mirror of
https://github.com/librenms/librenms.git
synced 2024-09-21 10:28:13 +00:00
feature: Added new EER and Water Flow Rate sensors (#8104)
* Add new EER sensor * remove bad RRD option * add waterflow sensor * add test data result * added test json data
This commit is contained in:
parent
1da86aa229
commit
c80f9726c8
@ -29,6 +29,8 @@ Currently we have support for the following health metrics along with the values
|
||||
| quality_factor | dB |
|
||||
| chromatic_disperision | ps/nm |
|
||||
| ber | ratio |
|
||||
| eer | eer |
|
||||
| waterflow | l/m |
|
||||
|
||||
#### Simple health discovery
|
||||
|
||||
|
7
html/includes/graphs/device/eer.inc.php
Normal file
7
html/includes/graphs/device/eer.inc.php
Normal file
@ -0,0 +1,7 @@
|
||||
<?php
|
||||
|
||||
$class = 'eer';
|
||||
$unit = '';
|
||||
$unit_long = '';
|
||||
|
||||
require 'includes/graphs/device/sensor.inc.php';
|
7
html/includes/graphs/device/waterflow.inc.php
Normal file
7
html/includes/graphs/device/waterflow.inc.php
Normal file
@ -0,0 +1,7 @@
|
||||
<?php
|
||||
|
||||
$class = 'waterflow';
|
||||
$unit = 'l/m';
|
||||
$unit_long = 'Liter Per Minute';
|
||||
|
||||
require 'includes/graphs/device/sensor.inc.php';
|
23
html/includes/graphs/sensor/eer.inc.php
Normal file
23
html/includes/graphs/sensor/eer.inc.php
Normal file
@ -0,0 +1,23 @@
|
||||
<?php
|
||||
|
||||
require 'includes/graphs/common.inc.php';
|
||||
|
||||
$rrd_options .= " COMMENT:' Min Last Max\\n'";
|
||||
|
||||
$sensor['sensor_descr_fixed'] = rrdtool_escape($sensor['sensor_descr'], 23);
|
||||
|
||||
$rrd_options .= " DEF:sensor=$rrd_filename:sensor:AVERAGE";
|
||||
$rrd_options .= " DEF:sensor_max=$rrd_filename:sensor:MAX";
|
||||
$rrd_options .= " DEF:sensor_min=$rrd_filename:sensor:MIN";
|
||||
$rrd_options .= " LINE1.5:sensor#cc0000:'".$sensor['sensor_descr_fixed']."'";
|
||||
$rrd_options .= " GPRINT:sensor_min$current_id:MIN:%4.0lf";
|
||||
$rrd_options .= ' GPRINT:sensor:LAST:%4.0lf';
|
||||
$rrd_options .= ' GPRINT:sensor_max:MAX:%4.0lf\\l';
|
||||
|
||||
if (is_numeric($sensor['sensor_limit'])) {
|
||||
$rrd_options .= ' HRULE:'.$sensor['sensor_limit'].'#999999::dashes';
|
||||
}
|
||||
|
||||
if (is_numeric($sensor['sensor_limit_low'])) {
|
||||
$rrd_options .= ' HRULE:'.$sensor['sensor_limit_low'].'#999999::dashes';
|
||||
}
|
23
html/includes/graphs/sensor/waterflow.inc.php
Normal file
23
html/includes/graphs/sensor/waterflow.inc.php
Normal file
@ -0,0 +1,23 @@
|
||||
<?php
|
||||
|
||||
require 'includes/graphs/common.inc.php';
|
||||
|
||||
$rrd_options .= " COMMENT:' Min Last Max\\n'";
|
||||
|
||||
$sensor['sensor_descr_fixed'] = rrdtool_escape($sensor['sensor_descr'], 15);
|
||||
|
||||
$rrd_options .= " DEF:sensor=$rrd_filename:sensor:AVERAGE";
|
||||
$rrd_options .= " DEF:sensor_max=$rrd_filename:sensor:MAX";
|
||||
$rrd_options .= " DEF:sensor_min=$rrd_filename:sensor:MIN";
|
||||
$rrd_options .= " LINE1.5:sensor#cc0000:'".$sensor['sensor_descr_fixed']."'";
|
||||
$rrd_options .= " GPRINT:sensor_min$current_id:MIN:%4.1lf";
|
||||
$rrd_options .= ' GPRINT:sensor:LAST:%4.1lf';
|
||||
$rrd_options .= ' GPRINT:sensor_max:MAX:%4.1lf\\l';
|
||||
|
||||
if (is_numeric($sensor['sensor_limit'])) {
|
||||
$rrd_options .= ' HRULE:'.$sensor['sensor_limit'].'#999999::dashes';
|
||||
}
|
||||
|
||||
if (is_numeric($sensor['sensor_limit_low'])) {
|
||||
$rrd_options .= ' HRULE:'.$sensor['sensor_limit_low'].'#999999::dashes';
|
||||
}
|
@ -399,6 +399,8 @@ $icons = array(
|
||||
'chromatic_dispersion' => 'indent',
|
||||
'ber' => 'sort-amount-desc',
|
||||
'quality_factor' => 'arrows',
|
||||
'eer' => 'snowflake-o',
|
||||
'waterflow' => 'tint',
|
||||
|
||||
);
|
||||
foreach (array('fanspeed','humidity','temperature','signal') as $item) {
|
||||
|
@ -5,27 +5,29 @@ $diskio = get_disks($device['device_id']);
|
||||
$mempools = dbFetchCell('select count(*) from mempools WHERE device_id = ?', array($device['device_id'])) + count_mib_mempools($device);
|
||||
$processor = dbFetchCell('select count(*) from processors WHERE device_id = ?', array($device['device_id'])) + count_mib_processors($device);
