Use high precision OIDs for APC UPS sensors (#12158)

This commit is contained in:
Cirno the Strongest 2021-03-07 10:45:10 +01:00 committed by GitHub
parent 3b2424fb1f
commit b340a3eec4
No known key found for this signature in database
GPG Key ID: 4AEE18F83AFDEB23
7 changed files with 1943 additions and 300 deletions

View File

@ -46,28 +46,30 @@ foreach (explode("\n", $oids) as $data) {
}
}
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.3.2.4.0', '-OsqnU', '');
// upsHighPrecInputFrequency
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.3.3.4.0', '-OsqnU', '');
d_echo($oids . "\n");
if ($oids) {
echo ' APC In ';
[$oid,$current] = explode(' ', $oids);
$divisor = 1;
$divisor = 10;
$type = 'apc';
$index = '3.2.4.0';
$index = '3.3.4.0';
$descr = 'Input';
discover_sensor($valid['sensor'], 'frequency', $device, $oid, $index, $type, $descr, $divisor, '1', null, null, null, null, $current);
discover_sensor($valid['sensor'], 'frequency', $device, $oid, $index, $type, $descr, $divisor, '1', null, null, null, null, $current / $divisor);
}
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.4.2.2.0', '-OsqnU', '');
// upsHighPrecOutputFrequency
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.4.3.2.0', '-OsqnU', '');
d_echo($oids . "\n");
if ($oids) {
echo ' APC Out ';
[$oid,$current] = explode(' ', $oids);
$divisor = 1;
$divisor = 10;
$type = 'apc';
$index = '4.2.2.0';
$index = '4.3.2.0';
$descr = 'Output';
discover_sensor($valid['sensor'], 'frequency', $device, $oid, $index, $type, $descr, $divisor, '1', null, null, null, null, $current);
discover_sensor($valid['sensor'], 'frequency', $device, $oid, $index, $type, $descr, $divisor, '1', null, null, null, null, $current / $divisor);
}

View File

@ -1,17 +1,18 @@
<?php
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.2.2.2.0', '-OsqnU', '');
// upsHighPrecBatteryTemperature
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.2.3.2.0', '-OsqnU', '');
d_echo($oids . "\n");
if ($oids) {
echo 'APC UPS Internal ';
[$oid,$current] = explode(' ', $oids);
$precision = 1;
$precision = 10;
$sensorType = 'apc';
$index = 0;
$descr = 'Internal Temperature';
discover_sensor($valid['sensor'], 'temperature', $device, $oid, $index, $sensorType, $descr, '1', '1', null, null, null, null, $current);
discover_sensor($valid['sensor'], 'temperature', $device, $oid, $index, $sensorType, $descr, $precision, '1', null, null, null, null, $current / $precision);
}
// Environmental monitoring on UPSes etc

View File

@ -2,17 +2,18 @@
// Battery Bus Voltage
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.2.2.8.0', '-OsqnU');
// upsHighPrecBatteryActualVoltage
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.2.3.4.0', '-OsqnU');
d_echo($oids . "\n");
if ($oids) {
echo ' Battery Bus ';
[$oid,$current] = explode(' ', $oids);
$divisor = 1;
$divisor = 10;
$type = 'apc';
$index = '2.2.8.0';
$index = '2.3.4.0';
$descr = 'Battery Bus';
discover_sensor($valid['sensor'], 'voltage', $device, $oid, $index, $type, $descr, $divisor, '1', null, null, null, null, $current);
discover_sensor($valid['sensor'], 'voltage', $device, $oid, $index, $type, $descr, $divisor, '1', null, null, null, null, $current / $divisor);
}
unset($oids);
@ -91,27 +92,29 @@ if ($phasecount > 1) {
}
}
}
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.3.2.1.0', '-OsqnU');
// upsHighPrecInputLineVoltage
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.3.3.1.0', '-OsqnU');
d_echo($oids . "\n");
if ($oids) {
echo ' APC In ';
[$oid,$current] = explode(' ', $oids);
$divisor = 1;
$divisor = 10;
$type = 'apc';
$index = '3.2.1.0';
$index = '3.3.1.0';
$descr = 'Input';
discover_sensor($valid['sensor'], 'voltage', $device, $oid, $index, $type, $descr, $divisor, '1', null, null, null, null, $current);
discover_sensor($valid['sensor'], 'voltage', $device, $oid, $index, $type, $descr, $divisor, '1', null, null, null, null, $current / $divisor);
}
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.4.2.1.0', '-OsqnU');
// upsHighPrecOutputVoltage
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.1.4.3.1.0', '-OsqnU');
d_echo($oids . "\n");
if ($oids) {
echo ' APC Out ';
[$oid,$current] = explode(' ', $oids);
$divisor = 1;
$divisor = 10;
$type = 'apc';
$index = '4.2.1.0';
$index = '4.3.1.0';
$descr = 'Output';
discover_sensor($valid['sensor'], 'voltage', $device, $oid, $index, $type, $descr, $divisor, '1', null, null, null, null, $current);
discover_sensor($valid['sensor'], 'voltage', $device, $oid, $index, $type, $descr, $divisor, '1', null, null, null, null, $current / $divisor);
}
// rPDUIdentDeviceLinetoLineVoltage
$oids = snmp_get($device, '.1.3.6.1.4.1.318.1.1.12.1.15.0', '-OsqnU');

