-- Copyright(C) 2003-2009 Server Technology, Inc.
--
Sentry3-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, NOTIFICATION-TYPE,
OBJECT-TYPE, enterprises FROM SNMPv2-SMI
DisplayString FROM SNMPv2-TC;
sentry3 MODULE-IDENTITY
LAST-UPDATED "200903101600Z" -- 10 Mar 2009
ORGANIZATION "Server Technology, Inc."
CONTACT-INFO
"Server Technology, Inc.
1040 Sandhill Drive
Reno, NV 89521
Tel: (775) 284-2000
Fax: (775) 284-2065
Email: mibmaster@servertech.com"
DESCRIPTION
"This is the MIB module for the third generation of the
Sentry product family. This includes the Sentry Remote
Power Manager (RPM), Sentry Power Distribution Unit (PDU),
Sentry Environmental Monitor (EM), and Sentry Smart and
Switched Cabinet Distribution Unit (CDU)."
REVISION "200903101600Z" -- 10 Mar 2009
DESCRIPTION
"Added support for Per-Outlet Power Sensing (POPS) hardware.
Added several new objects: systemFeatures, systemFeatureKey,
infeedApparentPower, infeedPowerFactor, infeedCrestFactor,
infeedEnergy, outletCapacity, outletVoltage, outletPower,
outletApparentPower, outletPowerFactor, outletCrestFactor,
and outletEnergy. Added 'voltageSense' and 'powerSense'
bit definitions to the input feed and outlet capabilities
objects. Increased the size of systemVersion to 50."
REVISION "200805071520Z" -- 7 May 2008
DESCRIPTION
"Added systemAreaUnit and systemPowerFactor objects. Renamed
the systemWattsPerUnitArea object to systemWattsPerAreaUnit.
Changed systemArea from read-only to read-write."
REVISION "200707091445Z" -- 9 Jul 2007
DESCRIPTION
"Added support for products with fan rotation sensing and
internal temperature sensing. Added 'fanSense' and
'tempSense' bit definitions to the tower capabilities
object. Added 'fanFail' and 'overTemp' states to the
towerStatus object. Modified the description of the
towerStatusEvent trap to reflect these additions."
REVISION "200701091410Z" -- 9 Jan 2007
DESCRIPTION
"Added several new objects: systemArea, systemTotalPower,
systemWattsPerUnitArea, towerProductSN, towerModelNumber,
towerCapabilities, infeedCapacity, infeedVoltage, and
infeedPower. Added six states to the outletControlState
object."
REVISION "200607201200Z" -- 20 Jul 2006
DESCRIPTION
"Changed the upper limit of systemTowerCount from 2 to 4."
REVISION "200606120930Z" -- 12 Jun 2006
DESCRIPTION
"Added a tempHumidSensorTempScale object to select either
Celsius or Fahrenheit as the scale for temperature values.
To accommodate the maximum Fahrenheit value, the upper limit
of tempHumidSensorTempValue was changed to 2540, and the
upper limit of tempHumidSensorTempHighThresh was changed to
254. Removed 'Celsius' from the UNITS clause and description
of temperature objects. Added the tempHumidSensorTempScale
object to the tempHumidSensorTempEvent trap. Changed the
upper limit of towerIndex from 2 to 4, to accommodate new
products with additional link capabilities."
REVISION "200507271105Z" -- 27 Jul 2005
DESCRIPTION
"Changed the upper limit of tempHumidSensorTempLowThresh to
123. Changed the upper limit of tempHumidSensorTempValue
to 1235."
REVISION "200502181145Z" -- 18 Feb 2005
DESCRIPTION
"Added CDU products to the MIB description. Corrected syntax
of outletID to specify SIZE(2..4)."
REVISION "200501071220Z" -- 7 Jan 2005
DESCRIPTION
"Added a 'fusedBranch' bit definition to the outlet
capabilities object. Added 'offFuse' and 'onFuse' states
to the outlet status object. Modified the descriptions of
objects and traps to reflect support for these additions."
REVISION "200412091320Z" -- 9 Dec 2004
DESCRIPTION
"Corrected spelling errors. Removed product acronyms from the
trap annotations."
REVISION "200411111200Z" -- 11 Nov 2004
DESCRIPTION
"Changed the upper limit of tempHumidSensorTempHighThresh to
123. Renamed systemSerialNumber to systemNICSerialNumber."
REVISION "200311201300Z" -- 20 Nov 2003
DESCRIPTION
"Changed the MIB description to reflect that there are
multiple products in the Sentry product family supported by
this MIB."
REVISION "200310231900Z" -- 23 Oct 2003
DESCRIPTION
"Added annotations to the trap definitions. Added a
'reading' state to the outletStatus object. Renamed
'notificationGroup' to 'sentry3Traps'. Corrected the
the description of the tempHumidSensorStatusEvent trap."
REVISION "200310021100Z" -- 2 Oct 2003
DESCRIPTION
"Added a 'failSafe' bit definition to the infeed capabilities
object, and corrected the definition of the 'defaultOff'
infeed capabilities bit."