|
||||
|
||||
$charge = dbFetchCell("select count(*) from sensors WHERE sensor_class='charge' AND device_id = ?", array($device['device_id']));
|
||||
$temperatures = dbFetchCell("select count(*) from sensors WHERE sensor_class='temperature' AND device_id = ?", array($device['device_id']));
|
||||
$humidity = dbFetchCell("select count(*) from sensors WHERE sensor_class='humidity' AND device_id = ?", array($device['device_id']));
|
||||
$fans = dbFetchCell("select count(*) from sensors WHERE sensor_class='fanspeed' AND device_id = ?", array($device['device_id']));
|
||||
$volts = dbFetchCell("select count(*) from sensors WHERE sensor_class='voltage' AND device_id = ?", array($device['device_id']));
|
||||
$current = dbFetchCell("select count(*) from sensors WHERE sensor_class='current' AND device_id = ?", array($device['device_id']));
|
||||
$freqs = dbFetchCell("select count(*) from sensors WHERE sensor_class='frequency' AND device_id = ?", array($device['device_id']));
|
||||
$runtime = dbFetchCell("select count(*) from sensors WHERE sensor_class='runtime' AND device_id = ?", array($device['device_id']));
|
||||
$power = dbFetchCell("select count(*) from sensors WHERE sensor_class='power' AND device_id = ?", array($device['device_id']));
|
||||
$dBm = dbFetchCell("select count(*) from sensors WHERE sensor_class='dBm' AND device_id = ?", array($device['device_id']));
|
||||
$states = dbFetchCell("select count(*) from sensors WHERE sensor_class='state' AND device_id = ?", array($device['device_id']));
|
||||
$load = dbFetchCell("select count(*) from sensors WHERE sensor_class='load' AND device_id = ?", array($device['device_id']));
|
||||
$signal = dbFetchCell("select count(*) from sensors WHERE sensor_class='signal' AND device_id = ?", array($device['device_id']));
|
||||
$airflow = dbFetchCell("select count(*) from sensors WHERE sensor_class='airflow' AND device_id = ?", array($device['device_id']));
|
||||
$snr = dbFetchCell("select count(*) from sensors WHERE sensor_class='snr' AND device_id = ?", array($device['device_id']));
|
||||
$pressure = dbFetchCell("select count(*) from sensors WHERE sensor_class='pressure' AND device_id = ?", array($device['device_id']));
|
||||
$cooling = dbFetchCell("select count(*) from sensors WHERE sensor_class='cooling' AND device_id = ?", array($device['device_id']));
|
||||
$delay = dbFetchCell("select count(*) from sensors WHERE sensor_class='delay' AND device_id = ?", array($device['device_id']));
|
||||
$quality_factor = dbFetchCell("select count(*) from sensors WHERE sensor_class='quality_factor' AND device_id = ?", array($device['device_id']));
|
||||
$charge = dbFetchCell("select count(*) from sensors WHERE sensor_class='charge' AND device_id = ?", array($device['device_id']));
|
||||
$temperatures = dbFetchCell("select count(*) from sensors WHERE sensor_class='temperature' AND device_id = ?", array($device['device_id']));
|
||||
$humidity = dbFetchCell("select count(*) from sensors WHERE sensor_class='humidity' AND device_id = ?", array($device['device_id']));
|
||||
$fans = dbFetchCell("select count(*) from sensors WHERE sensor_class='fanspeed' AND device_id = ?", array($device['device_id']));
|
||||
$volts = dbFetchCell("select count(*) from sensors WHERE sensor_class='voltage' AND device_id = ?", array($device['device_id']));
|
||||
$current = dbFetchCell("select count(*) from sensors WHERE sensor_class='current' AND device_id = ?", array($device['device_id']));
|
||||
$freqs = dbFetchCell("select count(*) from sensors WHERE sensor_class='frequency' AND device_id = ?", array($device['device_id']));
|
||||
$runtime = dbFetchCell("select count(*) from sensors WHERE sensor_class='runtime' AND device_id = ?", array($device['device_id']));
|
||||
$power = dbFetchCell("select count(*) from sensors WHERE sensor_class='power' AND device_id = ?", array($device['device_id']));
|
||||
$dBm = dbFetchCell("select count(*) from sensors WHERE sensor_class='dBm' AND device_id = ?", array($device['device_id']));
|
||||