View File

@ -4,15 +4,15 @@
"devices": [
{
"sysName": "<private>",
"sysObjectID": ".1.3.6.1.4.1.318.1.3.27",
"sysDescr": "APC Web/SNMP Management Card (MB:v4.1.0 PF:v6.6.4 PN:apc_hw05_aos_664.bin AF1:v6.6.4 AN1:apc_hw05_sumx_664.bin MN:AP9631 HR:08 SN: <private> MD:07/07/2017) (Embedded PowerNet SNMP Agent SW v2.2 compatible)",
"sysObjectID": ".1.3.6.1.4.1.318.1.3.2.7",
"sysDescr": "APC Web/SNMP Management Card (MB:v3.9.2 PF:v3.7.3 PN:apc_hw02_aos_373.bin AF1:v3.7.2 AN1:apc_hw02_sumx_372.bin MN:UPS_IDEN HR:A10 SN: FFFFFFFFFFFF MD:06/28/2010) (Embedded PowerNet SNMP Agent SW v2.2 compatible)",
"sysContact": "<private>",
"version": "AOS v6.6.4 / App v6.6.4",
"hardware": "Smart-UPS X 750 UPS 09.9 (ID20)",
"version": "AOS v3.7.3 / App v3.7.2",
"hardware": "Smart-UPS 1500 RM 617.3.I",
"features": null,
"os": "apc",
"type": "power",
"serial": "<private>",
"serial": "FFFFFFFFFFFF",
"icon": "apc.svg",
"location": "<private>"
}
@ -136,8 +136,8 @@
"port_descr_circuit": null,
"port_descr_speed": null,
"port_descr_notes": null,
"ifDescr": "vmac0",
"ifName": "vmac0",
"ifDescr": "lance",
"ifName": "lance",
"portName": null,
"ifIndex": 2,
"ifSpeed": null,
@ -153,7 +153,7 @@
"ifDuplex": null,
"ifMtu": null,
"ifType": "ethernetCsmacd",
"ifAlias": "vmac0",
"ifAlias": "lance",
"ifPhysAddress": null,
"ifHardType": null,
"ifLastChange": 0,
@ -354,11 +354,11 @@
"port_descr_circuit": null,
"port_descr_speed": null,
"port_descr_notes": null,
"ifDescr": "vmac0",
"ifName": "vmac0",
"ifDescr": "lance",
"ifName": "lance",
"portName": null,
"ifIndex": 2,
"ifSpeed": 100000000,
"ifSpeed": 10000000,
"ifSpeed_prev": null,
"ifConnectorPresent": null,
"ifPromiscuousMode": null,
@ -371,10 +371,10 @@
"ifDuplex": null,
"ifMtu": 1500,
"ifType": "ethernetCsmacd",
"ifAlias": "vmac0",
"ifPhysAddress": null,
"ifAlias": "lance",
"ifPhysAddress": "00c0b7231b87",
"ifHardType": null,
"ifLastChange": 25,
"ifLastChange": 0,
"ifVlan": "",
"ifTrunk": null,
"counter_in": null,
@ -393,11 +393,11 @@
"pagpEthcOperationMode": null,
"pagpDeviceId": null,
"pagpGroupIfIndex": null,
"ifInUcastPkts": 5905,
"ifInUcastPkts": 807578,
"ifInUcastPkts_prev": 0,
"ifInUcastPkts_delta": null,
"ifInUcastPkts_rate": null,
"ifOutUcastPkts": 6364,
"ifOutUcastPkts": 807746,
"ifOutUcastPkts_prev": 0,
"ifOutUcastPkts_delta": null,
"ifOutUcastPkts_rate": null,
@ -409,20 +409,20 @@
"ifOutErrors_prev": 0,
"ifOutErrors_delta": null,
"ifOutErrors_rate": null,
"ifInOctets": 603928,
"ifInOctets": 80990730,
"ifInOctets_prev": 0,
"ifInOctets_delta": null,
"ifInOctets_rate": null,
"ifOutOctets": 1726113,
"ifOutOctets": 86138588,
"ifOutOctets_prev": 0,
"ifOutOctets_delta": null,
"ifOutOctets_rate": null,
"poll_prev": null,
"ifInNUcastPkts": 58,
"ifInNUcastPkts": 10430,
"ifInNUcastPkts_prev": 0,
"ifInNUcastPkts_delta": null,
"ifInNUcastPkts_rate": null,
"ifOutNUcastPkts": 27,
"ifOutNUcastPkts": 6215,
"ifOutNUcastPkts_prev": 0,
"ifOutNUcastPkts_delta": null,
"ifOutNUcastPkts_rate": null,
@ -496,7 +496,7 @@
"group": null,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 0.6,
"sensor_current": 0,
"sensor_limit": null,
"sensor_limit_warn": null,
"sensor_limit_low": null,
@ -513,12 +513,12 @@
"sensor_deleted": 0,
"sensor_class": "frequency",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.3.2.4.0",
"sensor_index": "3.2.4.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.3.3.4.0",
"sensor_index": "3.3.4.0",
"sensor_type": "apc",
"sensor_descr": "Input",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 50,
"sensor_limit": 52.5,
@ -537,12 +537,12 @@
"sensor_deleted": 0,
"sensor_class": "frequency",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.4.2.2.0",
"sensor_index": "4.2.2.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.4.3.2.0",
"sensor_index": "4.3.2.0",
"sensor_type": "apc",
"sensor_descr": "Output",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 50,
"sensor_limit": 52.5,
@ -568,7 +568,7 @@
"group": null,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 20.2,
"sensor_current": 16.9,
"sensor_limit": 80,
"sensor_limit_warn": null,
"sensor_limit_low": null,
@ -592,7 +592,7 @@
"group": null,
"sensor_divisor": 6000,
"sensor_multiplier": 1,
"sensor_current": 570900,
"sensor_current": 396000,
"sensor_limit": 3000,
"sensor_limit_warn": 2000,
"sensor_limit_low": 5,
@ -605,54 +605,6 @@
"user_func": null,
"state_name": null
},
{
"sensor_deleted": 0,
"sensor_class": "state",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.10.2.3.4.1.3.1",
"sensor_index": "Door.1",
"sensor_type": "Door",
"sensor_descr": "Door",
"group": null,
"sensor_divisor": 1,
"sensor_multiplier": 1,
"sensor_current": 2,
"sensor_limit": null,
"sensor_limit_warn": null,
"sensor_limit_low": null,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
"entPhysicalIndex": null,
"entPhysicalIndex_measured": null,
"sensor_prev": null,
"user_func": null,
"state_name": "Door"
},
{
"sensor_deleted": 0,
"sensor_class": "state",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.10.2.3.4.1.3.2",
"sensor_index": "Fan.2",
"sensor_type": "Fan",
"sensor_descr": "Fan",
"group": null,
"sensor_divisor": 1,
"sensor_multiplier": 1,
