
by the alarmmessage variable."
::= 2
END