REVISION "200308271600Z" -- 27 Aug 2003
DESCRIPTION
"Added new bit definitions to the infeed and outlet
capabilities objects."
REVISION "200303281700Z" -- 28 Mar 2003
DESCRIPTION
"Added environmental monitor objects and traps."
REVISION "200303271700Z" -- 27 Mar 2003
DESCRIPTION
"Initial release."
::= { serverTech 3 }
serverTech OBJECT IDENTIFIER ::= { enterprises 1718 }
--
-- System Group
--
systemGroup OBJECT IDENTIFIER ::= { sentry3 1 }
systemVersion OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..50))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The firmware version of the system."
::= { systemGroup 1 }
systemNICSerialNumber OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The serial number of the network interface card in the
system."
::= { systemGroup 2 }
systemLocation OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..32))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The location of the system."
::= { systemGroup 3 }
systemTowerCount OBJECT-TYPE
SYNTAX INTEGER(0..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of towers in the system."
::= { systemGroup 4 }
systemEnvMonCount OBJECT-TYPE
SYNTAX INTEGER(0..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of environmental monitors in the system."
::= { systemGroup 5 }
systemTotalPower OBJECT-TYPE
SYNTAX INTEGER(-1..150000)
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total power consumption of all of the input feeds in the
system. A non-negative value indicates the total power
consumption in Watts. A negative value indicates that the
total power consumption was not available."
::= { systemGroup 6 }
systemArea OBJECT-TYPE
SYNTAX INTEGER(0..1000)
UNITS "tenth area units"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The area that the footprint of the system occupies. A
non-zero non-negative value indicates the area in tenths of
area units as selected by the systemAreaUnit object. A zero
or negative value indicates that the area was not available."
::= { systemGroup 7 }
systemWattsPerAreaUnit OBJECT-TYPE
SYNTAX INTEGER(-1..1500000)
UNITS "Watts per area unit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system Watts per area unit. A non-negative value
indicates the power consumption per area unit as selected by
the systemAreaUnit object. A negative value indicates that
the power consumption per area unit was not available."
::= { systemGroup 8 }
systemAreaUnit OBJECT-TYPE
SYNTAX INTEGER {
squareMeter(0),
squareFoot(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The unit of area for the systemArea and systemWattsPerAreaUnit
objects. If the agent does not support this object, then the
unit of area is a square foot."
::= { systemGroup 9 }
systemPowerFactor OBJECT-TYPE
SYNTAX INTEGER(50..100)
UNITS "hundredths"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The power factor used in power calculations performed by the
system."
::= { systemGroup 10 }
systemFeatures OBJECT-TYPE
SYNTAX BITS {
smartLoadShedding(0),
snmpPOPS(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The key-activated features enabled in the system."
::= { systemGroup 11 }
systemFeatureKey OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..19))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A valid feature key written to this object will enable a
feature in the system. A valid feature key is in the form
xxxx-xxxx-xxxx-xxxx. A read of this object returns an
empty string."
::= { systemGroup 12 }
--
-- System Tables
--
systemTables OBJECT IDENTIFIER ::= { sentry3 2 }
--
-- Tower Table
--
towerTable OBJECT-TYPE
SYNTAX SEQUENCE OF TowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of towers."
::= { systemTables 1 }
towerEntry OBJECT-TYPE
SYNTAX TowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Row definition for the tower table."
INDEX { towerIndex }
::= { towerTable 1 }
TowerEntry ::= SEQUENCE {
towerIndex INTEGER,
towerID DisplayString,
towerName DisplayString,
towerStatus INTEGER,
towerInfeedCount INTEGER,
towerProductSN DisplayString,
towerModelNumber DisplayString,
towerCapabilities BITS
}
towerIndex OBJECT-TYPE
SYNTAX INTEGER(0..4)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the tower table."
::= { towerEntry 1 }
towerID OBJECT-TYPE
SYNTAX DisplayString(SIZE(1))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ID of the tower."
::= { towerEntry 2 }
towerName OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..24))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the tower."
::= { towerEntry 3 }
towerStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
noComm(1),
fanFail(2),
overTemp(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The operational status of the tower."
::= { towerEntry 4 }
towerInfeedCount OBJECT-TYPE
SYNTAX INTEGER(0..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of input feeds on the tower."
::= { towerEntry 5 }
towerProductSN OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..16))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The product serial number of the tower."
::= { towerEntry 6 }
towerModelNumber OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..24))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The model number of the tower."
::= { towerEntry 7 }
towerCapabilities OBJECT-TYPE
SYNTAX BITS {
failSafe(0),
fuseSense(1),
directCurrent(2),
threePhase(3),
fanSense(4),
tempSense(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The capabilities of the tower."
::= { towerEntry 8 }
--
-- Input Feed Table
--
infeedTable OBJECT-TYPE
SYNTAX SEQUENCE OF InfeedEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of input feeds."
::= { systemTables 2 }
infeedEntry OBJECT-TYPE
SYNTAX InfeedEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Row definition for the input feed table."