$states = dbFetchCell("select count(*) from sensors WHERE sensor_class='state' AND device_id = ?", array($device['device_id']));
|
||||
$load = dbFetchCell("select count(*) from sensors WHERE sensor_class='load' AND device_id = ?", array($device['device_id']));
|
||||
$signal = dbFetchCell("select count(*) from sensors WHERE sensor_class='signal' AND device_id = ?", array($device['device_id']));
|
||||
$airflow = dbFetchCell("select count(*) from sensors WHERE sensor_class='airflow' AND device_id = ?", array($device['device_id']));
|
||||
$snr = dbFetchCell("select count(*) from sensors WHERE sensor_class='snr' AND device_id = ?", array($device['device_id']));
|
||||
$pressure = dbFetchCell("select count(*) from sensors WHERE sensor_class='pressure' AND device_id = ?", array($device['device_id']));
|
||||
$cooling = dbFetchCell("select count(*) from sensors WHERE sensor_class='cooling' AND device_id = ?", array($device['device_id']));
|
||||
$delay = dbFetchCell("select count(*) from sensors WHERE sensor_class='delay' AND device_id = ?", array($device['device_id']));
|
||||
$quality_factor = dbFetchCell("select count(*) from sensors WHERE sensor_class='quality_factor' AND device_id = ?", array($device['device_id']));
|
||||
$chromatic_dispersion = dbFetchCell("select count(*) from sensors WHERE sensor_class='chromatic_dispersion' AND device_id = ?", array($device['device_id']));
|
||||
$ber = dbFetchCell("select count(*) from sensors WHERE sensor_class='ber' AND device_id = ?", array($device['device_id']));
|
||||
$ber = dbFetchCell("select count(*) from sensors WHERE sensor_class='ber' AND device_id = ?", array($device['device_id']));
|
||||
$eer = dbFetchCell("select count(*) from sensors WHERE sensor_class='eer' AND device_id = ?", array($device['device_id']));
|
||||
$waterflow = dbFetchCell("select count(*) from sensors WHERE sensor_class='waterflow' AND device_id = ?", array($device['device_id']));
|
||||
|
||||
unset($datas);
|
||||
$datas[] = 'overview';
|
||||
@ -129,32 +131,42 @@ if ($ber) {
|
||||
$datas[] = 'ber';
|
||||
}
|
||||
|
||||
$type_text['overview'] = 'Overview';
|
||||
$type_text['charge'] = 'Battery Charge';
|
||||
$type_text['temperature'] = 'Temperature';
|
||||
$type_text['humidity'] = 'Humidity';
|
||||
$type_text['mempool'] = 'Memory';
|
||||
$type_text['storage'] = 'Disk Usage';
|
||||
$type_text['diskio'] = 'Disk I/O';
|
||||
$type_text['processor'] = 'Processor';
|
||||
$type_text['voltage'] = 'Voltage';
|
||||
$type_text['fanspeed'] = 'Fanspeed';
|
||||
$type_text['frequency'] = 'Frequency';
|
||||
$type_text['runtime'] = 'Runtime remaining';
|
||||
$type_text['current'] = 'Current';
|
||||
$type_text['power'] = 'Power';
|
||||
$type_text['dbm'] = 'dBm';
|
||||
$type_text['state'] = 'State';
|
||||
$type_text['load'] = 'Load';
|
||||
$type_text['signal'] = 'Signal';
|
||||
$type_text['airflow'] = 'Airflow';
|
||||
$type_text['snr'] = 'SNR';
|
||||
$type_text['pressure'] = 'Pressure';
|
||||
$type_text['cooling'] = 'Cooling';
|
||||
$type_text['delay'] = 'Delay';
|
||||
$type_text['quality_factor'] = 'Quality factor';
|
||||
$type_text['chromatic_dispersion'] = 'Chromatic Dispersion';
|
||||
$type_text['ber'] = 'Bit Error Rate';
|
||||
if ($eer) {
|
||||
$datas[] = 'eer';
|
||||
}
|
||||
|
||||
if ($waterflow) {
|
||||
$datas[] = 'waterflow';
|
||||
}
|
||||
|
||||
$type_text['overview'] = 'Overview';
|
||||
$type_text['charge'] = 'Battery Charge';
|
||||
$type_text['temperature'] = 'Temperature';
|
||||
$type_text['humidity'] = 'Humidity';
|
||||
$type_text['mempool'] = 'Memory';
|
||||
$type_text['storage'] = 'Disk Usage';
|
||||
$type_text['diskio'] = 'Disk I/O';
|
||||
$type_text['processor'] = 'Processor';
|
||||
$type_text['voltage'] = 'Voltage';
|
||||
$type_text['fanspeed'] = 'Fanspeed';
|
||||
$type_text['frequency'] = 'Frequency';
|
||||
$type_text['runtime'] = 'Runtime remaining';
|
||||
$type_text['current'] = 'Current';
|
||||
$type_text['power'] = 'Power';
|
||||
$type_text['dbm'] = 'dBm';
|
||||
$type_text['state'] = 'State';
|
||||
$type_text['load'] = 'Load';
|
||||
$type_text['signal'] = 'Signal';
|