"sensor_current": 1,
"sensor_limit": null,
"sensor_limit_warn": null,
"sensor_limit_low": null,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
"entPhysicalIndex": null,
"entPhysicalIndex_measured": null,
"sensor_prev": null,
"user_func": null,
"state_name": "Fan"
},
{
"sensor_deleted": 0,
"sensor_class": "state",
@ -705,17 +657,17 @@
"sensor_deleted": 0,
"sensor_class": "temperature",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.2.2.2.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.2.3.2.0",
"sensor_index": "0",
"sensor_type": "apc",
"sensor_descr": "Internal Temperature",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 31,
"sensor_limit": 51,
"sensor_current": 26.1,
"sensor_limit": 46.1,
"sensor_limit_warn": null,
"sensor_limit_low": 21,
"sensor_limit_low": 16.1,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
@ -732,15 +684,15 @@
"sensor_oid": ".1.3.6.1.4.1.318.1.1.10.2.3.2.1.4.1",
"sensor_index": "1",
"sensor_type": "apc",
"sensor_descr": "Port 1 Temp 1",
"sensor_descr": "AP9512T",
"group": null,
"sensor_divisor": 1,
"sensor_multiplier": 1,
"sensor_current": 23,
"sensor_limit": 43,
"sensor_limit_warn": null,
"sensor_limit_low": 13,
"sensor_limit_low_warn": null,
"sensor_current": 26,
"sensor_limit": 46,
"sensor_limit_warn": 40,
"sensor_limit_low": 16,
"sensor_limit_low_warn": 10,
"sensor_alert": 1,
"sensor_custom": "No",
"entPhysicalIndex": null,
@ -753,17 +705,17 @@
"sensor_deleted": 0,
"sensor_class": "voltage",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.2.2.8.0",
"sensor_index": "2.2.8.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.2.3.4.0",
"sensor_index": "2.3.4.0",
"sensor_type": "apc",
"sensor_descr": "Battery Bus",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 54,
"sensor_limit": 62.1,
"sensor_current": 27.5,
"sensor_limit": 31.625,
"sensor_limit_warn": null,
"sensor_limit_low": 45.9,
"sensor_limit_low": 23.375,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
@ -777,17 +729,17 @@
"sensor_deleted": 0,
"sensor_class": "voltage",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.3.2.1.0",
"sensor_index": "3.2.1.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.3.3.1.0",
"sensor_index": "3.3.1.0",
"sensor_type": "apc",
"sensor_descr": "Input",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 232,
"sensor_limit": 266.8,
"sensor_current": 239,
"sensor_limit": 274.85,
"sensor_limit_warn": null,
"sensor_limit_low": 197.2,
"sensor_limit_low": 203.15,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
@ -801,17 +753,17 @@
"sensor_deleted": 0,
"sensor_class": "voltage",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.4.2.1.0",
"sensor_index": "4.2.1.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.4.3.1.0",
"sensor_index": "4.3.1.0",
"sensor_type": "apc",
"sensor_descr": "Output",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 232,
"sensor_limit": 266.8,
"sensor_current": 239,
"sensor_limit": 274.85,
"sensor_limit_warn": null,
"sensor_limit_low": 197.2,
"sensor_limit_low": 203.15,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
@ -823,48 +775,6 @@
}
],
"state_indexes": [
{
"state_name": "Door",
"state_descr": "noFault",
"state_draw_graph": 0,
"state_value": 1,
"state_generic_value": 0
},
{
"state_name": "Door",
"state_descr": "fault",
"state_draw_graph": 1,
"state_value": 2,
"state_generic_value": 1
},
{
"state_name": "Door",
"state_descr": "disabled",
"state_draw_graph": 0,
"state_value": 3,
"state_generic_value": 0
},
{
"state_name": "Fan",
"state_descr": "noFault",
"state_draw_graph": 0,
"state_value": 1,
"state_generic_value": 0
},
{
"state_name": "Fan",
"state_descr": "fault",
"state_draw_graph": 1,
"state_value": 2,
"state_generic_value": 2
},
{
"state_name": "Fan",
"state_descr": "disabled",
"state_draw_graph": 0,
"state_value": 3,
"state_generic_value": 0
},
{
"state_name": "upsAdvBatteryReplaceIndicator",
"state_descr": "noBatteryNeedsReplacing",
@ -1072,7 +982,7 @@
"group": null,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 0.6,
"sensor_current": 0,
"sensor_limit": null,
"sensor_limit_warn": null,
"sensor_limit_low": null,
@ -1089,12 +999,12 @@
"sensor_deleted": 0,
"sensor_class": "frequency",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.3.2.4.0",
"sensor_index": "3.2.4.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.3.3.4.0",
"sensor_index": "3.3.4.0",
"sensor_type": "apc",
"sensor_descr": "Input",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 50,
"sensor_limit": 52.5,
@ -1113,12 +1023,12 @@
"sensor_deleted": 0,
"sensor_class": "frequency",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.4.2.2.0",
"sensor_index": "4.2.2.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.4.3.2.0",
"sensor_index": "4.3.2.0",
"sensor_type": "apc",
"sensor_descr": "Output",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 50,
"sensor_limit": 52.5,
@ -1144,7 +1054,7 @@
"group": null,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 20.2,
"sensor_current": 16.9,
"sensor_limit": 80,
"sensor_limit_warn": null,
"sensor_limit_low": null,
@ -1168,7 +1078,7 @@
"group": null,
"sensor_divisor": 6000,