INDEX { towerIndex, infeedIndex }
::= { infeedTable 1 }
InfeedEntry ::= SEQUENCE {
infeedIndex INTEGER,
infeedID DisplayString,
infeedName DisplayString,
infeedCapabilities BITS,
infeedStatus INTEGER,
infeedLoadStatus INTEGER,
infeedLoadValue INTEGER,
infeedLoadHighThresh INTEGER,
infeedOutletCount INTEGER,
infeedCapacity INTEGER,
infeedVoltage INTEGER,
infeedPower INTEGER,
infeedApparentPower INTEGER,
infeedPowerFactor INTEGER,
infeedCrestFactor INTEGER,
infeedEnergy INTEGER
}
infeedIndex OBJECT-TYPE
SYNTAX INTEGER(0..4)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the input feed table."
::= { infeedEntry 1 }
infeedID OBJECT-TYPE
SYNTAX DisplayString(SIZE(2))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ID of the input feed."
::= { infeedEntry 2 }
infeedName OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..24))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the input feed."
::= { infeedEntry 3 }
infeedCapabilities OBJECT-TYPE
SYNTAX BITS {
onSense(0),
loadSense(1),
powerControl(2),
failSafe(3),
defaultOff(4),
voltageSense(5),
powerSense(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The capabilities of the input feed."
::= { infeedEntry 4 }
infeedStatus OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1),
offWait(2),
onWait(3),
offError(4),
onError(5),
noComm(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the input feed. If the infeedCapabilities
'onSense' bit is TRUE, then all of the states are supported
and indicate the sensed state of the input feed. If the
infeedCapabilities 'onSense' bit is FALSE, then only the
'on' and 'noComm' states are supported, and 'on' indicates
a derived state, not a sensed state."
::= { infeedEntry 5 }
infeedLoadStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
notOn(1),
reading(2),
loadLow(3),
loadHigh(4),
overLoad(5),
readError(6),
noComm(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the load measured on the input feed. If the
infeedCapabilities 'loadSense' bit is TRUE, then all of the
states are supported. If the infeedCapabilities 'loadSense'
bit is FALSE, then only the 'normal' and 'noComm' states are
supported."
::= { infeedEntry 6 }
infeedLoadValue OBJECT-TYPE
SYNTAX INTEGER(-1..25500)
UNITS "hundredth Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The load measured on the input feed. A non-negative value
indicates the measured load in hundredths of Amps. A
negative value indicates that a load value was not able to
be measured."
::= { infeedEntry 7 }
infeedLoadHighThresh OBJECT-TYPE
SYNTAX INTEGER(0..255)
UNITS "Amps"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The load high threshold value of the input feed in Amps."
::= { infeedEntry 8 }
infeedOutletCount OBJECT-TYPE
SYNTAX INTEGER(0..16)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of outlets on the input feed."
::= { infeedEntry 9 }
infeedCapacity OBJECT-TYPE
SYNTAX INTEGER(-1..255)
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The load capacity of the input feed. A non-negative
value indicates the maximum load in Amps. A negative
value indicates that the capacity was not available."
::= { infeedEntry 10 }
infeedVoltage OBJECT-TYPE
SYNTAX INTEGER(-1..2600)
UNITS "tenth Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The voltage of the input feed. A non-negative value
indicates the voltage in tenths of Volts. A negative
value indicates that the voltage was not available."
::= { infeedEntry 11 }
infeedPower OBJECT-TYPE
SYNTAX INTEGER(-1..15000)
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The active power consumption of the input feed. A non-
negative value indicates the active power consumption in
Watts. A negative value indicates that the active power
consumption was not available."
::= { infeedEntry 12 }
infeedApparentPower OBJECT-TYPE
SYNTAX INTEGER(-1..15000)
UNITS "Volt-Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The apparent power consumption of the input feed. A non-
negative value indicates the apparent power consumption in
Volt-Amps. A negative value indicates that the apparent
power consumption was not available."
::= { infeedEntry 13 }
infeedPowerFactor OBJECT-TYPE
SYNTAX INTEGER(-1..100)
UNITS "hundredths"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power factor of the input feed. A non-negative value
indicates the power factor in hundredths. A negative value
indicates that the power factor was not able to be measured."
::= { infeedEntry 14 }
infeedCrestFactor OBJECT-TYPE
SYNTAX INTEGER(-1..1000)
UNITS "tenths"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The crest factor for the load of the input feed. A non-
negative value indicates the crest factor in tenths. A
negative value indicates that the crest factor was not able
to be measured."
::= { infeedEntry 15 }
infeedEnergy OBJECT-TYPE
SYNTAX INTEGER(-1..2147483647)
UNITS "Watt-Hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The energy consumption of the input feed. A non-negative
value indicates the energy consumption in Watt-Hours. A
negative value indicates that the energy consumption was
not available."
::= { infeedEntry 16 }
--
-- Outlet Table
--
outletTable OBJECT-TYPE
SYNTAX SEQUENCE OF OutletEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of outlets."
::= { systemTables 3 }
outletEntry OBJECT-TYPE
SYNTAX OutletEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Row definition for the outlet table."