||||
$type_text['airflow'] = 'Airflow';
|
||||
$type_text['snr'] = 'SNR';
|
||||
$type_text['pressure'] = 'Pressure';
|
||||
$type_text['cooling'] = 'Cooling';
|
||||
$type_text['delay'] = 'Delay';
|
||||
$type_text['quality_factor'] = 'Quality factor';
|
||||
$type_text['chromatic_dispersion'] = 'Chromatic Dispersion';
|
||||
$type_text['ber'] = 'Bit Error Rate';
|
||||
$type_text['eer'] = 'Energy Efficiency Ratio';
|
||||
$type_text['waterflow'] = 'Water Flow Rate';
|
||||
|
||||
$link_array = array(
|
||||
'page' => 'device',
|
||||
|
7
html/pages/device/health/eer.inc.php
Normal file
7
html/pages/device/health/eer.inc.php
Normal file
@ -0,0 +1,7 @@
|
||||
<?php
|
||||
|
||||
$class = 'eer';
|
||||
$unit = '';
|
||||
$graph_type = 'sensor_eer';
|
||||
|
||||
require 'sensors.inc.php';
|
7
html/pages/device/health/waterflow.inc.php
Normal file
7
html/pages/device/health/waterflow.inc.php
Normal file
@ -0,0 +1,7 @@
|
||||
<?php
|
||||
|
||||
$class = 'waterflow';
|
||||
$unit = 'l/m';
|
||||
$graph_type = 'sensor_waterflow';
|
||||
|
||||
require 'sensors.inc.php';
|
@ -76,6 +76,8 @@ require 'overview/sensors/delay.inc.php';
|
||||
require 'overview/sensors/quality_factor.inc.php';
|
||||
require 'overview/sensors/chromatic_dispersion.inc.php';
|
||||
require 'overview/sensors/ber.inc.php';
|
||||
require 'overview/sensors/eer.inc.php';
|
||||
require 'overview/sensors/waterflow.inc.php';
|
||||
require 'overview/eventlog.inc.php';
|
||||
require 'overview/services.inc.php';
|
||||
require 'overview/syslog.inc.php';
|
||||
|
8
html/pages/device/overview/sensors/eer.inc.php
Normal file
8
html/pages/device/overview/sensors/eer.inc.php
Normal file
@ -0,0 +1,8 @@
|
||||
<?php
|
||||
|
||||
$graph_type = 'sensor_eer';
|
||||
$sensor_class = 'eer';
|
||||
$sensor_unit = '';
|
||||
$sensor_type = 'Energy Efficiency Ratio';
|
||||
|
||||
require 'pages/device/overview/generic/sensor.inc.php';
|
8
html/pages/device/overview/sensors/waterflow.inc.php
Normal file
8
html/pages/device/overview/sensors/waterflow.inc.php
Normal file
@ -0,0 +1,8 @@
|
||||
<?php
|
||||
|
||||
$graph_type = 'sensor_waterflow';
|
||||
$sensor_class = 'waterflow';
|
||||
$sensor_unit = 'l/m';
|
||||
$sensor_type = 'Water Flow Rate';
|
||||
|
||||
require 'pages/device/overview/generic/sensor.inc.php';
|
@ -79,6 +79,12 @@ if ($used_sensors['chromatic_dispersion']) {
|
||||
if ($used_sensors['ber']) {
|
||||
$datas[] = 'ber';
|
||||
}
|
||||
if ($used_sensors['eer']) {
|
||||
$datas[] = 'eer';
|
||||
}
|
||||
if ($used_sensors['waterflow']) {
|
||||
$datas[] = 'waterflow';
|
||||
}
|
||||
|
||||
$type_text['overview'] = "Overview";
|
||||
$type_text['temperature'] = "Temperature";
|
||||
@ -107,6 +113,8 @@ $type_text['delay'] = 'Delay';
|
||||
$type_text['quality_factor'] = 'Quality factor';
|
||||
$type_text['chromatic_dispersion'] = 'Chromatic Dispersion';
|
||||
$type_text['ber'] = 'Bit Error Rate';
|
||||
$type_text['eer'] = 'Energy Efficiency Ratio';
|
||||
$type_text['waterflow'] = 'Water Flow Rate';
|
||||
|
||||
if (!$vars['metric']) {
|
||||
$vars['metric'] = "processor";
|
||||
|
7
html/pages/health/eer.inc.php
Normal file
7
html/pages/health/eer.inc.php
Normal file
@ -0,0 +1,7 @@
|
||||
<?php
|
||||
|
||||
$graph_type = 'sensor_eer';
|
||||
$class = 'eer';
|
||||
$unit = '';
|
||||
|
||||
require 'pages/health/sensors.inc.php';
|
7
html/pages/health/waterflow.inc.php
Normal file
7
html/pages/health/waterflow.inc.php
Normal file
@ -0,0 +1,7 @@
|
||||
<?php
|
||||
|
||||
$graph_type = 'sensor_waterflow';
|
||||
$class = 'waterflow';
|
||||
$unit = 'l/m';
|
||||
|
||||
require 'pages/health/sensors.inc.php';
|
@ -1,6 +1,23 @@
|
||||
mib: KELVIN-pCOWeb-Chiller-MIB
|
||||
modules:
|
||||
sensors:
|
||||
waterflow:
|
||||
data:
|
||||
-
|
||||
oid: flow-value.0
|
||||
value: flow-value
|
||||
divisor: 10
|
||||
num_oid: .1.3.6.1.4.1.9839.2.1.2.73.
|
||||
descr: Water Flow Rate
|
||||
index: 'flow-value.{{ $index }}'
|
||||
eer:
|
||||
data:
|
||||
-
|
||||
oid: analogObjects.120
|
||||
value: analogObjects
|
||||
num_oid: .1.3.6.1.4.1.9839.2.1.3.