"sensor_multiplier": 1,
"sensor_current": 95.15,
"sensor_current": 66,
"sensor_limit": 3000,
"sensor_limit_warn": 2000,
"sensor_limit_low": 5,
@ -1177,58 +1087,10 @@
"sensor_custom": "No",
"entPhysicalIndex": null,
"entPhysicalIndex_measured": null,
"sensor_prev": 570900,
"sensor_prev": 396000,
"user_func": null,
"state_name": null
},
{
"sensor_deleted": 0,
"sensor_class": "state",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.10.2.3.4.1.3.1",
"sensor_index": "Door.1",
"sensor_type": "Door",
"sensor_descr": "Door",
"group": null,
"sensor_divisor": 1,
"sensor_multiplier": 1,
"sensor_current": 2,
"sensor_limit": null,
"sensor_limit_warn": null,
"sensor_limit_low": null,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
"entPhysicalIndex": null,
"entPhysicalIndex_measured": null,
"sensor_prev": null,
"user_func": null,
"state_name": "Door"
},
{
"sensor_deleted": 0,
"sensor_class": "state",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.10.2.3.4.1.3.2",
"sensor_index": "Fan.2",
"sensor_type": "Fan",
"sensor_descr": "Fan",
"group": null,
"sensor_divisor": 1,
"sensor_multiplier": 1,
"sensor_current": 1,
"sensor_limit": null,
"sensor_limit_warn": null,
"sensor_limit_low": null,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
"entPhysicalIndex": null,
"entPhysicalIndex_measured": null,
"sensor_prev": null,
"user_func": null,
"state_name": "Fan"
},
{
"sensor_deleted": 0,
"sensor_class": "state",
@ -1281,17 +1143,17 @@
"sensor_deleted": 0,
"sensor_class": "temperature",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.2.2.2.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.2.3.2.0",
"sensor_index": "0",
"sensor_type": "apc",
"sensor_descr": "Internal Temperature",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 31,
"sensor_limit": 51,
"sensor_current": 26.1,
"sensor_limit": 46.1,
"sensor_limit_warn": null,
"sensor_limit_low": 21,
"sensor_limit_low": 16.1,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
@ -1308,15 +1170,15 @@
"sensor_oid": ".1.3.6.1.4.1.318.1.1.10.2.3.2.1.4.1",
"sensor_index": "1",
"sensor_type": "apc",
"sensor_descr": "Port 1 Temp 1",
"sensor_descr": "AP9512T",
"group": null,
"sensor_divisor": 1,
"sensor_multiplier": 1,
"sensor_current": 23,
"sensor_limit": 43,
"sensor_limit_warn": null,
"sensor_limit_low": 13,
"sensor_limit_low_warn": null,
"sensor_current": 26,
"sensor_limit": 46,
"sensor_limit_warn": 40,
"sensor_limit_low": 16,
"sensor_limit_low_warn": 10,
"sensor_alert": 1,
"sensor_custom": "No",
"entPhysicalIndex": null,
@ -1329,17 +1191,17 @@
"sensor_deleted": 0,
"sensor_class": "voltage",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.2.2.8.0",
"sensor_index": "2.2.8.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.2.3.4.0",
"sensor_index": "2.3.4.0",
"sensor_type": "apc",
"sensor_descr": "Battery Bus",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 54,
"sensor_limit": 62.1,
"sensor_current": 27.5,
"sensor_limit": 31.625,
"sensor_limit_warn": null,
"sensor_limit_low": 45.9,
"sensor_limit_low": 23.375,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
@ -1353,17 +1215,17 @@
"sensor_deleted": 0,
"sensor_class": "voltage",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.3.2.1.0",
"sensor_index": "3.2.1.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.3.3.1.0",
"sensor_index": "3.3.1.0",
"sensor_type": "apc",
"sensor_descr": "Input",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 232,
"sensor_limit": 266.8,
"sensor_current": 239,
"sensor_limit": 274.85,
"sensor_limit_warn": null,
"sensor_limit_low": 197.2,
"sensor_limit_low": 203.15,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
@ -1377,17 +1239,17 @@
"sensor_deleted": 0,
"sensor_class": "voltage",
"poller_type": "snmp",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.4.2.1.0",
"sensor_index": "4.2.1.0",
"sensor_oid": ".1.3.6.1.4.1.318.1.1.1.4.3.1.0",
"sensor_index": "4.3.1.0",
"sensor_type": "apc",
"sensor_descr": "Output",
"group": null,
"sensor_divisor": 1,
"sensor_divisor": 10,
"sensor_multiplier": 1,
"sensor_current": 232,
"sensor_limit": 266.8,
"sensor_current": 239,
"sensor_limit": 274.85,
"sensor_limit_warn": null,
"sensor_limit_low": 197.2,
"sensor_limit_low": 203.15,
"sensor_limit_low_warn": null,
"sensor_alert": 1,
"sensor_custom": "No",
@ -1399,48 +1261,6 @@
}
],
"state_indexes": [
{
"state_name": "Door",
"state_descr": "noFault",
"state_draw_graph": 0,
"state_value": 1,
"state_generic_value": 0
},
{
"state_name": "Door",
"state_descr": "fault",
"state_draw_graph": 1,
"state_value": 2,
"state_generic_value": 1
},
{
"state_name": "Door",
"state_descr": "disabled",
"state_draw_graph": 0,
"state_value": 3,
"state_generic_value": 0
},
{
"state_name": "Fan",
"state_descr": "noFault",
"state_draw_graph": 0,
"state_value": 1,
"state_generic_value": 0
},
{
"state_name": "Fan",
"state_descr": "fault",
"state_draw_graph": 1,
"state_value": 2,
"state_generic_value": 2
},
{
"state_name": "Fan",
"state_descr": "disabled",
"state_draw_graph": 0,
"state_value": 3,
"state_generic_value": 0
},
{
"state_name": "upsAdvBatteryReplaceIndicator",
"state_descr": "noBatteryNeedsReplacing",