INDEX { towerIndex, infeedIndex, outletIndex }
::= { outletTable 1 }
OutletEntry ::= SEQUENCE {
outletIndex INTEGER,
outletID DisplayString,
outletName DisplayString,
outletCapabilities BITS,
outletStatus INTEGER,
outletLoadStatus INTEGER,
outletLoadValue INTEGER,
outletLoadLowThresh INTEGER,
outletLoadHighThresh INTEGER,
outletControlState INTEGER,
outletControlAction INTEGER,
outletCapacity INTEGER,
outletVoltage INTEGER,
outletPower INTEGER,
outletApparentPower INTEGER,
outletPowerFactor INTEGER,
outletCrestFactor INTEGER,
outletEnergy INTEGER
}
outletIndex OBJECT-TYPE
SYNTAX INTEGER(0..16)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the outlet table."
::= { outletEntry 1 }
outletID OBJECT-TYPE
SYNTAX DisplayString(SIZE(2..4))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ID of the outlet."
::= { outletEntry 2 }
outletName OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..24))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the outlet."
::= { outletEntry 3 }
outletCapabilities OBJECT-TYPE
SYNTAX BITS {
onSense(0),
loadSense(1),
powerControl(2),
shutdown(3),
defaultOn(4),
ownInfeed(5),
fusedBranch(6),
voltageSense(7),
powerSense(8)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The capabilities of the outlet."
::= { outletEntry 4 }
outletStatus OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1),
offWait(2),
onWait(3),
offError(4),
onError(5),
noComm(6),
reading(7),
offFuse(8),
onFuse(9)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the outlet. If the outletCapabilities
'onSense' bit is TRUE, then the state indicates the sensed
state of the outlet, not a derived state, and 'offError'
and 'onError' are supported to indicate a mismatch between
the control and sensed state. If the outletCapabilities
'fusedBranch' bit is TRUE, then the outlet is on a fused
branch circuit that can detect the fuse state, and 'offFuse'
and 'onFuse' are supported to indicate a fuse error."
::= { outletEntry 5 }
outletLoadStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
notOn(1),
reading(2),
loadLow(3),
loadHigh(4),
overLoad(5),
readError(6),
noComm(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the load measured on the outlet. If the
outletCapabilities 'loadSense' bit is TRUE, then all of the
states are supported. If the outletCapabilities 'loadSense'
bit is FALSE, then only the 'normal' and 'noComm' states are
supported."
::= { outletEntry 6 }
outletLoadValue OBJECT-TYPE
SYNTAX INTEGER(-1..25500)
UNITS "hundredth Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The load measured on the outlet. A non-negative value
indicates the measured load in hundredths of Amps. A
negative value indicates that a load value was not able to
be measured."
::= { outletEntry 7 }
outletLoadLowThresh OBJECT-TYPE
SYNTAX INTEGER(0..255)
UNITS "Amps"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The load low threshold value of the outlet in Amps."
::= { outletEntry 8 }
outletLoadHighThresh OBJECT-TYPE
SYNTAX INTEGER(0..255)
UNITS "Amps"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The load high threshold value of the outlet in Amps."
::= { outletEntry 9 }
outletControlState OBJECT-TYPE
SYNTAX INTEGER {
idleOff(0),
idleOn(1),
wakeOff(2),
wakeOn(3),
off(4),
on(5),
lockedOff(6),
lockedOn(7),
reboot(8),
shutdown(9),
pendOn(10),
pendOff(11),
minimumOff(12),
minimumOn(13),
eventOff(14),
eventOn(15),
eventReboot(16),
eventShutdown(17)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The control state of the outlet. The supported states are
dependent upon the outletCapabilities 'powerControl' and
'shutdown' bits, as well as the supported features of the
firmware version."
::= { outletEntry 10 }
outletControlAction OBJECT-TYPE
SYNTAX INTEGER {
none(0),
on(1),
off(2),
reboot(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"An action to change the control state of the outlet. If
the outletCapabilities 'powerControl' bit is TRUE, then the
'on', 'off', and 'reboot' actions can be used to change the
control state of the outlet. If the outletCapabilities
'powerControl' bit is FALSE, then the actions have no
effect."
::= { outletEntry 11 }
outletCapacity OBJECT-TYPE
SYNTAX INTEGER(-1..255)
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The load capacity of the outlet. A non-negative value
indicates the maximum load in Amps. A negative value
indicates that the capacity was not available. A non-
negative value requires POPS hardware and key activation
of the 'snmpPOPS' feature."
::= { outletEntry 12 }
outletVoltage OBJECT-TYPE
SYNTAX INTEGER(-1..2600)
UNITS "tenth Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The voltage of the outlet. A non-negative value indicates
the voltage in tenths of Volts. A negative value indicates
that the voltage was not available. A non-negative value
requires POPS hardware and key activation of the 'snmpPOPS'
feature."
::= { outletEntry 13 }
outletPower OBJECT-TYPE
SYNTAX INTEGER(-1..5000)
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The active power consumption of the device plugged into the
outlet. A non-negative value indicates the active power
consumption in Watts. A negative value indicates that the
active power consumption was not available. A non-negative
value requires POPS hardware and key activation of the
'snmpPOPS' feature."