|
||||
descr: Energy Efficiency Ratio
|
||||
index: 'analogObjects.{{ $index }}'
|
||||
power:
|
||||
data:
|
||||
-
|
||||
|
@ -417,6 +417,8 @@ function sensor_low_limit($class, $current)
|
||||
case 'quality_factor':
|
||||
case 'chromatic_dispersion':
|
||||
case 'ber':
|
||||
case 'eer':
|
||||
case 'waterflow':
|
||||
}//end switch
|
||||
|
||||
return $limit;
|
||||
|
@ -78,6 +78,8 @@ $run_sensors = array(
|
||||
'quality_factor',
|
||||
'chromatic_dispersion',
|
||||
'ber',
|
||||
'eer',
|
||||
'waterflow',
|
||||
);
|
||||
sensors($run_sensors, $device, $valid, $pre_cache);
|
||||
unset(
|
||||
|
788
tests/data/pcoweb-rittalchiller.json
Normal file
788
tests/data/pcoweb-rittalchiller.json
Normal file
@ -0,0 +1,788 @@
|
||||
{
|
||||
"os": {
|
||||
"discovery": {
|
||||
"devices": [
|
||||
{
|
||||
"sysName": "<private>",
|
||||
"sysObjectID": ".1.3.6.1.4.1.9839.2606.1",
|
||||
"sysDescr": "Rittal IT Chiller",
|
||||
"sysContact": null,
|
||||
"version": null,
|
||||
"hardware": "",
|
||||
"features": null,
|
||||
"location": null,
|
||||
"os": "pcoweb-rittalchiller",
|
||||
"type": "environment",
|
||||
"serial": null,
|
||||
"icon": "rittal.svg"
|
||||
}
|
||||
]
|
||||
},
|
||||
"poller": {
|
||||
"devices": [
|
||||
{
|
||||
"sysName": "<private>",
|
||||
"sysObjectID": ".1.3.6.1.4.1.9839.2606.1",
|
||||
"sysDescr": "Rittal IT Chiller",
|
||||
"sysContact": "<private>",
|
||||
"version": null,
|
||||
"hardware": "",
|
||||
"features": null,
|
||||
"location": "<private>",
|
||||
"os": "pcoweb-rittalchiller",
|
||||
"type": "environment",
|
||||
"serial": null,
|
||||
"icon": "rittal.svg"
|
||||
}
|
||||
]
|
||||
}
|
||||
},
|
||||
"sensors": {
|
||||
"discovery": {
|
||||
"sensors": [
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "current",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.74.0",
|
||||
"sensor_index": "amp-value.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Current Consumption",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "1",
|
||||
"sensor_limit": "1.5",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": null,
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "humidity",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.90.0",
|
||||
"sensor_index": "pp1.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Hydraulic Pump 1 Speed",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "100",
|
||||
"sensor_limit": "70",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "30",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "humidity",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.91.0",
|
||||
"sensor_index": "pp2.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Hydraulic Pump 2 Speed",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "0",
|
||||
"sensor_limit": "70",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "30",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "power",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.103.0",
|
||||
"sensor_index": "analogObjects.103.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Power Consumption",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "100",
|
||||
"sensor_current": "700",
|
||||
"sensor_limit": "1050",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": null,
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "temperature",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.140.0",
|
||||
"sensor_index": "analogObjects.140.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Temperature Ambient",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "3.6",
|
||||
"sensor_limit": "23.6",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "-6.4",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "temperature",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.137.0",
|
||||
"sensor_index": "analogObjects.137.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Temperature Out",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "17.9",
|
||||
"sensor_limit": "37.9",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "7.9",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "temperature",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.136.0",
|
||||
"sensor_index": "analogObjects.136.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Temperature In",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "18",
|
||||
"sensor_limit": "38",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "8",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "pressure",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.138.0",
|
||||
"sensor_index": "analogObjects.138.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Hydraulic Pressure (Suction)",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "10",
|
||||
"sensor_current": "160",
|
||||
"sensor_limit": "168",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "152",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "pressure",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.133.0",
|
||||
"sensor_index": "analogObjects.133.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Hydraulic Pressure (Discharge)",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "10",
|
||||
"sensor_current": "370",
|
||||
"sensor_limit": "388.5",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "351.5",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "pressure",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.77.0",
|
||||