1387
tests/data/apc_sua750i.json Normal file

File diff suppressed because it is too large Load Diff

View File

@ -0,0 +1,217 @@
1.3.6.1.2.1.1.1.0|4|APC Web/SNMP Management Card (MB:v3.9.2 PF:v3.7.3 PN:apc_hw02_aos_373.bin AF1:v3.7.2 AN1:apc_hw02_sumx_372.bin MN:UPS_IDEN HR:A10 SN: FFFFFFFFFFFF MD:06/28/2010) (Embedded PowerNet SNMP Agent SW v2.2 compatible)
1.3.6.1.2.1.1.2.0|6|1.3.6.1.4.1.318.1.3.2.7
1.3.6.1.2.1.1.3.0|67|18567570
1.3.6.1.2.1.1.4.0|4|<private>
1.3.6.1.2.1.1.5.0|4|<private>
1.3.6.1.2.1.1.6.0|4|<private>
1.3.6.1.2.1.2.2.1.1.1|2|1
1.3.6.1.2.1.2.2.1.1.2|2|2
1.3.6.1.2.1.2.2.1.2.1|4|LOOPBACK
1.3.6.1.2.1.2.2.1.2.2|4|lance
1.3.6.1.2.1.2.2.1.3.1|2|24
1.3.6.1.2.1.2.2.1.3.2|2|6
1.3.6.1.2.1.2.2.1.4.1|2|1500
1.3.6.1.2.1.2.2.1.4.2|2|1500
1.3.6.1.2.1.2.2.1.5.1|66|0
1.3.6.1.2.1.2.2.1.5.2|66|10000000
1.3.6.1.2.1.2.2.1.6.1|4|
1.3.6.1.2.1.2.2.1.6.2|4x|00C0B7231B87
1.3.6.1.2.1.2.2.1.7.1|2|1
1.3.6.1.2.1.2.2.1.7.2|2|1
1.3.6.1.2.1.2.2.1.8.1|2|1
1.3.6.1.2.1.2.2.1.8.2|2|1
1.3.6.1.2.1.2.2.1.9.1|67|0
1.3.6.1.2.1.2.2.1.9.2|67|0
1.3.6.1.2.1.2.2.1.10.1|65|0
1.3.6.1.2.1.2.2.1.10.2|65|80990730
1.3.6.1.2.1.2.2.1.11.1|65|0
1.3.6.1.2.1.2.2.1.11.2|65|807578
1.3.6.1.2.1.2.2.1.12.1|65|0
1.3.6.1.2.1.2.2.1.12.2|65|10430
1.3.6.1.2.1.2.2.1.13.1|65|0
1.3.6.1.2.1.2.2.1.13.2|65|0
1.3.6.1.2.1.2.2.1.14.1|65|0
1.3.6.1.2.1.2.2.1.14.2|65|0
1.3.6.1.2.1.2.2.1.15.1|65|0
1.3.6.1.2.1.2.2.1.15.2|65|0
1.3.6.1.2.1.2.2.1.16.1|65|0
1.3.6.1.2.1.2.2.1.16.2|65|86138588
1.3.6.1.2.1.2.2.1.17.1|65|0
1.3.6.1.2.1.2.2.1.17.2|65|807746
1.3.6.1.2.1.2.2.1.18.1|65|0
1.3.6.1.2.1.2.2.1.18.2|65|6215
1.3.6.1.2.1.2.2.1.19.1|65|0
1.3.6.1.2.1.2.2.1.19.2|65|0
1.3.6.1.2.1.2.2.1.20.1|65|0
1.3.6.1.2.1.2.2.1.20.2|65|0
1.3.6.1.2.1.2.2.1.21.1|66|0
1.3.6.1.2.1.2.2.1.21.2|66|1
1.3.6.1.2.1.2.2.1.22.1|6|0.0
1.3.6.1.2.1.2.2.1.22.2|6|0.0
1.3.6.1.2.1.4.3.0|65|814284
1.3.6.1.2.1.4.4.0|65|0
1.3.6.1.2.1.4.5.0|65|0
1.3.6.1.2.1.4.6.0|65|0
1.3.6.1.2.1.4.7.0|65|0
1.3.6.1.2.1.4.8.0|65|0
1.3.6.1.2.1.4.9.0|65|814283
1.3.6.1.2.1.4.10.0|65|797853
1.3.6.1.2.1.4.11.0|65|0
1.3.6.1.2.1.4.12.0|65|1
1.3.6.1.2.1.4.14.0|65|0
1.3.6.1.2.1.4.15.0|65|0
1.3.6.1.2.1.4.16.0|65|0
1.3.6.1.2.1.4.17.0|65|0
1.3.6.1.2.1.4.18.0|65|0
1.3.6.1.2.1.4.19.0|65|0
1.3.6.1.2.1.4.20.1.2.127.0.0.1|2|1
1.3.6.1.2.1.4.20.1.2.192.168.2.96|2|2
1.3.6.1.2.1.4.20.1.3.127.0.0.1|64|255.255.255.255
1.3.6.1.2.1.4.20.1.3.192.168.2.96|64|255.255.255.0
1.3.6.1.2.1.4.22.1.2.2.192.168.2.1|4x|B869F403F39B
1.3.6.1.2.1.4.22.1.2.2.192.168.2.111|4x|C27C19E58A5C
1.3.6.1.2.1.4.22.1.2.2.192.168.2.121|4x|AC1F6B1B7546
1.3.6.1.2.1.4.22.1.2.2.192.168.2.124|4x|C81F66C94B3F
1.3.6.1.2.1.5.1.0|65|3830
1.3.6.1.2.1.5.2.0|65|0
1.3.6.1.2.1.5.3.0|65|0
1.3.6.1.2.1.5.4.0|65|0
1.3.6.1.2.1.5.5.0|65|0
1.3.6.1.2.1.5.6.0|65|0
1.3.6.1.2.1.5.7.0|65|0
1.3.6.1.2.1.5.8.0|65|3145
1.3.6.1.2.1.5.9.0|65|685
1.3.6.1.2.1.5.10.0|65|0
1.3.6.1.2.1.5.11.0|65|0
1.3.6.1.2.1.5.12.0|65|0
1.3.6.1.2.1.5.13.0|65|0
1.3.6.1.2.1.5.14.0|65|3831
1.3.6.1.2.1.5.15.0|65|0
1.3.6.1.2.1.5.16.0|65|0
1.3.6.1.2.1.5.17.0|65|0
1.3.6.1.2.1.5.18.0|65|0
1.3.6.1.2.1.5.19.0|65|0
1.3.6.1.2.1.5.20.0|65|0
1.3.6.1.2.1.5.21.0|65|686
1.3.6.1.2.1.5.22.0|65|3145
1.3.6.1.2.1.5.23.0|65|0
1.3.6.1.2.1.5.24.0|65|0
1.3.6.1.2.1.5.25.0|65|0
1.3.6.1.2.1.5.26.0|65|0
1.3.6.1.2.1.6.5.0|65|4
1.3.6.1.2.1.6.6.0|65|24
1.3.6.1.2.1.6.7.0|65|2
1.3.6.1.2.1.6.8.0|65|3
1.3.6.1.2.1.6.9.0|66|0
1.3.6.1.2.1.6.10.0|65|759
1.3.6.1.2.1.6.11.0|65|701
1.3.6.1.2.1.6.12.0|65|0
1.3.6.1.2.1.6.14.0|65|0
1.3.6.1.2.1.6.15.0|65|8
1.3.6.1.2.1.7.1.0|65|793199
1.3.6.1.2.1.7.2.0|65|10339
1.3.6.1.2.1.7.3.0|65|0
1.3.6.1.2.1.7.4.0|65|793205
1.3.6.1.2.1.11.1.0|65|793173
1.3.6.1.2.1.11.2.0|65|793172
1.3.6.1.2.1.11.3.0|65|0
1.3.6.1.2.1.11.4.0|65|0
1.3.6.1.2.1.11.5.0|65|12
1.3.6.1.2.1.11.6.0|65|0
1.3.6.1.2.1.11.8.0|65|0
1.3.6.1.2.1.11.9.0|65|0
1.3.6.1.2.1.11.10.0|65|0
1.3.6.1.2.1.11.11.0|65|0
1.3.6.1.2.1.11.12.0|65|0