::= { outletEntry 14 }
outletApparentPower OBJECT-TYPE
SYNTAX INTEGER(-1..15000)
UNITS "Volt-Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The apparent power consumption of the device plugged into
the outlet. A non-negative value indicates the apparent
power consumption in Volt-Amps. A negative value indicates
that the apparent power consumption was not available. A
non-negative value requires POPS hardware and key activation
of the 'snmpPOPS' feature."
::= { outletEntry 15 }
outletPowerFactor OBJECT-TYPE
SYNTAX INTEGER(-1..100)
UNITS "hundredths"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power factor of the device plugged into the outlet. A
non-negative value indicates the power factor in hundredths.
A negative value indicates that the power factor was not able
to be measured. A non-negative value requires POPS hardware
and key activation of the 'snmpPOPS' feature."
::= { outletEntry 16 }
outletCrestFactor OBJECT-TYPE
SYNTAX INTEGER(-1..1000)
UNITS "tenths"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The crest factor for the load of the device plugged into the
outlet. A non-negative value indicates the crest factor in
tenths. A negative value indicates that the crest factor
was not able to be measured. A non-negative value requires
POPS hardware and key activation of the 'snmpPOPS' feature."
::= { outletEntry 17 }
outletEnergy OBJECT-TYPE
SYNTAX INTEGER(-1..2147483647)
UNITS "Watt-Hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The energy consumption of the device plugged into the outlet.
A non-negative value indicates the energy consumption in
Watt-Hours. A negative value indicates that the energy
consumption was not available. A non-negative value requires
POPS hardware and key activation of the 'snmpPOPS' feature."
::= { outletEntry 18 }
--
-- Environmental Monitor Table
--
envMonTable OBJECT-TYPE
SYNTAX SEQUENCE OF EnvMonEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of environmental monitors."
::= { systemTables 4 }
envMonEntry OBJECT-TYPE
SYNTAX EnvMonEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Row definition for the environmental monitor table."
INDEX { envMonIndex }
::= { envMonTable 1 }
EnvMonEntry ::= SEQUENCE {
envMonIndex INTEGER,
envMonID DisplayString,
envMonName DisplayString,
envMonStatus INTEGER,
envMonWaterSensorName DisplayString,
envMonWaterSensorStatus INTEGER,
envMonADCName DisplayString,
envMonADCStatus INTEGER,
envMonADCCount INTEGER,
envMonADCLowThresh INTEGER,
envMonADCHighThresh INTEGER,
envMonTempHumidSensorCount INTEGER,
envMonContactClosureCount INTEGER
}
envMonIndex OBJECT-TYPE
SYNTAX INTEGER(0..4)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the environmental monitor table."
::= { envMonEntry 1 }
envMonID OBJECT-TYPE
SYNTAX DisplayString(SIZE(1))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ID of the environmental monitor."
::= { envMonEntry 2 }
envMonName OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..24))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the environmental monitor."
::= { envMonEntry 3 }
envMonStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
noComm(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The operational status of the environmental monitor."
::= { envMonEntry 4 }
envMonWaterSensorName OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..24))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the water sensor."
::= { envMonEntry 5 }
envMonWaterSensorStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
alarm(1),
noComm(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the water sensor."
::= { envMonEntry 6 }
envMonADCName OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..24))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the analog-to-digital converter."
::= { envMonEntry 7 }
envMonADCStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
reading(1),
countLow(2),
countHigh(3),
readError(4),
noComm(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the analog-to-digital converter."
::= { envMonEntry 8 }
envMonADCCount OBJECT-TYPE
SYNTAX INTEGER(-1..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The 8-bit count value from the analog-to-digital converter.
A non-negative value indicates the digital value retrieved
from the ADC. A negative value indicates that a digital
value was not able to be retrieved."
::= { envMonEntry 9 }
envMonADCLowThresh OBJECT-TYPE
SYNTAX INTEGER(0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The 8-bit count low threshold value of the analog-to-digital
converter."
::= { envMonEntry 10 }
envMonADCHighThresh OBJECT-TYPE
SYNTAX INTEGER(0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The 8-bit count high threshold value of the analog-to-digital
converter."
::= { envMonEntry 11 }
envMonTempHumidSensorCount OBJECT-TYPE
SYNTAX INTEGER(0..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of temperature/humidity sensors on the
environmental monitor."
::= { envMonEntry 12 }
envMonContactClosureCount OBJECT-TYPE
SYNTAX INTEGER(0..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of contact closures on the environmental
monitor."
::= { envMonEntry 13 }
--
-- Temperature/Humidity Sensor Table
--
tempHumidSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF TempHumidSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of temperature/humidity sensors."
::= { systemTables 5 }
tempHumidSensorEntry OBJECT-TYPE
SYNTAX TempHumidSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Row definition for the temperature/humidity sensor table."