"sensor_index": "pressione1.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Condensation Pressure 1",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "10",
|
||||
"sensor_current": "700",
|
||||
"sensor_limit": "735",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "665",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "pressure",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.78.0",
|
||||
"sensor_index": "pressione2.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Condensation Pressure 2",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "10",
|
||||
"sensor_current": "0",
|
||||
"sensor_limit": "0",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "0",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "cooling",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.100.0",
|
||||
"sensor_index": "cooling-capacity.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Free Cooling Capacity",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "100",
|
||||
"sensor_current": "33900",
|
||||
"sensor_limit": "35595",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "32205",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "cooling",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.101.0",
|
||||
"sensor_index": "freecooling-capacity.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Compressor Cooling Capacity",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "100",
|
||||
"sensor_current": "0",
|
||||
"sensor_limit": "0",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "0",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "cooling",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.102.0",
|
||||
"sensor_index": "total-capacity.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Total cooling Capacity",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "100",
|
||||
"sensor_current": "33900",
|
||||
"sensor_limit": "35595",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "32205",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "eer",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.3.120.0",
|
||||
"sensor_index": "analogObjects.120.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Energy Efficiency Ratio",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "0",
|
||||
"sensor_limit": null,
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": null,
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "waterflow",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.73.0",
|
||||
"sensor_index": "flow-value.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Water Flow Rate",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "141.3",
|
||||
"sensor_limit": null,
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": null,
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
}
|
||||
],
|
||||
"state_indexes": []
|
||||
},
|
||||
"poller": {
|
||||
"sensors": [
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "current",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.74.0",
|
||||
"sensor_index": "amp-value.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Current Consumption",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "1",
|
||||
"sensor_limit": "1.5",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": null,
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "humidity",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.90.0",
|
||||
"sensor_index": "pp1.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Hydraulic Pump 1 Speed",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "100",
|
||||
"sensor_limit": "70",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "30",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "humidity",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.91.0",
|
||||
"sensor_index": "pp2.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Hydraulic Pump 2 Speed",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "0",
|
||||
"sensor_limit": "70",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "30",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "power",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.103.0",
|
||||
"sensor_index": "analogObjects.103.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Power Consumption",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "100",
|
||||
"sensor_current": "700",
|
||||
"sensor_limit": "1050",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": null,
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "temperature",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.140.0",
|
||||
"sensor_index": "analogObjects.140.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Temperature Ambient",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "3.6",
|
||||
"sensor_limit": "23.6",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "-6.4",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "temperature",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.137.0",
|
||||
"sensor_index": "analogObjects.137.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Temperature Out",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "17.9",
|
||||
"sensor_limit": "37.9",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "7.9",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "temperature",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.136.0",
|
||||
"sensor_index": "analogObjects.136.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Temperature In",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "18",