1.3.6.1.2.1.11.13.0|65|810523
1.3.6.1.2.1.11.14.0|65|0
1.3.6.1.2.1.11.15.0|65|778106
1.3.6.1.2.1.11.16.0|65|2492
1.3.6.1.2.1.11.17.0|65|0
1.3.6.1.2.1.11.18.0|65|0
1.3.6.1.2.1.11.19.0|65|0
1.3.6.1.2.1.11.20.0|65|0
1.3.6.1.2.1.11.21.0|65|12
1.3.6.1.2.1.11.22.0|65|0
1.3.6.1.2.1.11.24.0|65|0
1.3.6.1.2.1.11.25.0|65|0
1.3.6.1.2.1.11.26.0|65|0
1.3.6.1.2.1.11.27.0|65|0
1.3.6.1.2.1.11.28.0|65|793174
1.3.6.1.2.1.11.29.0|65|12
1.3.6.1.2.1.11.30.0|2|1
1.3.6.1.2.1.11.31.0|65|0
1.3.6.1.2.1.11.32.0|65|0
1.3.6.1.4.1.318.1.1.1.1.1.1.0|4|Smart-UPS 1500 RM
1.3.6.1.4.1.318.1.1.1.1.2.1.0|4|617.3.I
1.3.6.1.4.1.318.1.1.1.1.2.3.0|4|FFFFFFFFFFFF
1.3.6.1.4.1.318.1.1.1.2.2.3.0|67|396000
1.3.6.1.4.1.318.1.1.1.2.2.4.0|2|1
1.3.6.1.4.1.318.1.1.1.2.3.1.0|66|1000
1.3.6.1.4.1.318.1.1.1.2.3.2.0|66|261
1.3.6.1.4.1.318.1.1.1.2.3.4.0|2|275
1.3.6.1.4.1.318.1.1.1.3.3.1.0|66|2390
1.3.6.1.4.1.318.1.1.1.3.3.4.0|66|500
1.3.6.1.4.1.318.1.1.1.4.1.1.0|2|2
1.3.6.1.4.1.318.1.1.1.4.3.1.0|66|2390
1.3.6.1.4.1.318.1.1.1.4.3.2.0|66|500
1.3.6.1.4.1.318.1.1.1.4.3.3.0|66|169
1.3.6.1.4.1.318.1.1.1.4.3.4.0|66|0
1.3.6.1.4.1.318.1.1.10.2.2.2.1.1.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.2.1|4|AP9512T
1.3.6.1.4.1.318.1.1.10.2.2.2.1.3.1|2|40
1.3.6.1.4.1.318.1.1.10.2.2.2.1.4.1|2|10
1.3.6.1.4.1.318.1.1.10.2.2.2.1.5.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.6.1|2|60
1.3.6.1.4.1.318.1.1.10.2.2.2.1.7.1|2|30
1.3.6.1.4.1.318.1.1.10.2.2.2.1.8.1|2|2
1.3.6.1.4.1.318.1.1.10.2.2.2.1.9.1|2|2
1.3.6.1.4.1.318.1.1.10.2.2.2.1.10.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.11.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.12.1|2|60
1.3.6.1.4.1.318.1.1.10.2.2.2.1.13.1|2|0
1.3.6.1.4.1.318.1.1.10.2.2.2.1.14.1|2|90
1.3.6.1.4.1.318.1.1.10.2.2.2.1.15.1|2|10
1.3.6.1.4.1.318.1.1.10.2.2.2.1.16.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.17.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.18.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.19.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.20.1|2|0
1.3.6.1.4.1.318.1.1.10.2.2.2.1.21.1|2|0
1.3.6.1.4.1.318.1.1.10.2.2.2.1.22.1|4|SSR-12-600X1000
1.3.6.1.4.1.318.1.1.10.2.2.4.1.1.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.1.2|2|2
1.3.6.1.4.1.318.1.1.10.2.2.4.1.2.1|4|Int Contact 1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.2.2|4|Int Contact 2
1.3.6.1.4.1.318.1.1.10.2.2.4.1.3.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.3.2|2|1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.4.1|2|2
1.3.6.1.4.1.318.1.1.10.2.2.4.1.4.2|2|2
1.3.6.1.4.1.318.1.1.10.2.2.4.1.5.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.5.2|2|1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.6.1|4|SSR-12-600X1000
1.3.6.1.4.1.318.1.1.10.2.2.4.1.6.2|4|SSR-12-600X1000
1.3.6.1.4.1.318.1.1.10.2.3.2.1.1.1|2|1
1.3.6.1.4.1.318.1.1.10.2.3.2.1.2.1|4|AP9512T
1.3.6.1.4.1.318.1.1.10.2.3.2.1.3.1|2|2
1.3.6.1.4.1.318.1.1.10.2.3.2.1.4.1|2|26
1.3.6.1.4.1.318.1.1.10.2.3.2.1.5.1|2|1
1.3.6.1.4.1.318.1.1.10.2.3.2.1.6.1|2|-1
1.3.6.1.4.1.318.1.1.10.2.3.2.1.7.1|2|1
1.3.6.1.4.1.318.1.1.10.2.3.2.1.8.1|2|1
1.3.6.1.4.1.318.1.1.10.2.3.2.1.9.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.10.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.11.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.12.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.13.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.14.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.15.1|4|SSR-12-600X1000
1.3.6.1.4.1.318.1.1.10.2.3.4.1.1.1|2|1
1.3.6.1.4.1.318.1.1.10.2.3.4.1.1.2|2|2
1.3.6.1.4.1.318.1.1.10.2.3.4.1.2.1|4|Int Contact 1
1.3.6.1.4.1.318.1.1.10.2.3.4.1.2.2|4|Int Contact 2
1.3.6.1.4.1.318.1.1.10.2.3.4.1.3.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.4.1.3.2|2|3
1.3.6.1.4.1.318.1.4.2.4.1.4.1|4|v3.7.3
1.3.6.1.4.1.318.1.4.2.4.1.4.2|4|v3.7.2
1.3.6.1.6.3.10.2.1.3.0|2|185675