INDEX { envMonIndex, tempHumidSensorIndex }
::= { tempHumidSensorTable 1 }
TempHumidSensorEntry ::= SEQUENCE {
tempHumidSensorIndex INTEGER,
tempHumidSensorID DisplayString,
tempHumidSensorName DisplayString,
tempHumidSensorStatus INTEGER,
tempHumidSensorTempStatus INTEGER,
tempHumidSensorTempValue INTEGER,
tempHumidSensorTempLowThresh INTEGER,
tempHumidSensorTempHighThresh INTEGER,
tempHumidSensorHumidStatus INTEGER,
tempHumidSensorHumidValue INTEGER,
tempHumidSensorHumidLowThresh INTEGER,
tempHumidSensorHumidHighThresh INTEGER,
tempHumidSensorTempScale INTEGER
}
tempHumidSensorIndex OBJECT-TYPE
SYNTAX INTEGER(0..2)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the temperature/humidity sensor table."
::= { tempHumidSensorEntry 1 }
tempHumidSensorID OBJECT-TYPE
SYNTAX DisplayString(SIZE(2))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ID of the temperature/humidity sensor."
::= { tempHumidSensorEntry 2 }
tempHumidSensorName OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..24))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the temperature/humidity sensor."
::= { tempHumidSensorEntry 3 }
tempHumidSensorStatus OBJECT-TYPE
SYNTAX INTEGER {
found(0),
notFound(1),
lost(2),
noComm(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The operational status of the temperature/humidity sensor."
::= { tempHumidSensorEntry 4 }
tempHumidSensorTempStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
notFound(1),
reading(2),
tempLow(3),
tempHigh(4),
readError(5),
lost(6),
noComm(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the temperature sensor."
::= { tempHumidSensorEntry 5 }
tempHumidSensorTempValue OBJECT-TYPE
SYNTAX INTEGER(-1..2540)
UNITS "tenth degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature measured by the sensor. A non-negative value
indicates the measured temperature in tenths of degrees, using
the scale selected by tempHumidSensorTempScale. If the agent
does not support the tempHumidSensorTempScale object, then the
temperature scale used is Celsius. A negative value indicates
that a temperature value was not able to be measured."
::= { tempHumidSensorEntry 6 }
tempHumidSensorTempLowThresh OBJECT-TYPE
SYNTAX INTEGER(0..254)
UNITS "degrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The temperature low threshold value of the sensor in degrees,
using the scale selected by tempHumidSensorTempScale. If the
agent does not support the tempHumidSensorTempScale object,
then the temperature scale used is Celsius."
::= { tempHumidSensorEntry 7 }
tempHumidSensorTempHighThresh OBJECT-TYPE
SYNTAX INTEGER(0..254)
UNITS "degrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The temperature high threshold value of the sensor in degrees,
using the scale selected by tempHumidSensorTempScale. If the
agent does not support the tempHumidSensorTempScale object,
then the temperature scale used is Celsius."
::= { tempHumidSensorEntry 8 }
tempHumidSensorHumidStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
notFound(1),
reading(2),
humidLow(3),
humidHigh(4),
readError(5),
lost(6),
noComm(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the humidity sensor."
::= { tempHumidSensorEntry 9 }
tempHumidSensorHumidValue OBJECT-TYPE
SYNTAX INTEGER(-1..100)
UNITS "percentage relative humidity"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The humidity measured by the sensor. A non-negative value
indicates the measured humidity in percentage relative
humidity. A negative value indicates that a humidity value
was not able to be measured."
::= { tempHumidSensorEntry 10 }
tempHumidSensorHumidLowThresh OBJECT-TYPE
SYNTAX INTEGER(0..100)
UNITS "percentage relative humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The humidity low threshold value of the sensor in percentage
relative humidity."
::= { tempHumidSensorEntry 11 }
tempHumidSensorHumidHighThresh OBJECT-TYPE
SYNTAX INTEGER(0..100)
UNITS "percentage relative humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The humidity low threshold value of the sensor in percentage
relative humidity."
::= { tempHumidSensorEntry 12 }
tempHumidSensorTempScale OBJECT-TYPE
SYNTAX INTEGER {
celsius(0),
fahrenheit(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The scale used for temperature values. This is a global
setting for all temperature values in the system. If the
agent does not support this object, then the temperature
scale used is Celsius."
::= { tempHumidSensorEntry 13 }
--
-- Contact Closure Table
--
contactClosureTable OBJECT-TYPE
SYNTAX SEQUENCE OF ContactClosureEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of contact closures."
::= { systemTables 6 }
contactClosureEntry OBJECT-TYPE
SYNTAX ContactClosureEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Row definition for the contact closure table."
INDEX { envMonIndex, contactClosureIndex }
::= { contactClosureTable 1 }
ContactClosureEntry ::= SEQUENCE {
contactClosureIndex INTEGER,
contactClosureID DisplayString,
contactClosureName DisplayString,
contactClosureStatus INTEGER
}
contactClosureIndex OBJECT-TYPE
SYNTAX INTEGER(0..4)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the contact closure table."