|
||||
"sensor_limit": "38",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "8",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "pressure",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.138.0",
|
||||
"sensor_index": "analogObjects.138.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Hydraulic Pressure (Suction)",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "10",
|
||||
"sensor_current": "160",
|
||||
"sensor_limit": "168",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "152",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "pressure",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.133.0",
|
||||
"sensor_index": "analogObjects.133.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Hydraulic Pressure (Discharge)",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "10",
|
||||
"sensor_current": "370",
|
||||
"sensor_limit": "388.5",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "351.5",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "pressure",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.77.0",
|
||||
"sensor_index": "pressione1.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Condensation Pressure 1",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "10",
|
||||
"sensor_current": "700",
|
||||
"sensor_limit": "735",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "665",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "pressure",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.78.0",
|
||||
"sensor_index": "pressione2.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Condensation Pressure 2",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "10",
|
||||
"sensor_current": "0",
|
||||
"sensor_limit": "0",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "0",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "cooling",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.100.0",
|
||||
"sensor_index": "cooling-capacity.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Free Cooling Capacity",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "100",
|
||||
"sensor_current": "33900",
|
||||
"sensor_limit": "35595",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "32205",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "cooling",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.101.0",
|
||||
"sensor_index": "freecooling-capacity.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Compressor Cooling Capacity",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "100",
|
||||
"sensor_current": "0",
|
||||
"sensor_limit": "0",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "0",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "cooling",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.102.0",
|
||||
"sensor_index": "total-capacity.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Total cooling Capacity",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "100",
|
||||
"sensor_current": "33900",
|
||||
"sensor_limit": "35595",
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": "32205",
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "eer",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.3.120.0",
|
||||
"sensor_index": "analogObjects.120.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Energy Efficiency Ratio",
|
||||
"sensor_divisor": "1",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "48",
|
||||
"sensor_limit": null,
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": null,
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": "0",
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
},
|
||||
{
|
||||
"sensor_deleted": "0",
|
||||
"sensor_class": "waterflow",
|
||||
"poller_type": "snmp",
|
||||
"sensor_oid": ".1.3.6.1.4.1.9839.2.1.2.73.0",
|
||||
"sensor_index": "flow-value.0",
|
||||
"sensor_type": "pcoweb-rittalchiller",
|
||||
"sensor_descr": "Water Flow Rate",
|
||||
"sensor_divisor": "10",
|
||||
"sensor_multiplier": "1",
|
||||
"sensor_current": "141.3",
|
||||
"sensor_limit": null,
|
||||
"sensor_limit_warn": null,
|
||||
"sensor_limit_low": null,
|
||||
"sensor_limit_low_warn": null,
|
||||
"sensor_alert": "1",
|
||||
"sensor_custom": "No",
|
||||
"entPhysicalIndex": null,
|
||||
"entPhysicalIndex_measured": null,
|
||||
"sensor_prev": null,
|
||||
"user_func": null,
|
||||
"state_name": null
|
||||
}
|
||||
],
|
||||
"state_indexes": []
|
||||
}
|
||||
}
|
||||
}
|
@ -1,2 +1,178 @@
|
||||
1.3.6.1.2.1.1.1.0|4|Rittal IT Chiller
|
||||
1.3.6.1.2.1.1.2.0|6|1.3.6.1.4.1.9839.2606.1
|
||||
1.3.6.1.2.1.1.3.0|67|281177388
|
||||
1.3.6.1.2.1.1.4.0|4|<private>
|
||||
1.3.6.1.2.1.1.5.0|4|<private>
|
||||
1.3.6.1.2.1.1.6.0|4|<private>
|
||||
1.3.6.1.2.1.2.2.1.1.1|2|1
|
||||
1.3.6.1.2.1.2.2.1.1.2|2|2
|
||||
1.3.6.1.2.1.2.2.1.2.1|4|lo
|
||||
1.3.6.1.2.1.2.2.1.2.2|4|eth0
|
||||
1.3.6.1.2.1.2.2.1.3.1|2|24
|
||||
1.3.6.1.2.1.2.2.1.3.2|2|6
|
||||
1.3.6.1.2.1.2.2.1.4.1|2|16436
|
||||
1.3.6.1.2.1.2.2.1.4.2|2|1500
|
||||
1.3.6.1.2.1.2.2.1.5.1|66|10000000
|
||||
1.3.6.1.2.1.2.2.1.5.2|66|10000000
|
||||
1.3.6.1.2.1.2.2.1.6.1|4|
|
||||
1.3.6.1.2.1.2.2.1.6.2|4x|000A5C1065DD
|
||||
1.3.6.1.2.1.2.2.1.7.1|2|1
|
||||
1.3.6.1.2.1.2.2.1.7.2|2|1
|
||||
1.3.6.1.2.1.2.2.1.8.1|2|1
|
||||
1.3.6.1.2.1.2.2.1.8.2|2|1
|
||||
1.3.6.1.2.1.2.2.1.10.1|65|31717028
|
||||
1.3.6.1.2.1.2.2.1.10.2|65|856022279
|
||||
1.3.6.1.2.1.2.2.1.11.1|65|157706
|
||||