View File

@ -0,0 +1,213 @@
1.3.6.1.2.1.1.1.0|4|APC Web/SNMP Management Card (MB:v3.9.2 PF:v3.7.3 PN:apc_hw02_aos_373.bin AF1:v3.7.2 AN1:apc_hw02_sumx_372.bin MN:AP9619 HR:A10 SN: FFFFFFFFFFFF MD:04/20/2011) (Embedded PowerNet SNMP Agent SW v2.2 compatible)
1.3.6.1.2.1.1.2.0|6|1.3.6.1.4.1.318.1.3.2.7
1.3.6.1.2.1.1.3.0|67|25176050
1.3.6.1.2.1.1.4.0|4|<private>
1.3.6.1.2.1.1.5.0|4|<private>
1.3.6.1.2.1.1.6.0|4|<private>
1.3.6.1.2.1.2.2.1.1.1|2|1
1.3.6.1.2.1.2.2.1.1.2|2|2
1.3.6.1.2.1.2.2.1.2.1|4|LOOPBACK
1.3.6.1.2.1.2.2.1.2.2|4|lance
1.3.6.1.2.1.2.2.1.3.1|2|24
1.3.6.1.2.1.2.2.1.3.2|2|6
1.3.6.1.2.1.2.2.1.4.1|2|1500
1.3.6.1.2.1.2.2.1.4.2|2|1500
1.3.6.1.2.1.2.2.1.5.1|66|0
1.3.6.1.2.1.2.2.1.5.2|66|10000000
1.3.6.1.2.1.2.2.1.6.1|4|
1.3.6.1.2.1.2.2.1.6.2|4x|00C0B758B288
1.3.6.1.2.1.2.2.1.7.1|2|1
1.3.6.1.2.1.2.2.1.7.2|2|1
1.3.6.1.2.1.2.2.1.8.1|2|1
1.3.6.1.2.1.2.2.1.8.2|2|1
1.3.6.1.2.1.2.2.1.9.1|67|0
1.3.6.1.2.1.2.2.1.9.2|67|0
1.3.6.1.2.1.2.2.1.10.1|65|58
1.3.6.1.2.1.2.2.1.10.2|65|108177679
1.3.6.1.2.1.2.2.1.11.1|65|2
1.3.6.1.2.1.2.2.1.11.2|65|1082481
1.3.6.1.2.1.2.2.1.12.1|65|0
1.3.6.1.2.1.2.2.1.12.2|65|14184
1.3.6.1.2.1.2.2.1.13.1|65|0
1.3.6.1.2.1.2.2.1.13.2|65|0
1.3.6.1.2.1.2.2.1.14.1|65|0
1.3.6.1.2.1.2.2.1.14.2|65|0
1.3.6.1.2.1.2.2.1.15.1|65|0
1.3.6.1.2.1.2.2.1.15.2|65|0
1.3.6.1.2.1.2.2.1.16.1|65|30
1.3.6.1.2.1.2.2.1.16.2|65|116355115
1.3.6.1.2.1.2.2.1.17.1|65|2
1.3.6.1.2.1.2.2.1.17.2|65|1083178
1.3.6.1.2.1.2.2.1.18.1|65|0
1.3.6.1.2.1.2.2.1.18.2|65|8473
1.3.6.1.2.1.2.2.1.19.1|65|0
1.3.6.1.2.1.2.2.1.19.2|65|0
1.3.6.1.2.1.2.2.1.20.1|65|0
1.3.6.1.2.1.2.2.1.20.2|65|0
1.3.6.1.2.1.2.2.1.21.1|66|0
1.3.6.1.2.1.2.2.1.21.2|66|1
1.3.6.1.2.1.2.2.1.22.1|6|0.0
1.3.6.1.2.1.2.2.1.22.2|6|0.0
1.3.6.1.2.1.4.3.0|65|1091314
1.3.6.1.2.1.4.4.0|65|0
1.3.6.1.2.1.4.5.0|65|0
1.3.6.1.2.1.4.6.0|65|0
1.3.6.1.2.1.4.7.0|65|0
1.3.6.1.2.1.4.8.0|65|0
1.3.6.1.2.1.4.9.0|65|1091313
1.3.6.1.2.1.4.10.0|65|1069489
1.3.6.1.2.1.4.11.0|65|0
1.3.6.1.2.1.4.12.0|65|8
1.3.6.1.2.1.4.14.0|65|0
1.3.6.1.2.1.4.15.0|65|0
1.3.6.1.2.1.4.16.0|65|0
1.3.6.1.2.1.4.17.0|65|0
1.3.6.1.2.1.4.18.0|65|0
1.3.6.1.2.1.4.19.0|65|0
1.3.6.1.2.1.4.20.1.2.127.0.0.1|2|1
1.3.6.1.2.1.4.20.1.2.192.168.2.95|2|2
1.3.6.1.2.1.4.20.1.3.127.0.0.1|64|255.255.255.255
1.3.6.1.2.1.4.20.1.3.192.168.2.95|64|255.255.255.0
1.3.6.1.2.1.5.1.0|65|5193
1.3.6.1.2.1.5.2.0|65|0
1.3.6.1.2.1.5.3.0|65|7
1.3.6.1.2.1.5.4.0|65|0
1.3.6.1.2.1.5.5.0|65|0
1.3.6.1.2.1.5.6.0|65|0
1.3.6.1.2.1.5.7.0|65|0
1.3.6.1.2.1.5.8.0|65|4259
1.3.6.1.2.1.5.9.0|65|927
1.3.6.1.2.1.5.10.0|65|0
1.3.6.1.2.1.5.11.0|65|0
1.3.6.1.2.1.5.12.0|65|0
1.3.6.1.2.1.5.13.0|65|0
1.3.6.1.2.1.5.14.0|65|5190
1.3.6.1.2.1.5.15.0|65|0
1.3.6.1.2.1.5.16.0|65|0
1.3.6.1.2.1.5.17.0|65|0
1.3.6.1.2.1.5.18.0|65|0
1.3.6.1.2.1.5.19.0|65|0
1.3.6.1.2.1.5.20.0|65|0
1.3.6.1.2.1.5.21.0|65|931
1.3.6.1.2.1.5.22.0|65|4259
1.3.6.1.2.1.5.23.0|65|0
1.3.6.1.2.1.5.24.0|65|0
1.3.6.1.2.1.5.25.0|65|0
1.3.6.1.2.1.5.26.0|65|0
1.3.6.1.2.1.6.5.0|65|4
1.3.6.1.2.1.6.6.0|65|103
1.3.6.1.2.1.6.7.0|65|3
1.3.6.1.2.1.6.8.0|65|13
1.3.6.1.2.1.6.9.0|66|0
1.3.6.1.2.1.6.10.0|65|2869
1.3.6.1.2.1.6.11.0|65|2937
1.3.6.1.2.1.6.12.0|65|1
1.3.6.1.2.1.6.14.0|65|0
1.3.6.1.2.1.6.15.0|65|48
1.3.6.1.2.1.7.1.0|65|1060872
1.3.6.1.2.1.7.2.0|65|14024
1.3.6.1.2.1.7.3.0|65|0
1.3.6.1.2.1.7.4.0|65|1060907
1.3.6.1.2.1.11.1.0|65|1060841
1.3.6.1.2.1.11.2.0|65|1060828
1.3.6.1.2.1.11.3.0|65|0
1.3.6.1.2.1.11.4.0|65|24
1.3.6.1.2.1.11.5.0|65|15
1.3.6.1.2.1.11.6.0|65|0
1.3.6.1.2.1.11.8.0|65|0
1.3.6.1.2.1.11.9.0|65|0
1.3.6.1.2.1.11.10.0|65|0
1.3.6.1.2.1.11.11.0|65|0
1.3.6.1.2.1.11.12.0|65|0
1.3.6.1.2.1.11.13.0|65|1083559
1.3.6.1.2.1.11.14.0|65|0
1.3.6.1.2.1.11.15.0|65|1040594
1.3.6.1.2.1.11.16.0|65|3360
1.3.6.1.2.1.11.17.0|65|0
1.3.6.1.2.1.11.18.0|65|0
1.3.6.1.2.1.11.19.0|65|0