::= { contactClosureEntry 1 }
contactClosureID OBJECT-TYPE
SYNTAX DisplayString(SIZE(2))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ID of the contact closure."
::= { contactClosureEntry 2 }
contactClosureName OBJECT-TYPE
SYNTAX DisplayString(SIZE(0..24))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the contact closure."
::= { contactClosureEntry 3 }
contactClosureStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
alarm(1),
noComm(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the contact closure."
::= { contactClosureEntry 4 }
--
-- Notifications
--
sentry3Traps OBJECT IDENTIFIER ::= { sentry3 100 }
events OBJECT IDENTIFIER ::= { sentry3Traps 0 }
-- the 0 is for V1 compatibility
-- Tower Traps
towerStatusEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
towerID,
towerName,
towerStatus
}
STATUS current
DESCRIPTION
"Tower status event. If enabled, this trap is sent when the
towerStatus indicates an error state ('noComm', 'fanFail',
or 'overTemp'). This trap is repeated periodically while the
towerStatus remains in an error state. If the towerStatus
returns to a non-error state ('normal'), this trap is sent
once more with the non-error towerStatus, and then stops
being repeated.
While the towerStatus indicates a 'noComm' error state, all
status and load traps are suppressed for input feeds and
outlets on the tower."
--#TYPE "Sentry: Tower Status Event."
--#SUMMARY "Status of Tower '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 1 }
-- Input Feed Traps
infeedStatusEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
infeedID,
infeedName,
infeedStatus
}
STATUS current
DESCRIPTION
"Input feed status event. If enabled, this trap is sent when
the infeedStatus indicates an error state ('offError',
'onError', or 'noComm'). This trap is repeated periodically
while the infeedStatus remains in an error state. If the
infeedStatus returns to a non-error state ('off' or 'on'),
this trap is sent once more with the non-error infeedStatus,
and then stops being repeated.
While the infeedStatus indicates an error state, load
traps are suppressed for the input feed, and, if the
infeedCapabilities 'failSafe' bit is FALSE, all status and
load traps are suppressed for outlets on the input feed."
--#TYPE "Sentry: Input Feed Status Event."
--#SUMMARY "Status of Input Feed '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 2 }
infeedLoadEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
infeedID,
infeedName,
infeedLoadStatus,
infeedLoadValue,
infeedLoadHighThresh
}
STATUS current
DESCRIPTION
"Input feed load event. If enabled, this trap is sent when
the infeedLoadStatus indicates an error state ('loadLow',
'loadHigh', 'overLoad', 'readError', or 'noComm'). This
trap is repeated periodically while the infeedLoadStatus
remains in an error state. If the infeedLoadStatus returns
to a non-error state ('normal' or 'notOn'), this trap is
sent once more with the non-error infeedLoadStatus, and then
stops being repeated."
--#TYPE "Sentry: Input Feed Load Event."
--#SUMMARY "Load Status of Input Feed '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 3 }
-- Outlet Traps
outletStatusEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
outletID,
outletName,
outletStatus
}
STATUS current
DESCRIPTION
"Outlet status event. If enabled, this trap is sent when the
outletStatus indicates an error state ('offError', 'onError',
'noComm', 'offFuse', or 'onFuse'). This trap is repeated
periodically while the outletStatus remains in an error state.
If the outletStatus returns to a non-error state ('off' or
'on'), this trap is sent once more with the non-error
outletStatus, and then stops being repeated.
While the outletStatus indicates an error state, load traps
are suppressed for the outlet."
--#TYPE "Sentry: Outlet Status Event."
--#SUMMARY "Status of Outlet '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 4 }
outletLoadEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
outletID,
outletName,
outletLoadStatus,
outletLoadValue,
outletLoadLowThresh,
outletLoadHighThresh
}
STATUS current
DESCRIPTION
"Outlet load event. If enabled, this trap is sent when the
outletLoadStatus indicates an error state ('loadLow',
'loadHigh', 'overLoad', 'readError', or 'noComm'). This
trap is repeated periodically while the outletLoadStatus
remains in an error state. If the outletLoadStatus returns
to a non-error state ('normal' or 'notOn'), this trap is
sent once more with the non-error outletLoadStatus, and then
stops being repeated."
--#TYPE "Sentry: Outlet Load Event."
--#SUMMARY "Load Status of Outlet '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 5 }
outletChangeEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
outletID,
outletName,
outletStatus,
outletControlState
}
STATUS current
DESCRIPTION
"Outlet on/off change event. If enabled, this trap is sent
when the outletStatus changes from any 'on' state ('on',
'onWait', 'onError', or 'onFuse') to any 'off' state ('off',
'offWait', 'offError', or 'offFuse'), and vice-versa."
--#TYPE "Sentry: Outlet Change Event."
--#SUMMARY "Outlet '%s' (%s) has changed to '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY INFORMATIONAL
--#GENERIC 6
--#CATEGORY "Status Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 6 }
-- Environmental Monitor Traps
envMonStatusEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
envMonID,
envMonName,
envMonStatus
}
STATUS current
DESCRIPTION
"Environmental monitor status event. If enabled, this trap
is sent when the envMonStatus indicates an error state
('noComm'). This trap is repeated periodically while the
envMonStatus remains in an error state. If the envMonStatus
returns to a non-error state ('normal'), this trap is sent
once more with the non-error envMonStatus, and then stops
being repeated.