1.3.6.1.2.1.2.2.1.11.2|65|8984368
|
||||
1.3.6.1.2.1.2.2.1.13.1|65|0
|
||||
1.3.6.1.2.1.2.2.1.13.2|65|3710
|
||||
1.3.6.1.2.1.2.2.1.14.1|65|0
|
||||
1.3.6.1.2.1.2.2.1.14.2|65|4
|
||||
1.3.6.1.2.1.2.2.1.16.1|65|31717028
|
||||
1.3.6.1.2.1.2.2.1.16.2|65|0
|
||||
1.3.6.1.2.1.2.2.1.17.1|65|157706
|
||||
1.3.6.1.2.1.2.2.1.17.2|65|5671997
|
||||
1.3.6.1.2.1.2.2.1.19.1|65|0
|
||||
1.3.6.1.2.1.2.2.1.19.2|65|0
|
||||
1.3.6.1.2.1.2.2.1.20.1|65|0
|
||||
1.3.6.1.2.1.2.2.1.20.2|65|0
|
||||
1.3.6.1.2.1.2.2.1.21.1|66|0
|
||||
1.3.6.1.2.1.2.2.1.21.2|66|0
|
||||
1.3.6.1.2.1.2.2.1.22.1|6|0.0
|
||||
1.3.6.1.2.1.2.2.1.22.2|6|0.0
|
||||
1.3.6.1.2.1.4.3.0|65|5775772
|
||||
1.3.6.1.2.1.4.4.0|65|0
|
||||
1.3.6.1.2.1.4.5.0|65|0
|
||||
1.3.6.1.2.1.4.6.0|65|0
|
||||
1.3.6.1.2.1.4.7.0|65|0
|
||||
1.3.6.1.2.1.4.8.0|65|0
|
||||
1.3.6.1.2.1.4.9.0|65|5308469
|
||||
1.3.6.1.2.1.4.10.0|65|5758900
|
||||
1.3.6.1.2.1.4.11.0|65|78848
|
||||
1.3.6.1.2.1.4.12.0|65|0
|
||||
1.3.6.1.2.1.4.14.0|65|0
|
||||
1.3.6.1.2.1.4.15.0|65|0
|
||||
1.3.6.1.2.1.4.16.0|65|0
|
||||
1.3.6.1.2.1.4.17.0|65|0
|
||||
1.3.6.1.2.1.4.18.0|65|0
|
||||
1.3.6.1.2.1.4.19.0|65|0
|
||||
1.3.6.1.2.1.4.20.1.2.10.1.22.31|2|2
|
||||
1.3.6.1.2.1.4.20.1.2.127.0.0.1|2|1
|
||||
1.3.6.1.2.1.4.20.1.3.10.1.22.31|64|255.255.255.0
|
||||
1.3.6.1.2.1.4.20.1.3.127.0.0.1|64|255.0.0.0
|
||||
1.3.6.1.2.1.4.22.1.2.2.10.1.22.1|4x|001B17000130
|
||||
1.3.6.1.2.1.5.1.0|65|450178
|
||||
1.3.6.1.2.1.5.2.0|65|5486
|
||||
1.3.6.1.2.1.5.3.0|65|84564
|
||||
1.3.6.1.2.1.5.4.0|65|0
|
||||
1.3.6.1.2.1.5.5.0|65|0
|
||||
1.3.6.1.2.1.5.6.0|65|0
|
||||
1.3.6.1.2.1.5.7.0|65|0
|
||||
1.3.6.1.2.1.5.8.0|65|365614
|
||||
1.3.6.1.2.1.5.9.0|65|0
|
||||
1.3.6.1.2.1.5.10.0|65|0
|
||||
1.3.6.1.2.1.5.11.0|65|0
|
||||
1.3.6.1.2.1.5.12.0|65|0
|
||||
1.3.6.1.2.1.5.13.0|65|0
|
||||
1.3.6.1.2.1.5.14.0|65|444474
|
||||
1.3.6.1.2.1.5.15.0|65|0
|
||||
1.3.6.1.2.1.5.16.0|65|78860
|
||||
1.3.6.1.2.1.5.17.0|65|0
|
||||
1.3.6.1.2.1.5.18.0|65|0
|
||||
1.3.6.1.2.1.5.19.0|65|0
|
||||
1.3.6.1.2.1.5.20.0|65|0
|
||||
1.3.6.1.2.1.5.21.0|65|0
|
||||
1.3.6.1.2.1.5.22.0|65|365614
|
||||
1.3.6.1.2.1.5.23.0|65|0
|
||||
1.3.6.1.2.1.5.24.0|65|0
|
||||
1.3.6.1.2.1.5.25.0|65|0
|
||||
1.3.6.1.2.1.5.26.0|65|0
|
||||
1.3.6.1.2.1.6.5.0|65|0
|
||||
1.3.6.1.2.1.6.6.0|65|10364
|
||||
1.3.6.1.2.1.6.7.0|65|0
|
||||
1.3.6.1.2.1.6.8.0|65|73
|
||||
1.3.6.1.2.1.6.9.0|66|0
|
||||
1.3.6.1.2.1.6.10.0|65|155860
|
||||
1.3.6.1.2.1.6.11.0|65|173649
|
||||
1.3.6.1.2.1.6.12.0|65|118
|
||||
1.3.6.1.2.1.6.14.0|65|0
|
||||
1.3.6.1.2.1.6.15.0|65|0
|
||||
1.3.6.1.2.1.7.1.0|65|5055095
|
||||
1.3.6.1.2.1.7.2.0|65|78860
|
||||
1.3.6.1.2.1.7.3.0|65|0
|
||||
1.3.6.1.2.1.7.4.0|65|5140777
|
||||
1.3.6.1.2.1.11.1.0|65|5055161
|
||||
1.3.6.1.2.1.11.2.0|65|5055158
|
||||
1.3.6.1.2.1.11.3.0|65|0
|
||||
1.3.6.1.2.1.11.4.0|65|6
|
||||
1.3.6.1.2.1.11.5.0|65|0
|
||||
1.3.6.1.2.1.11.6.0|65|0
|
||||
1.3.6.1.2.1.11.8.0|65|0
|
||||
1.3.6.1.2.1.11.9.0|65|0
|
||||
1.3.6.1.2.1.11.10.0|65|0
|
||||
1.3.6.1.2.1.11.11.0|65|0
|
||||
1.3.6.1.2.1.11.12.0|65|0
|
||||
1.3.6.1.2.1.11.13.0|65|32282158
|
||||
1.3.6.1.2.1.11.14.0|65|0
|
||||
1.3.6.1.2.1.11.15.0|65|2677335
|
||||
1.3.6.1.2.1.11.16.0|65|9520
|
||||
1.3.6.1.2.1.11.17.0|65|0
|
||||
1.3.6.1.2.1.11.18.0|65|0
|
||||
1.3.6.1.2.1.11.19.0|65|0
|
||||
1.3.6.1.2.1.11.20.0|65|0
|
||||
1.3.6.1.2.1.11.21.0|65|0
|
||||
1.3.6.1.2.1.11.22.0|65|0
|
||||
1.3.6.1.2.1.11.24.0|65|0
|
||||
1.3.6.1.2.1.11.25.0|65|0
|
||||
1.3.6.1.2.1.11.26.0|65|0
|
||||
1.3.6.1.2.1.11.27.0|65|0
|
||||
1.3.6.1.2.1.11.28.0|65|5055156
|
||||
1.3.6.1.2.1.11.29.0|65|4
|
||||
1.3.6.1.2.1.11.30.0|2|2
|
||||
1.3.6.1.2.1.11.31.0|65|0
|
||||
1.3.6.1.2.1.11.32.0|65|0
|
||||
1.3.6.1.4.1.2021.4.3.0|2|0
|
||||
1.3.6.1.4.1.2021.4.4.0|2|0
|
||||
1.3.6.1.4.1.2021.4.5.0|2|14860
|
||||
1.3.6.1.4.1.2021.4.6.0|2|1276
|
||||
1.3.6.1.4.1.2021.4.11.0|2|1280
|
||||
1.3.6.1.4.1.2021.4.13.0|2|0
|
||||
1.3.6.1.4.1.2021.4.14.0|2|860
|
||||
1.3.6.1.4.1.2021.4.15.0|2|5640
|
||||
1.3.6.1.4.1.2021.10.1.5.1|2|40
|
||||
1.3.6.1.4.1.2021.10.1.5.2|2|17
|
||||
1.3.6.1.4.1.2021.10.1.5.3|2|11
|
||||
1.3.6.1.4.1.2021.11.1.0|2|1
|
||||
1.3.6.1.4.1.2021.11.2.0|4|systemStats
|
||||
1.3.6.1.4.1.2021.11.3.0|2|0
|
||||
1.3.6.1.4.1.2021.11.4.0|2|0
|
||||
1.3.6.1.4.1.2021.11.5.0|2|0
|
||||
1.3.6.1.4.1.2021.11.6.0|2|0
|
||||
1.3.6.1.4.1.2021.11.7.0|2|6
|
||||
1.3.6.1.4.1.2021.11.8.0|2|8
|
||||
1.3.6.1.4.1.2021.11.9.0|2|4
|
||||
1.3.6.1.4.1.2021.11.10.0|2|4
|
||||
1.3.6.1.4.1.2021.11.11.0|2|90
|
||||
1.3.6.1.4.1.2021.11.50.0|65|19396780
|
||||
1.3.6.1.4.1.2021.11.51.0|65|418207
|
||||
1.3.6.1.4.1.2021.11.52.0|65|21249416
|
||||
1.3.6.1.4.1.2021.11.53.0|65|387922247
|
||||
1.3.6.1.4.1.2021.11.59.0|65|539814649
|
||||
1.3.6.1.4.1.2021.11.60.0|65|1152952676
|
||||
1.3.6.1.4.1.9839.2.1.2.73.0|2|1413
|
||||
1.3.6.1.4.1.9839.2.1.2.74.0|2|10
|
||||
1.3.6.1.4.1.9839.2.1.2.77.0|2|70
|
||||
1.3.6.1.4.1.9839.2.1.2.78.0|2|0
|
||||
1.3.6.1.4.1.9839.2.1.2.90.0|2|1000
|
||||
1.3.6.1.4.1.9839.2.1.2.91.0|2|0
|
||||
1.3.6.1.4.1.9839.2.1.2.100.0|2|339
|
||||
1.3.6.1.4.1.9839.2.1.2.101.0|2|0
|
||||
1.3.6.1.4.1.9839.2.1.2.102.0|2|339
|
||||
1.3.6.1.4.1.9839.2.1.2.103.0|2|7
|
||||
1.3.6.1.4.1.9839.2.1.2.120.0|2|0
|
||||
1.3.6.1.4.1.9839.2.1.2.133.0|2|37
|
||||
1.3.6.1.4.1.9839.2.1.2.136.0|2|180
|
||||
1.3.6.1.4.1.9839.2.1.2.137.0|2|179
|
||||
1.3.6.1.4.1.9839.2.1.2.138.0|2|16
|
||||
1.3.6.1.4.1.9839.2.1.2.140.0|2|36
|
||||
1.3.6.1.4.1.9839.2.1.3.120.0|2|48
|
||||
|
Loading…
Reference in New Issue
Block a user