1.3.6.1.2.1.11.20.0|65|0
1.3.6.1.2.1.11.21.0|65|15
1.3.6.1.2.1.11.22.0|65|0
1.3.6.1.2.1.11.24.0|65|0
1.3.6.1.2.1.11.25.0|65|0
1.3.6.1.2.1.11.26.0|65|0
1.3.6.1.2.1.11.27.0|65|0
1.3.6.1.2.1.11.28.0|65|1060830
1.3.6.1.2.1.11.29.0|65|54
1.3.6.1.2.1.11.30.0|2|1
1.3.6.1.2.1.11.31.0|65|0
1.3.6.1.2.1.11.32.0|65|0
1.3.6.1.4.1.318.1.1.1.1.1.1.0|4|Smart-UPS 750
1.3.6.1.4.1.318.1.1.1.1.2.1.0|4|651.12.I
1.3.6.1.4.1.318.1.1.1.1.2.3.0|4|FFFFFFFFFFFF
1.3.6.1.4.1.318.1.1.1.2.2.3.0|67|438000
1.3.6.1.4.1.318.1.1.1.2.2.4.0|2|1
1.3.6.1.4.1.318.1.1.1.2.3.1.0|66|1000
1.3.6.1.4.1.318.1.1.1.2.3.2.0|66|369
1.3.6.1.4.1.318.1.1.1.2.3.4.0|2|272
1.3.6.1.4.1.318.1.1.1.3.3.1.0|66|2433
1.3.6.1.4.1.318.1.1.1.3.3.4.0|66|500
1.3.6.1.4.1.318.1.1.1.4.1.1.0|2|2
1.3.6.1.4.1.318.1.1.1.4.3.1.0|66|2433
1.3.6.1.4.1.318.1.1.1.4.3.2.0|66|500
1.3.6.1.4.1.318.1.1.1.4.3.3.0|66|227
1.3.6.1.4.1.318.1.1.1.4.3.4.0|66|2
1.3.6.1.4.1.318.1.1.10.2.2.2.1.1.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.2.1|4|Int Sensor
1.3.6.1.4.1.318.1.1.10.2.2.2.1.3.1|2|40
1.3.6.1.4.1.318.1.1.10.2.2.2.1.4.1|2|10
1.3.6.1.4.1.318.1.1.10.2.2.2.1.5.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.6.1|2|60
1.3.6.1.4.1.318.1.1.10.2.2.2.1.7.1|2|30
1.3.6.1.4.1.318.1.1.10.2.2.2.1.8.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.9.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.10.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.11.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.12.1|2|60
1.3.6.1.4.1.318.1.1.10.2.2.2.1.13.1|2|0
1.3.6.1.4.1.318.1.1.10.2.2.2.1.14.1|2|90
1.3.6.1.4.1.318.1.1.10.2.2.2.1.15.1|2|10
1.3.6.1.4.1.318.1.1.10.2.2.2.1.16.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.17.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.18.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.19.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.2.1.20.1|2|0
1.3.6.1.4.1.318.1.1.10.2.2.2.1.21.1|2|0
1.3.6.1.4.1.318.1.1.10.2.2.2.1.22.1|4|Int Sensor Loc
1.3.6.1.4.1.318.1.1.10.2.2.4.1.1.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.1.2|2|2
1.3.6.1.4.1.318.1.1.10.2.2.4.1.2.1|4|Int Contact 1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.2.2|4|Int Contact 2
1.3.6.1.4.1.318.1.1.10.2.2.4.1.3.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.3.2|2|1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.4.1|2|2
1.3.6.1.4.1.318.1.1.10.2.2.4.1.4.2|2|2
1.3.6.1.4.1.318.1.1.10.2.2.4.1.5.1|2|1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.5.2|2|1
1.3.6.1.4.1.318.1.1.10.2.2.4.1.6.1|4|Contact Location
1.3.6.1.4.1.318.1.1.10.2.2.4.1.6.2|4|Contact Location
1.3.6.1.4.1.318.1.1.10.2.3.2.1.1.1|2|1
1.3.6.1.4.1.318.1.1.10.2.3.2.1.2.1|4|Int Sensor
1.3.6.1.4.1.318.1.1.10.2.3.2.1.3.1|2|1
1.3.6.1.4.1.318.1.1.10.2.3.2.1.4.1|2|-1
1.3.6.1.4.1.318.1.1.10.2.3.2.1.5.1|2|1
1.3.6.1.4.1.318.1.1.10.2.3.2.1.6.1|2|-1
1.3.6.1.4.1.318.1.1.10.2.3.2.1.7.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.8.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.9.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.10.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.11.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.12.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.13.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.14.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.2.1.15.1|4|Int Sensor Loc
1.3.6.1.4.1.318.1.1.10.2.3.4.1.1.1|2|1
1.3.6.1.4.1.318.1.1.10.2.3.4.1.1.2|2|2
1.3.6.1.4.1.318.1.1.10.2.3.4.1.2.1|4|Int Contact 1
1.3.6.1.4.1.318.1.1.10.2.3.4.1.2.2|4|Int Contact 2
1.3.6.1.4.1.318.1.1.10.2.3.4.1.3.1|2|3
1.3.6.1.4.1.318.1.1.10.2.3.4.1.3.2|2|3
1.3.6.1.4.1.318.1.4.2.4.1.4.1|4|v3.7.3
1.3.6.1.4.1.318.1.4.2.4.1.4.2|4|v3.7.2
1.3.6.1.6.3.10.2.1.3.0|2|251760