While the envMonStatus indicates an error state, all status
traps are suppressed for the water sensor, ADC, temperature/
humudity sensors, and contact closures on the environmental
monitor."
--#TYPE "Sentry: Environmental Monitor Status Event."
--#SUMMARY "Status of Environmental Monitor '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 7 }
envMonWaterSensorEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
envMonID,
envMonWaterSensorName,
envMonWaterSensorStatus
}
STATUS current
DESCRIPTION
"Environmental monitor water sensor event. If enabled, this
trap is sent when the envMonWaterSensorStatus indicates an
error state ('alarm'). This trap is repeated periodically
while the envMonWaterSensorStatus remains in an error state.
If the envMonWaterSensorStatus returns to a non-error state
('normal'), this trap is sent once more with the non-error
envMonWaterSensorStatus, and then stops being repeated."
--#TYPE "Sentry: Water Sensor Event."
--#SUMMARY "Status of Water Sensor '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 8 }
envMonADCEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
envMonID,
envMonADCName,
envMonADCStatus,
envMonADCCount,
envMonADCLowThresh,
envMonADCHighThresh
}
STATUS current
DESCRIPTION
"Environmental monitor analog-to-digital converter event.
If enabled, this trap is sent when the envMonADCStatus
indicates an error state ('countLow' or 'countHigh'). This
trap is repeated periodically while the envMonADCStatus
remains in an error state. If the envMonADCStatus returns
to a non-error state ('normal'), this trap is sent once more
with the non-error envMonADCStatus, and then stops being
repeated."
--#TYPE "Sentry: ADC Event."
--#SUMMARY "Status of ADC '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 9 }
tempHumidSensorStatusEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
tempHumidSensorID,
tempHumidSensorName,
tempHumidSensorStatus
}
STATUS current
DESCRIPTION
"Temperature/humidity sensor status event. If enabled, this
trap is sent when the tempHumidSensorStatus indicates an
error state ('lost'). This trap is repeated periodically
while the tempHumidSensorStatus remains in an error state.
If the tempHumidSensorStatus returns to a non-error state
('found'), this trap is sent once more with the non-error
tempHumidSensorStatus, and then stops being repeated.
While the tempHumidSensorStatus indicates an error state, all
temperature and humidity status traps are suppressed for the
temperature/humudity sensor."
--#TYPE "Sentry: T/H Sensor Status Event."
--#SUMMARY "Status of T/H Sensor '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 10 }
tempHumidSensorTempEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
tempHumidSensorID,
tempHumidSensorName,
tempHumidSensorTempStatus,
tempHumidSensorTempValue,
tempHumidSensorTempLowThresh,
tempHumidSensorTempHighThresh,
tempHumidSensorTempScale
}
STATUS current
DESCRIPTION
"Temperature/humidity sensor temperature event. If enabled,
this trap is sent when the tempHumidSensorTempStatus
indicates an error state ('tempLow' or 'tempHigh').
This trap is repeated periodically while the
tempHumidSensorTempStatus remains in an error state. If
the tempHumidSensorTempStatus returns to a non-error state
('normal'), this trap is sent once more with the non-error
tempHumidSensorTempStatus, and then stops being repeated."
--#TYPE "Sentry: T/H Sensor Temperature Event."
--#SUMMARY "Temperature Status of T/H Sensor '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 11 }
tempHumidSensorHumidEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
tempHumidSensorID,
tempHumidSensorName,
tempHumidSensorHumidStatus,
tempHumidSensorHumidValue,
tempHumidSensorHumidLowThresh,
tempHumidSensorHumidHighThresh
}
STATUS current
DESCRIPTION
"Temperature/humidity sensor humidity event. If enabled,
this trap is sent when the tempHumidSensorHumidStatus
indicates an error state ('humidLow' or 'humidHigh').
This trap is repeated periodically while the
tempHumidSensorHumidStatus remains in an error state. If
the tempHumidSensorHumidStatus returns to a non-error state
('normal'), this trap is sent once more with the non-error
tempHumidSensorHumidStatus, and then stops being repeated."
--#TYPE "Sentry: T/H Sensor Humidity Event."
--#SUMMARY "Humidity Status of T/H Sensor '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 12 }
contactClosureEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
contactClosureID,
contactClosureName,
contactClosureStatus
}
STATUS current
DESCRIPTION
"Contact closure event. If enabled, this trap is sent when
the contactClosureStatus indicates an error state ('alarm').
This trap is repeated periodically while the
contactClosureStatus remains in an error state. If the
contactClosureStatus returns to a non-error state ('normal'),
this trap is sent once more with the non-error
contactClosureStatus, and then stops being repeated."
--#TYPE "Sentry: Contact Closure Event."
--#SUMMARY "Status of Contact Closure '%s' (%s) is '%d'."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
::= { events 13 }
END